background image

48

2-Pipe and 1-Pipe Vent Termination

NOTE

:  Follow the instructions of the vent terminal manufacturer.

These instructions are provided as a reference, only.

RECOMMENDED SUPPORT FOR VENT

TERMINATIONS

It is recommended that sidewall vent terminations in excess of

24 inches (0.6 M) in vertical length be supported by 

EITHER

the Direct Vent Termination Kit shown in Table 13 or by

field

supplied brackets or supports fastened to the structure.

NOTICE

Determine an appropriate location for termination kit using the
guidelines provided in section “Locating The Vent Termination” in
this instruction.

1. Cut two holes, one for each pipe, of appropriate size for

pipe size being used.

2. Loosely install elbow in bracket (if used) and place assem-

bly on combustion

air pipe.

3. Install bracket as shown in Fig. 54 and 56.

NOTE

:  For applications using vent pipe option indicated by

dashed lines in Fig. 54 and 55, rotate vent elbow 90

 from

position.

4. Disassemble loose pipe fittings. Clean and cement using

same procedures as used for system piping.  

DO NOT CE-

MENT POLYPROPYLENE FITTINGS.

(Direct Vent / 2-Pipe System ONLY)

When two or more furnaces are vented near each other, two vent

terminations may be installed as shown in Fig. 54, but next vent

termination, or pair of vent terminations,  must be at least 36 in.

(914 mm) away from the first two terminations. It is important that

vent terminations be made as shown in Fig. 54 to avoid

recirculation of vent gases.

Inducer Outlet Restrictor

To improve efficiency and operation of 40K, 60K, 100K or 120K

BTUH input models on very short vent systems, an inducer outlet

restrictor is required to be installed on the outlet of the inducer

assembly. The outlet restrictor is shown in the footnote of Table 17

Maximum Equivalent Vent Length.  The outlet restrictor for the

40K models is shipped in the loose parts bag.  See Table 17 for

usage, part numbers and sourcing of 60K, 100K and 120K inducer

outlet restrictors.
To determine if the outlet restrictor is required, see Table 17.

Failure to use an outlet restrictor on the 40K input model when

required may result in flame disturbance or flame sense

lockout.

Table 15 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installations)

MATERIALS

USA

1. All pipe, fittings, primers*, and solvents* must conform to American National Standards Institute (ANSI) standards and

American Society for Testing and Materials (ASTM) standards or ULC S636 where required by code.

2. See Table below for approved materials for use in the U.S.A.

3. ULC S636 vent systems must be composed of pipe, fittings, cements, and primers from the same supplier.

4. Factory accessory concentric vent kits are ULC S636 listed.

CANADA

1. Installation in Canada must conform to the requirements of CAN/CSA B149 code.

2. Vent systems must be composed of pipe, fittings, cements, and primers from the same supplier and listed to ULC S636.

3. Not all materials below may be approved or listed to ULC S636.

4. Royal Pipe and IPEX are approved suppliers of ULC S636 pipe, fittings, cements and primers*.

5. Factory accessory concentric vent kits are ULC S636 listed for use with Royal Pipe and IPEX venting systems

Material

Description

Type

ASTM or ULC Specification

Pipe

Solvents/

Primers**

Cements

PVC

Pressure Pipe

Schedule 40

D1785

D2466

or

D2665

F656

D2564

DWV

Schedule 40

D1785/D2665

Cellular Core

Schedule 40

F891

SDR 26

N/A

D2241

SDR 21

N/A

D2241

IPEX

Schedule 40

ULC S636

ULC S636

ULC S636

ULC S636

Royal Pipe

Schedule 40

ULC S636

ULC S636

ULC S636

ULC S636

ABS

ABS

Schedule 40

D1527

D2468

Clear Cleaner

For ABS†

D2235

DWV

IPS Sizes

Schedule 40

D2661

D2661

Cellular Core DWV

IPS

Sizes

Schedule 40

F628

CPVC

Pressure Pipe

Schedule 40

F441

F438

F656

F493

SDR

N/A

F442

N/A

IPEX

Schedule 40

ULC S636

ULC S636

ULC S636

ULC S636

Royal Pipe

Schedule 40

ULC S636

ULC S636

ULC S636

ULC S636

*PVC and ABS pipe may use either DWV or pressure rated fittings.
**Colored or tinted solvents or primers must be used where required by code in the USA
†ABS plastic does not require a primer before solvent cementing. A cleaner for ABS is recommended to remove any surface residue. ABS

cleaners are not subject to ASTM standards.
Polypropylene

Approved Manufacturer

Solvents Primers Cements

Poly

 

Pro

®

M & G Dura Vent

Not Permitted

Not Permitted

NOTE: Polypropylene vent systems are UL

*

1738 and ULC S636 listed and assembled using mechanical fastening systems

supplied by the vent manufacturer.

912S

Содержание 912S

Страница 1: ...y org Portions of the text and tables are reprinted from current edition of NFPA 54 ANSI Z223 1 with permission of National Fire Protection Association Quincy MA 02269 and American Gas Association Washington DC 20001 This reprinted material is not the complete and official position of the NFPA or ANSI on the referencedsubject which is represented only by the standard in its entirety TABLES Loose P...

Страница 2: ...xhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector obser...

Страница 3: ...ing on heating equipment observe precautions in literature on tags and on labels attached to or shipped with furnace and other safety precautions that may apply These instructions cover minimum requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain local codes and ordinances especially those that may not have kept up with changi...

