Product Introduction
4
User Manual CPM PI2066en Rev.B
© BTG 2019
1.2 Technical Data
General
Type
CPM Communication Platform.
Manufacturer
BTG, Säffle, Sweden.
Quality Assurance
Quality-assured in accordance with ISO 9001.
Product Safety
Fulfills all relevant CE-directive requirements and all Australian TIC requirements.
Function Specifications
Communication Modules:
HCM-8000/8010
Hart communication module using HART
®
protocol.
Equipped with slot for SD memory card.
Analog output (AO1- AO5)
4 - 20 mA. Galvanic isolated. Current limited to min. 3.9 and max. 20.5 mA.
Loop load signal: Voltage supply/load 24 V DC
Active or passive output for HCM-8000
Active output only for HCM-8010
Superimposed signal over 4 - 20 mA current loop according to standard HART
®
protocol.
Analog input (AI1 - AI4)
4 - 20 mA 250
Ω
input resistance
Digital input (DI1 - DI4)
Galvanic isolated
High-ohmic = logical 0
+24 V
≥
12 mA = logical 1
Digital output (DO1 - DO2)
Galvanic isolated
Maximum 120 mA
Maximum 30 V DC
Solenoid valve (SV1 - SV5)
Open drain output for solenoids
Maximum 500 mA
Maximum 30 V DC
FCM-8000/8010
Fieldbus communication module programmed for PROFIBUS.
Equipped with slot for SD memory card.
Output / Input signal
PROFIBUS (PA)
User Interface
Illuminated display. Key pad for adjustment of instrument settings.
Содержание CPM 1300
Страница 1: ...User Manual CPM Communication Platform ...
Страница 32: ...Service Instructions 28 User Manual CPM SI2066en Rev A BTG 2019 ...
Страница 43: ......
Страница 44: ...BTG Instruments AB P O Box 602 SE 661 29 Säffle Sweden Phone 46 533 426 00 www btg com ...