background image

Operating Manual

Flame Detector KLC 20 / KLC 21

 

Содержание FLAMONITEC KLC 21

Страница 1: ...Operating Manual Flame Detector KLC 20 KLC 21...

Страница 2: ...ing 10 2 5 1 Fundamental aspects 10 2 5 2 Electrical electronic devices 11 2 5 3 Inspection in accordance with the Ordinance on Industrial Safety and Health 11 2 5 4 Safety test 11 3 Technical data 12...

Страница 3: ...Relay module for flame detectors RMF 1 19 6 Operation of the flame detektor 20 6 1 Test of the flame detektor 20 6 2 Operating indicator LED 20 6 3 Diagnostic with KLC Com 20 7 Maintenance and servici...

Страница 4: ...are used in these operating instructions DANGER This warning level indicates an imminent hazardous situation If the hazardous situation is not prevented this will result in death or severe injury Fol...

Страница 5: ...or with operating instructions based on existing national regulations for accident pre vention and environmental protection including information on supervisory and reporting obli gations to take acco...

Страница 6: ...this person has the authority to overrule any unsafe instructions of third parties 1 7 Liability disclaimer All technical information data and guidance on device operation that are contained within th...

Страница 7: ...RMF1 Product Flame detector KLC2x with or without RMF1 Typ KLC20 KLC21 KLC22 KLC2002 mit oder ohne RMF1 Type KLC20 KLC21 KLC22 KLC2002 with or without RMF1 Hiermit erkl ren wir dass der nachstehend b...

Страница 8: ...ted to carry out work on the device Connection set up maintenance and repair work may only be carried out by qualified spe cialist staff This device may cause hazards if it is operated inappropriately...

Страница 9: ...ately notify the appropriate authority person of any changes that occur including changes in operating performance If necessary stop and secure the device imme diately Allow only authorised specialist...

Страница 10: ...he replacement of parts assemblies have to be ob served These tasks may only be carried out by authorised specialist staff Operating staff have to be informed before maintenance or other special work...

Страница 11: ...cal specialists NOTICE To ensure proper operation the flame detector must be tested several times in all applications by starting and stopping the burner several times The flame relay must switch off...

Страница 12: ...ent max switching power max switching voltage 15 mA 0 3 W 280 V AC 400 V DC Input 230 240 V AC 50 60 Hz 120 V AC optional 24 V AC DC optional Consumption max 6 mA Operating temperature KLC 20 KLC 21 2...

Страница 13: ...LAME DETECTOR KLC 20 KLC 21 Page 13 TECHNICAL DATA 3 3 Weight Weight approx 0 029 kg 3 4 Dimensions Length with plug 115 mm Width 30 mm Height 22 mm Dimensional drawing see under point 4 4 3 5 Block d...

Страница 14: ...efer to our terms of sale and delivery otherwise Report any damage After arrival of the device and accessories notify the shipping agent the insurance company and BST Solutions immediately in case of...

Страница 15: ...ng materials are cardboard and plastics foils foamed material 4 3 Shipping instructions 4 4 Dimensions see the following illustration Packaging has to be disposed of in an environmentally friendly way...

Страница 16: ...The angle of view especially with sight tubes must be of appropriate dimensions to avoid any reduction of flame radiation Protect the sensor against other light sources To prevent faults the direct v...

Страница 17: ...ed With maintenance work the reflector surface should be protected from possible contamination and if necessary it is to clean with a clean soft and lint free cloth 4 5 3 Adapter ADP The ADP adapter m...

Страница 18: ...e storage room is dry during storage Protect from direct sunlight Storage temperature 20 to 60 C Store dust free Avoid mechanical shocks and damage Danger to life caused by electrical current When con...

Страница 19: ...FF The KLC 20 KLC 21 activates its self test function during power up Therefor the flame de tector is approved for intermittend operation For safety reasons and technical regulations a controlled burn...

Страница 20: ...C 20 KLC 21 is indicating the following operating conditions 6 3 Diagnostic with KLC Com With the data interface KLC Com consisting of optical adapter with cable USB Interface and software BST Com the...

Страница 21: ...eck of the flame monitoring must be carried out during commissioning and every maintenance of the combustion system The following steps should be checked During start up of the BMS the flame detector...

Страница 22: ...s an the connetions of the burner controller box Power off the KLC and take it out of the flange Now clean the glass carefully with a clean and fuzz free cloth Exchange the KLC No communication with l...

Страница 23: ...t off DFC 611120110215 Flame detector KLC20 24 25 15Hz DFC axial with disturbing frequency cut off DFC 611320110212 Flame detector KLC20 24 52 15Hz DFC axial with disturbing frequency cut off DFC 6113...

Страница 24: ...applications 615001020000 Angle adapter KLC stainless steel mirror Accessory for radial mounting applications 615001030000 ADP 10 UV Adapter KLC heat insulating up to 180 C R quartz glass 57501051211...

Страница 25: ...BST Solutions GmbH Ruegenstr 7 D 42579 Heiligenhaus Germany T 49 2056 98947 0 info amonitec bst com www amonitec bst com Subject to technical changes BST Solutions 2021 MEMBER OF MINDERMANN GROUP...

Отзывы: