Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
33
Network interface
3
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
3.4.5 Boiler 1
This section describes "boiler 1."
Burner OFF [0 %]
ON [> 0 %]
Current output [%]
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
27
System return actual
temperature
SNVT_temp_p(105)
nvoAnlRLIst_Tp
2
Tab. 75 Display of the currently-measured return temperature for the boiler system
28
Status burner 4000 boiler 1
SNVT_lev_cont (21)
nvoKS1_Br_4000
2
Tab. 76 Indicator for boiler 1 with Logamatic 4000 and third party burner
29
Temperature 4000 boiler 1 (FK)
actual
SNVT_temp_p(105)
nvoKS1VLIst_4000
2
Tab. 77 Display of the current boiler temperature for boiler 1 with Logamatic 4000 and third party
burner
30
Additional temperature 4000
boiler 1 (FZ) actual
SNVT_temp_p(105)
nvoKS1FZIst_4000 2
Tab. 78 Display of the measured temperature on the additional temperature sensor FZ in the
supply of boiler 1 with Logamatic 4000 and third party burner
31
Boiler hours of operation 4000
boiler 1 level 1
SNVT_time_hour(124)
nvoKS1Br4000S1_h 2
Tab. 79 Display of the hours of operation for the level 1 (basic load) of boiler 1 with
Logamatic 4000 and third party burner