Technical Information Logamatic LON-Gateway - Subject to modifications resulting from technical improvements!
21
Network interface
3
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
3.2.5 Floor-standing boilers
This section describes "floor-standing boiler 1."
For boiler 2, the details apply accordingly.
x = the bit is not used
Boiler with Logamatic EMS boiler output
Example:
Result: 64 + 32 + 4 = 100% (only evaluate second byte)
X - is not used
Note:
230 °F (110 °C) is an invalid value (e.g. no temperature sensor connected, sensor defective, etc.).
47
Status burner boiler 1
SNVT_state(83)
nvoKS1Br1Stufe1
2
Tab. 34 Display of the current burner level in operation and/or display of the current boiler output
for boilers with Logamatic EMS
Boiler with Logamatic 4000
Burner 1st level on
Burner 2nd level on / modulating
High byte
Low byte
High byte
Low byte
OFF
xxxx xxxx
0xxx xxxx
xxxx xxxx
x0xx xxxx
ON
xxxx xxxx
1xxx xxxx
xxxx xxxx
x1xx xxxx
Tab. 35
First byte
Second byte
Factor
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
Display
x
x
x
x
x
x
x
x
0
0
1
0
0
1
1
0
Tab. 36
49
Boiler supply temperature (FK) actual
SNVT_temp_p(105)
nvoKS1VLIst_Tp
2
Tab. 37 Display of the currently-measured supply temperature for a floor-standing multi-boiler
system