background image

: Advanced Installation and Configuration Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

3

Wiring Diagrams

Conventional System

For single stage heat and single stage cooling applications, 5 wires are required instead of the traditional 4.

A200455

A common wire to power is needed to power the thermostat. Additional wires are shown as dotted lines for 2-stage equipment.
Most Bryant 2 stage furnace equipment can be operated with a single stage thermostat using the algorithm in the furnace circuit board to engage 2nd

stage. While a 2-stage thermostat can control the equipment, it is preferred to allow the Bryant equipment to determine the staging by not connecting

W2. See furnace installation instructions for heat staging setup.

Power Extender Kit (PEK) 

The Power Extender Kit, also known as the PEK, allows the thermostat to operate with 4 wires instead of 5, which helps with retrofit applications. The

thermostat has a PEK terminal which digitally combines the G and Y1 signal. The PEK device, which gets installed at the equipment, separates that

combined signal back into separate 24v wires.
The PEK can go from 5 to 6 wires or from 8 to 9 wires. It can always add one more wire to the available wires. The 4 wires at the thermostat should be

wired as shown above. Additional wires would bypass the PEK and connect directly to the equipment.

Photo credit: ecobee

A200456

A200457

Содержание EB-STATE3LTBB-01

Страница 1: ...or ERV Also the thermostats can be installed with the PEK if a C wire isn t present Additionally the thermostats can control boilers with or without an AC When connected to a boiler the thermostats s...

Страница 2: ...ntify the final assembly number model name country of origin and device serial number A210086 The following final assembly numbers and corresponding model name are as follows c Table 1 Final Assembly...

Страница 3: ...mostat can control the equipment it is preferred to allow the Bryant equipment to determine the staging by not connecting W2 See furnace installation instructions for heat staging setup Power Extender...

Страница 4: ...dd a Wire Kit works similar to the PEK Normally this would not be needed because the PEK comes with the ecobee However the PEK is limited to one extra wire and only one PEK can be used per system Seve...

Страница 5: ...g valve During the startup process the O B should be configured to act as an O terminal with Bryant equipment since the equipment defaults to heating and needs the reversing valve to be energized on a...

Страница 6: ...ion and Configuration Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Air Conditioner with Boiler A200461 Boiler...

Страница 7: ...bee PEK Venstar Add a Wire or Fast Stat Wiring Extender accessories mentioned above cannot be used The W call gets piggy backed on the common wire with the small black sender module installed at the t...

Страница 8: ...ct variable speed furnaces The ACC terminal will wire to the DH or DHUM terminal on the equipment in these applications On the FV fan coils remove jumper J1 from the Easy Select board to enable this f...

Страница 9: ...mer and so only Rc is connected It is important to note that in these applications Rc must be used instead of Rh like some Bryant thermostats If the heating and cooling equipment have separate transfo...

Страница 10: ...made here Start Up Dehum for Fan Coil or Furnace Initial Start Up Wiring Standard A200469 During installation the thermostat will automatically detect which terminals have wires connected If something...

Страница 11: ...entilator Initial Start Up Wiring Accessory Dehumidifier for Fancoil or Furnace A200471 When selecting dehumidifier for using the equipment s DHUM or DH terminal select the appropriate relay action A...

Страница 12: ...e auxiliary heat is electric resistance then shut off the compressor when either a The manufacturer has a published lowest operating temperature for example our 5 stage inverters can only run down to...

Страница 13: ...y the fan on a W1 allowing the heat exchanger to warm up before engaging airflow so the occupants do not get a blast of cold air This setting only affects the gas heat startup sequence it will not del...

Страница 14: ...latent capacity of the evaporator coil while reducing sensible capacity Installation Settings Thresholds Cool Dissipation A200478 Cool Dissipation Time is default on but the feature should only be us...

Страница 15: ...to 76 degrees the 2nd stage will come on Then both will run together until the room temperature is satisfied at 74 Reverse staging works example If there is a 74 degree cooling setpoint the 1st stage...

Страница 16: ...200482 The Auxiliary Heat Maximum Outdoor Temperature specifies when the heat pump should be able to handle the heating load solo without the need for auxiliary electric heat to assist Aux heat will b...

Страница 17: ...the thermostat the maximum difference allowed between the thermostat and hottest or coldest rooms in the home If a sensor measures a temperature that is significantly outside of this range it probabl...

Страница 18: ...and the sensor stops detecting occupancy the thermostat s temperature data is gradually and not immediately removed from the calculation A200488 Each sensor can be used with a Comfort Setting Home Aw...

Страница 19: ...nd without obligations 19 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe in providing...

Страница 20: ...pany Edition Date 04 21 Catalog No II EBSTATE 02 Replaces II EBSTATE 01 Advanced Installation and Configuration Instructions Manufacturer reserves the right to change at any time specifications and de...

Отзывы: