
13
Fig. 18 — Separating Coil Sections
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal manner.
7. Secure inner and outer coil rows together with a field-sup-
plied fastener.
8. Reposition the outer coil section and remove the coil cor-
ner post from between the top panel and center post. Rein-
stall the coil corner post and replace all screws.
TOTALINE ENVIRONMENTALLY SOUND COIL
CLEANER APPLICATION EQUIPMENT
• 2
1
/
2
gallon garden sprayer
• Water rinse with low velocity spray nozzle
TOTALINE ENVIRONMENTALLY SOUND COIL
CLEANER APPLICATION INSTRUCTIONS
1. Proper eye protection such as safety glasses is recom-
mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum
cleaner as described above.
3. Thoroughly wet all finned surfaces with clean water and a
low velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally sound coil cleaner in a
2
1
/
2
gallon garden sprayer according to the instructions
included with the cleaner. The optimum solution tempera-
ture is 100°F.
NOTE: Do NOT USE water in excess of 130°F, as the enzymatic
activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound coil
cleaner solution to all coil surfaces including finned area,
tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and apply
cleaner with a vertical, up-and-down motion. Avoid spraying
in horizontal pattern to minimize potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas. Interior and exterior finned areas must be thor-
oughly cleaned. Finned surfaces should remain wet with
cleaning solution for 10 minutes. Ensure surfaces are not
allowed to dry before rinsing. Reapply cleaner as needed
to ensure 10 minute saturation is achieved.
8. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray noz-
zle. Protect fins from damage from the spray nozzle.
Evaporator Coil
CLEANING THE EVAPORATOR COIL
1. Turn unit power off. Install lockout tag. Remove evapora-
tor coil access panel.
2. If economizer or two-position damper is installed, remove
economizer by disconnecting Molex plug and removing
mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results, back-
flush toward return-air section to remove foreign material.
Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
THERMOSTATIC EXPANSION VALVE (TXV)
All 581J units have a factory-installed nonadjustable thermo-
static expansion valve (TXV). The TXV will be a bi-flow,
bleed port expansion valve with an external equalizer. TXVs
are specifically designed to operate with Puron
®
or R-22 re-
frigerant. Use only factory authorized TXVs. Do not inter-
change Puron and R-22 TXVs.
TXV Operation
The TXV is a metering device that is used in air conditioning
and heat pump systems to adjust to the changing load condi-
tions by maintaining a preset superheat temperature at the out-
let of the evaporator coil.
The volume of refrigerant metered through the valve seat is de-
pendent upon the following:
1. Superheat temperature is sensed by cap tube sensing bulb
on suction tube at outlet of evaporator coil. This tempera-
ture is converted into pressure by refrigerant in the bulb
pushing downward on the diaphragm, which opens the
valve using the push rods.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit
performance or unit shutdown.
High velocity water from a pressure washer, garden hose,
or compressed air should never be used to clean a coil. The
force of the water or air jet will bend the fin edges and in-
crease airside pressure drop.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in accelerated cor-
rosion of unit parts.
Harsh chemicals, household bleach or acid or basic clean-
ers should not be used to clean outdoor or indoor coils of
any kind. These cleaners can be very difficult to rinse out of
the coil and can accelerate corrosion at the fin/tube inter-
face where dissimilar materials are in contact. If there is
dirt below the surface of the coil, use the Totaline environ-
mentally balanced coil cleaner.
Содержание Preferred 581J04-14
Страница 36: ...36 Fig 60 Integrated Gas Control IGC Board RED LED STATUS ...
Страница 44: ...44 Fig 65 RTU Open Overlay for Economizer Wiring ...
Страница 45: ...45 Fig 66 VFD Overlay for W2770 Controller Wiring ...
Страница 96: ...96 Fig B 581J 04 06 YAC Control Diagram 208 1 60 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 99: ...99 Fig E 581J 07A B C YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 100: ...100 Fig F 581J 08 09 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 101: ...101 Fig G 581J 11YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 102: ...102 Fig H 581J 12 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 103: ...103 Fig I 581J 04 06 YAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Страница 104: ...104 Fig J 581J 04 06 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 105: ...105 Fig K 581J 04 06 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 106: ...106 Fig L 581J 07 12D F YAC Power Diagram 208 230 3 60 460 3 60 6 Ton 2 Stage with Cooling APPENDIX D WIRING DIAGRAMS ...
Страница 108: ...108 Fig N 581J 07 12A B C YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 109: ...109 Fig O 581J 07 12A B C YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 110: ...110 Fig P 581J 08 09 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 111: ...111 Fig Q 581J 08 09 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 112: ...112 Fig R 581J 11 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 113: ...113 Fig S 581J 11 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 114: ...114 Fig T 581J 11 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 115: ...115 Fig U 581J 12 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 116: ...116 Fig V 581J 12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 117: ...117 Fig W 581J 14 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 118: ...118 Fig X 581J 14 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 119: ...119 Fig Y 581J 14 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 120: ...120 Fig Z 581J 14 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Страница 121: ...121 Fig AA 581J 04 06 YAC Control Diagram 230 1 60 230 460 575 3 60 with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 122: ...122 Fig AB 581J 07A B C YAC Control Diagram 230 1 60 230 460 575 3 60 with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 123: ...123 Fig AC 581J 08 09 YAC Control Diagram 230 460 575 3 60 with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 124: ...124 Fig AD 581J 11 YAC Control Diagram 230 1 60 230 460 575 3 60 with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 125: ...125 Fig AE 581J 12 YAC Control Diagram 230 460 575 3 60 with Dehumidification APPENDIX D WIRING DIAGRAMS ...
Страница 126: ...126 Fig AF 581J 04 06 YAC Power Diagram 208 230 1 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 127: ...127 Fig AG 581J 04 06 YAC Power Diagram 230 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 128: ...128 Fig AH 581J 04 06 YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 129: ...129 Fig AI 581J 07A B C YAC Power Diagram 230 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 130: ...130 Fig AJ 581J 07A B C YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 131: ...131 Fig AK 581J 08 09 YAC Power Diagram 230 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 132: ...132 Fig AL 581J 08 09 YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 133: ...133 Fig AM 581J 11 YAC Power Diagram 208 230 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 134: ...134 Fig AN 581J 11 YAC Power Diagram 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 135: ...135 Fig AO 581J 11 YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 136: ...136 Fig AP 581J 12 YAC Power Diagram 230 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 137: ...137 Fig AQ 581J 12 YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 138: ...138 Fig AR 581J 14 YAC Control Diagram 230 460 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 139: ...139 Fig AS 581J 14 YAC Power Diagram 208 230 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 140: ...140 Fig AT 581J 14 YAC Power Diagram 460 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 141: ...141 Fig AU 581J 14 YAC Power Diagram 575 3 60 with Perfect Humidity System APPENDIX D WIRING DIAGRAMS ...
Страница 142: ...142 Fig AV YAC Direct Digital System Control Wiring Diagram System 50HE500891 F APPENDIX D WIRING DIAGRAMS ...
Страница 143: ...143 Fig AW RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...