background image

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . .

1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6

I. Select Thermostat Location

. . . . . . . . . . . . . . . .

1

II. Install Thermostat

. . . . . . . . . . . . . . . . . . . . . . . .

2

III. Set Clock

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

IV. Heat Pump Configuration

. . . . . . . . . . . . . . . . . .

3

V. Configure Advanced Setup

. . . . . . . . . . . . . . . . .

3

VI. Install Accessories

. . . . . . . . . . . . . . . . . . . . . . . .

4

VII. Program Thermostat Schedules

. . . . . . . . . . . . .

4

VIII. Calibrate Temperature Sensor

. . . . . . . . . . . . . .

6

IX. Light Sensor Adjustment

. . . . . . . . . . . . . . . . . .

6

X. Check Thermostat Operation

. . . . . . . . . . . . . . .

6

XI. Final Checklist

. . . . . . . . . . . . . . . . . . . . . . . . . . .

6

OPERATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

I. Auto-Changeover

. . . . . . . . . . . . . . . . . . . . . . . . .

7

II. Light-Activated Operation

. . . . . . . . . . . . . . . . . .

7

III. Two-Stage Operation

. . . . . . . . . . . . . . . . . . . . . .

7

IV. Clock Backup

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

V. Fan Operation

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

VI. Emergency Heat

. . . . . . . . . . . . . . . . . . . . . . . . . .

7

VII. Electric Heat

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

VIII. Holiday Mode

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

IX. Keypad Lock

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

IMPORTANT:

Read entire instructions before starting the

installation.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow
all local electrical codes during installation. All wiring must
conform to local and national electrical codes. Improper wir-
ing or installation may damage thermostat.

Recognize safety information. This is the safety alert sym-
bol

. When the safety alert symbol is present on equip-

ment or in the instruction manual, be alert to the potential
for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety alert symbol.
DANGER identifies the most serious hazards which will
result in severe personal injury or death. WARNING signi-
fies a hazard which could result in personal injury or death.
CAUTION is used to identify unsafe practices which would
result in minor personal injury or property damage.

GENERAL

The 7-day, commercial, programmable thermostats are wall-
mounted, low-voltage thermostats which maintain room tem-
perature by controlling the operation of an HVAC (heating,
ventilation, and air-conditioning) system. Separate heating
and cooling set points and auto-changeover capability allow
occupied and unoccupied programming for energy savings.

All thermostats allow up to 4 time/temperature settings to
be programmed per 24-hour period. Each thermostat stores
programs for 7 independent days. Batteries are not required.
During power interruption the internal NEVERLOST™
memory stores programmed schedules for an unlimited time
while the clock continues to run for at least 48 hours.

The thermostat can be configured to accept several different
equipment configurations, including heat pump operation.

NOTE:

The thermostat is not factory-configured for use in

heat pump applications. The advanced setup must be per-
formed to configure the thermostat for use with heat pump
units.

A light sensor is provided on the thermostat for light
activation. When the sensor detects light (the space is
occupied), the thermostat will enter Occupied 1 mode. If
the room is dark, the thermostat will follow its programmed
schedule.

INSTALLATION

I. SELECT THERMOSTAT LOCATION

The thermostat should be mounted:

• approximately 5 ft from the floor
• close to or in a frequently used room, preferably on an in-

side partitioning wall

• on a section of wall without pipes or ductwork
• where temperature operating limits are within 41 to 104 F

(5 to 40 C)

• where humidity operating range is within 0 to 95% rela-

tive humidity, non-condensing

The thermostat should NOT be mounted:

• close to a window, on an outside wall, or next to a door

leading to the outside

• where exposed to direct light and heat from a lamp, the

sun, a fireplace, or any other temperature-radiating object
which may cause a false reading

• close to or in direct airflow from supply registers or return

air grilles

• in areas with poor air circulation (such as behind a door or

in an alcove)

installation, start-up and
service instructions

TEMPSURE COMMERCIAL THERMOSTAT
(P/N TSTATBBP220-LA)

Cancels: New

II TSTAT-8

11/1/98

Содержание TEMPSURE COMMERCIAL THERMOSTAT P/N TSTATBBP220-LA

Страница 1: ...e heating and cooling set points and auto changeover capability allow occupied and unoccupied programming for energy savings All thermostats allow up to 4 time temperature settings to be programmed pe...

Страница 2: ...where marked WARNING Be careful not to drill into wiring in wall Electrical shock could result 7 Secure mounting base to wall with 2 screws and anchors provided Ensure all wires exit through hole in...

Страница 3: ...right corner of the thermostat screen Use the Mode button to advance through the steps There are 15 Advanced Setup Steps See Table 2 Press the Program button at any time to exit the Advanced Setup mod...

Страница 4: ...ram On mode is always in effect and set point changes are prohib ited The default is 0 Security Maximum Heat Set Point Step 14 If the Security Level is not set to 0 the maximum heating set point will...

Страница 5: ...s are M Monday through S Sunday Press the Mode button when the desired day is shown 7 The Start Time for Occupied 1 will be displayed Use the UP ARROW and DOWN ARROW buttons to raise or lower the time...

Страница 6: ...screw is located on the inner cover of the thermostat near the DOWN ARROW button Turning the screw clockwise increases the sensitivity of the sensor to light Turning the screw counterclockwise decrea...

Страница 7: ...r cooling operation VI EMERGENCY HEAT Emergency heat is available for heat pump applications To turn on emergency heat press and hold the Fan button While holding the Fan button press the UP button fo...

Страница 8: ...oblem is with wiring or equip ment If 24 vac is not present replace the thermostat When using 4 wires R G W Y the cooling equip ment tries repeatedly to turn on but cannot At times the display dims or...