Technical data sheet:  S000092412EN-1 

Updated: 

Created: 02/06/2016

Cat No(s): LN4691KNX - H4691KNX

KNX temperature control panel

  1. USE

Combined with a KNX room temperature controller (with an embedded 

temperature control algorithm), the KNX temperature control panel is 

used to manage the heating/cooling control system (fan coil control 

unit, heating/cooling valve, electrical load, etc) in the rooms where it is 

installed, and can be configured for different applications as required. 

The temperature control panel incorporates a user interface and a 

temperature sensor.
This device is completely configurable in term of parameters, operating 

modes and other features. Depending on the type of use, the backlit 

display will show the following information: the current function or 

mode (Heating, Cooling; Comfort, Eco, Frost/Overheat Protection), the 

measured room temperature, the defined temperature setpoint, the 

fan coil speed. It is a native KNX device and all the configurations and 

associations must be made via ETS software (ETS versions 3, 4 and 5) 

only.

  2. DESCrIPTION

1 2

3 4 5

6

MODE

FAN

7

8

9

13

12

11 10

14

15

+

-

1 - Heating mode.
2 - Cooling mode.
3 - Comfort mode.
4 - Eco mode.
5 - Frost/Overheat protection.
6 -  MODE key: A short press changes the device operating mode;  

a long press changes the function.

7 - + key: increases the set value.
8 - – key: decreases the set value.
9 - FAN key: sets the fan-coil speed to one of 3 automatic.
10 - Heating On indicator.
11 - Cooling On indicator.
12 - Fan coil speed indicator, 3 levels.
13 - Fan coil in automatic mode indicator.
14 -  Measured temperature (thermometer symbol On)/set temperature 

(thermometer symbol Off) indicator.

15 - Unit of measurement: °C or °F.

  3. TEChNICal CharaCTErISTICS

3.1  Electrical characteristics

-  KNX BUS current consumption: 6 mA (OFF) / 9 mA (Backlight min ) /  

16 mA (Backlight max)

- KNX BUS power supply: 29 V =
-  KNX connector (red/black): terminal capacity 4x (Ø 0.6 to 0.8 mm) 

3.2  Climatic characteristics

- Environmental operating temperature: -0°C to +40°C
- Storage temperature: -25°C to +70°C

3.3  Mechanical characteristics

- Impact resistance: IK04
- Penetration by solid and liquid matter: IP20
-Weight: 40 g

LED

Prog and Reset

  4. DIMENSIONS

37

47

45

37

45

45

Содержание H4691KNX

Страница 1: ... 3 3 Mechanical characteristics 2 4 Dimensions 2 5 Connection 3 6 Installation 3 6 1 Physical installation 3 6 2 System installation 3 7 Operating modes 3 8 System applications 3 8 1 Heating application 3 8 2 Cooling application 3 8 3 Heating and Cooling application 3 9 Settings 4 9 1 Display during installation 4 9 2 Display during use 4 10 Standards and approvals 5 11 Maintenance 5 12 Communicat...

Страница 2: ... associations must be made via ETS software ETS versions 3 4 and 5 only 2 Description 1 2 3 4 5 6 MODE FAN 7 8 9 13 12 11 10 14 15 1 Heating mode 2 Cooling mode 3 Comfort mode 4 Eco mode 5 Frost Overheat protection 6 MODE key A short press changes the device operating mode a long press changes the function 7 key increases the set value 8 key decreases the set value 9 FAN key sets the fan coil spee...

Страница 3: ...ve Cooling application only cooling is active Cooling and Heating application 8 1 Heating application If the measured temperature is lower than the reference value the heating system is activated and the corresponding symbol appears on the display When the temperature is reached the control panel switches the zone off and the icon disappears Note The heating icon is always displayed 8 2 Cooling ap...

Страница 4: ...tinued 9 2 Display during use Ambient temperature and or setpoint MODE FAN MODE FAN MODE FAN MODE FAN MODE FAN MODE FAN MODE FAN MODE FAN A With ETS you can choose to display the setpoint the thermometer icon is not shown and or the ambient temperature the thermometer icon is shown The temperature unit of measurement is C or F and can be chosen via a communication object A short press on the Mode ...

Страница 5: ...X H4691KNX comply with Directive 2014 53 EU The full text of the EU declaration of conformity is available at the following internet address www bticino com 11 Maintenance Clean the surface with a cloth Do not use acetone tar removing cleaning agents or trichloroethylene Caution Always test before using other special cleaning products Note All technical information is available at NFC compatible A...

Страница 6: ...21 C In the event of a power cut the value is saved and restored when the power returns 5 Heating Cooling Temperature setpoint limit high 9 001 2 Bytes CW Highest limit for the temperature setpoint received from the bus Default value 35 C In the event of a power cut the value is saved and restored when the power returns 6 Heating Cooling Temperature setpoint limit low 9 001 2 Bytes CW Lowest limit...

Страница 7: ... open or Heating valve open received from the bus Default value 0 17 Heating Cooling Heating valve status 1 002 1 bit CW Heating valve open received from the bus Only in 4 tube installations 1 Heating valve open 0 Heating valve closed default value 18 Heating Cooling Cooling Heating Cooling valve status 1 002 1 bit CW In 4 tube installation Cooling valve open received from the bus In 2 tube instal...

Страница 8: ...n speed off default value 27 Fan Fan Speed 2 status 1 002 1 bit CW Fan speed 2 received by the bus Only if 1 bit Fan function is active 1 Fan speed 2 0 Fan speed off default value 28 Fan Fan Speed 3 status 1 002 1 bit CW Fan speed 3 received by the bus Only if 1 bit Fan function is active 1 Fan speed 3 0 Fan speed off default value 29 Information Window status 1 002 1 bit CW Window status received...

Страница 9: ...it will automatically switch the backlight to normal mode after a button is pressed it will revert to ECO after 30 s of inactivity 12 COMMUNICATION OBJECTS CONTINUED 12 2 ETS parameters continued Activate standby mode With this parameter you can decide whether or not to use the standby display mode monitor switch OFF If YES you will then be able to switch between normal and standby display mode by...

Страница 10: ...for valve With this parameter you can choose the type of object 1 bit or 1 byte to communicate the status of the heating cooling valve s The choice must be the same as for the actuator 1 bit objects 15 16 are not active objects 17 18 are active 1 byte objects 17 18 are not active objects 15 16 are active Add Object HVAC mode If yes object 8 HVAC mode is active Add Object HVAC Status If yes object ...

Отзывы: