6
Fitting
Logano plus GB402 – 6 720 820 700 (2018/01)
17
6.2
Installing the condensate hose
▶ Remove the cap from the filler hole in the siphon supplied and fill with
approx. 2 litres of water.
▶ Fit elbow [4] with inserted gasket onto the filler hole.
▶ Fit the condensate hose from connector [3] with a hose clip to the
elbow.
▶ Fit the siphon to the outlet on condensate pan [2].
▶ Install neutralising systems (accessories) in accordance with the
installation instructions, either inside the boiler or on site.
▶ Connect the condensate hose from the siphon with a slope to the
neutralising system.
▶ Connect the condensate hose from the siphon with a slope to the
neutralising system.
Fig. 10 Installing the condensate hose
[1]
Neutralising system (accessory)
[2]
Condensate pan
[3]
Connection for condensate hose from the connector
[4]
Elbow, filler hole
[5]
Siphon outlet to condensate neutraliser or waste water pipe
[6]
Siphon
▶ Make the connection to the sewerage system in accordance with the
instructions of the neutralising system and locally applicable
regulations.
NOTICE:
Damage to gaskets due to burred edges on the
insertion ends of the pipe parts!
▶ Ensure that the insertion ends are free of burrs.
If chamfering on site is required, only in accordance
with the manufacturer's documentation.
Centrocerin (scope of delivery) must be used as a
lubricating paste for installing the flue system into the
connector.
DANGER:
Risk to life through toxic exhaust gases
escaping.
▶ Check the entire flue system for correctly made and
sealed joints.
Information regarding the condensate hose.
▶ Carefully drain the condensate created inside the
boiler and flue (route the flue with a slope towards
the boiler).
▶ Drain the condensate generated in the flue via the
boiler flue connection directly into the siphon inside
the boiler. Boiler flue connection, condensate drain
and hose are part of the standard delivery.
▶ Drain the condensate into the public sewerage
system in accordance with the requirements in your
country.
▶ Observe regional regulations.
DANGER:
Risk to life through poisoning! Open
connections or siphons not filled with water can cause a
through from escaping flue gas.
▶ Filling the siphon with water.
Neutralising systems are available as accessories and
can be fitted inside the boiler casing.
Where the neutralising system is installed outside the
boiler, there is the option of guiding the condensate hose
through the aperture in the back panel.
6 720 618 585-45.2T