T2SNAC01, T2SNHP01

NON--PROGRAMMABLE THERMOSTAT

Installation Instructions

A08148

NOTE

: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform

to local and national electrical codes. Improper wiring or
installation may damage thermostat.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard
which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight
suggestions which

will

result in enhanced installation, reliability, or

operation.

Power

Note that all thermostats are dual powered where batteries can be
installed or in the presence of R and C (24vac) are not required.

Two AA batteries are furnished with the product.

Models

There are 2 different models. The 5th and 6th letters of the part

number indicate the model. These 2 letters also appear on the
package and on the circuit board. Be sure to have the proper

thermostat for the intended application. Models are:
AC -- 1--stage cool, 1--stage heat for AC systems only.
HP -- 1--stage cool, 2--stage heat for either HP, or AC with 2--stage
heat.
Use each only for its intended purpose. See Table 1.

INSTALLATION

Thermostat Location

Thermostat should be mounted:

S

Approximately 5 ft. (1.5m) from floor.

S

Close to or in a frequently used room, preferably on an inside
partitioning wall.

S

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

S

Close to a window, on an outside wall, or next to a door leading
to the outside.

S

Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature--radiating object which may cause a false
reading.

S

Close to or in direct airflow from supply registers and return--air
grilles.

S

In areas with poor air circulation, such as behind a door or in an
alcove.

Select Model

AC Model

(1--stage cool, 1--stage heat) is to be used for single stage heating
and/or cooling applications only.

HP Model

(1--stage cool, 2--stage heat) can be used with a single--speed heat

pump (HP), or an air conditioner (AC) with a 2--stage furnace or
fan coil. Software Option 5 selects HP/AC operation. This

thermostat comes configured from the factory as a heat pump
thermostat. Select AC in software Option 5 for AC operation.

Содержание T2SNAC01

Страница 1: ...els There are 2 different models The 5th and 6th letters of the part number indicate the model These 2 letters also appear on the package and on the circuit board Be sure to have the proper thermostat...

Страница 2: ...1 4 6mm of extra wire Strip only 1 4 6mm of insulation from each wire to prevent adjacent wires from shorting together when connected 8 Match and connect equipment wires to proper terminals of the con...

Страница 3: ...able Option 02 values of OF and 1 through 9 Factory default is 2 5 Press MODE button again to return to Option 02 The SET icon will now be off 6 Use up and down buttons to select another Option or pre...

Страница 4: ...not already there 2 Use up and down buttons to display Option 15 The SET icon should be off 3 Press MODE button once The SET icon will come on The display now shows Option 15 setting 4 Use up and down...

Страница 5: ...ee then first and second stages if a second stage exists will turn on for three minutes 4 If the mode is set to EHEAT auxiliary heat turns on for three minutes then the mode returns to OFF Terminating...

Страница 6: ...k the furnace into low heat operation and let O B control high heat operation Refer to indoor equipment Installation Instructions for proper setup 4 O B can control second stage heat Refer to indoor e...

Страница 7: ...shing the equipment is temporarily prevented from turning on by one of the timers see above While the icon remains on without flashing the equipment is on Power On Check When AC power is first applied...

Страница 8: ...change at any time specifications or designs without notice and without incurring obligations E2008 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in China Edition...

Страница 9: ...splayed when the cooling equipment is operating HEAT ON Indicator is displayed when the heating equipment is operating RESET FILTER Button restarts the timer that calculates the next air filter change...

Страница 10: ...D display means there is not enough voltage for the system to operate Contact your dealer for further information If the outdoor air temperature sensor is absent the outdoor temperature reading will b...

Отзывы: