2
Information on the device
Logano plus GB402 – 6 720 820 700 (2018/01)
10
Soot combustion resistance classification to be used
for flue system in accordance with EN 1443
G, O
G, O
G, O
G, O
G, O
Maximum permitted flue gas return flow under wind
conditions
%
10
10
10
10
10
Maximum permitted combustion air temperature
°C
35
35
35
35
35
Type (according to DVGW regulations)
Open flue operation: B
23
, B
23P
Balanced flue operation: C
13
, C
33
, C
43
, C
53,
C
63
, C
83
, C
93
Type (Belgium and Netherlands)
Open flue operation: B
23
, (B
23P
only valid for Belgium)
Balanced flue operation: C
13
, C
33
, C
43
, C
53,
(C
63
only valid for the Netherlands),
C
83
, C
93
Electrical details
IP rating
-
IPX0D
Supply voltage/frequency
V/Hz
230/50
Electric consumption power
[P(el)]
1)
Full Load
W
418
449
487
588
734
Partial load
W
39
45
42
45
49
Protection against electrocution
Safety category 1
Maximum permissible unit fuse protection
A
10
Appliance dimensions and weight
Handling dimensions width × depth × height
mm
781 x 1740 x 1542
Weight (excl. casing)
kg
410
438
465
493
520
1) The details [xxx] correspond to the symbols and formula signs used on the type plate.
2) Is to be ensured by means of system sizing, and it corresponds to a minimum differential between flow and return temperatures of 8 K.
Boiler size (output - no. of sections)
Unit
GB402-320 - 5 GB402-395 - 6 GB402-470 - 7 GB402-545 - 8 GB402-620 - 9
Table 4 Specifications
Boiler size
Natural gas E, H, Es
(G20)
Natural gas L (DE)
Natural gas LL, L, Ei
(G25)
Natural gas Lw (G27)
(PL)
Natural gas S (G25.1)
(HU)
Wobbe index
14.9 kWh/m
3 1)
Wobbe index
12.8 kWh/m
3
1)
Wobbe index
12.2 kWh/m
3 1)
Wobbe index
11.4 kWh/m
3 1)
Wobbe index
11.5 kWh/m
3 1)
Gas throughput
Gas throughput
Gas throughput
Gas throughput
Gas throughput
[m
3
/h]
[m
3
/h]
[m
3
/h]
[m
3
/h]
[m
3
/h]
320 -5
32.3
34.3
37.6
–
–
395 -6
39.8
42.4
46.4
48.5
46.2
470 -7
47.4
50.4
55.2
57.8
55.0
545 -8
55.0
58.4
64.0
67.1
63.9
620 -9
62.5
66.5
72.8
76.2
72.6
Table 5 Gas throughput (relative to 15 °C gas temperature and 1013 mbar air pressure)
1) Upper Wobbe index for 0 °C, 1013 mbar
Country
Boiler size
Nominal gas
pressure [mbar]
Gas category
Gas family, gas group and reference gas
set on delivery
Set to rated gas pressure on
delivery [mbar]
1)
EN 320-620
20
I
2ELL
2E, G20
20
AT, BY, CH, CZ,
DK, EE, ES, GB,
HR, IE, IT, LT, LV,
PT, RO, RS, RU,
SI, SK, TR, UA
320-620
20
I
2H
2H, G20
20
Table 6 Country-specific gas categories and supply pressures