Страница 4: ...l sizes can be used if the heating load is 20 000 BTU or lower Use Air Conditioning Contractors of America Manual J and S American Society of Heating Refrigerating and Air Conditioning Engineers or other approved engineering method to calculate heating load estimates and select the furnace Excessive oversizing of the furnace may cause the furnace and or vent to fail prematurely customer discomfort...

Страница 5: ...not touch ungrounded objects etc 4 If you touch ungrounded objects and recharge your body with static electricity firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungroun ded furnaces 6 Before removing a new control from its container discharge your body s electrostatic charge to ground to protect ...

Страница 6: ...2 1 2 319 12 9 16 322 7 1 8 181 121 0 55 0 36060 125 0 56 8 36040 17 1 2 445 15 7 8 403 16 406 8 3 4 222 132 0 60 0 48060 142 0 64 5 48080 151 0 68 6 60080 21 533 19 3 8 492 19 1 2 495 10 1 2 267 158 5 72 0 48100 166 5 75 7 60100 166 5 75 7 60120 24 1 2 622 22 7 8 581 23 584 12 1 4 311 184 0 83 6 Fig 1 Dimensional Drawing 912S ...

Страница 7: ...R IS LOCATED TO THE LEFT OF THE BURNER SECTION AND CONDITIONED AIR IS DISCHARGED TO THE RIGHT A12181 Fig 2 Multipoise Orientations 60 80 27 C 16 C SUPPLY AIR SEE PRODUCT DATA FOR ACCESSORY CONDENSATE TRAP HEATER AND CONDENSATE DRAIN LINE PROTECTION A150573 Fig 3 Freeze Protection and Return Air Temperature BACK POSITIONED DOWNWARD AIR RETURN CUT IN BACK BACK POSITIONED UPWARD A12182 Fig 4 Prohibit...

Страница 8: ...o an air distribution system Refer to Air Ducts section be provided ample space for servicing and cleaning Always comply with minimum fire protection clearances shown in Table 2 or on the furnace clearance to combustible construction label CARBON MONOXIDE POISONING COMPONENT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death and unit component damage Corrosive or...

Страница 9: ...equate combustion ventilation and dilution air must be provided in accordance with U S A Installations Section 9 3 of the current edition of NFPA 54 ANSI Z223 1 Air for Combustion and Ventilation and applicable provisions of the local building codes Canada Part 8 of the current edition of CAN CSA B149 1 Venting Systems and Air Supply for Appliances FURNACE CORROSION HAZARD Failure to follow this c...

Страница 10: ... be considered part of a space if a There are no closeable doors between rooms b Combining spaces on same floor level Each opening shall have free area of at least 1 in 2 1 000 Btuh 2 000 mm2 kW of the total input rating of all gas appliances in the space but not less than 100 in 2 0 06 m2 One opening shall commence within 12 in 300 mm of the ceiling and the second opening shall commence within 12...

Страница 11: ...rtical Ducts or Openings 60 000 40 000 100 000 divided by 3 000 33 3 Sq In for each Single Duct or Opening 80 000 30 000 110 000 divided by 2 000 55 0 Sq In for each two Horizontal Ducts Table 4 Minimum Space Volumes for 100 Combustion Ventilation and Dilution Air from Outdoors OTHER THAN FAN ASSISTED TOTAL 1 000 S BTUH GAS INPUT RATE FAN ASSISTED TOTAL 1 000 S BTUH GAS INPUT RATE ACH 30 40 50 40 ...

Страница 12: ...A B C D D E F G L12F012 Fig 6 Air for Combustion Ventilation and Dilution for Outdoors Minimum opening size is 100 sq in 64516 sq mm with minimum dimensions of 3 in 76mm Minimum of 3 in 76mm when type B1 vent is used L12F013 Fig 7 Air for Combustion Ventilation and Dilution from Indoors 912S ...

Страница 13: ... in Fig 10 and 11 A field supplied accessory Horizontal Installation Kit trap grommet is required for all direct vent horizontal installations only The kit contains a rubber casing grommet designed to seal between the furnace casing and the condensate trap See Fig 17 The field supplied accessory horizontal drain trap grommet is ONLY REQUIRED FOR DIRECT VENT APPLICATIONS It it NOT required for appl...

Страница 14: ...n ports of the collector box Connect relief tube to port on collector box Rotate elbow to desired position and tighten clamp to 15 lb ïin Slide tube in standïoffs to adjust length Connect the new pressure switch tube from Loose Parts bag to port on front pressure switch Route tube through inducer standïoffs to adjust position of the tube Trim excess tube Connect pressure switch tube to port on col...

Страница 15: ...ion Attach condensate trap with screw to collector box Slide relief tube in standïoffs to adjust length Vent elbow shown in alternate orientation Tighten clamp on inlet to vent elbow 15 lb ïin Align trap over middle and rightïhand port on collector box NOTE Remove knockout in casing before reïinstalling the condensate trap Install plug on open port of collector box Horizontal Right Trap Configurat...

Страница 16: ...position and torque clamp on inlet 15 lb in Slide relief tube in stand offs to adjust length Attach condensate trap with screw to collector box Align trap over middle and right hand port on collector box Install two plugs previously removed in open ports on collector box Connect relief tube to port on collector box Connect the new pressure switch tube from Loose Parts bag to port on front pressure...

Страница 17: ... not hard piped together and b There is an air gap at the point where the two drain lines meet or c All condensate piping is at least 3 4 in PVC and there is a relief tee at the top of condensate drain piping as shown in Fig 14 NOTE On narrower casings it may be easier to remove the condensate trap connect the drain line components and re install the condensate trap Read the steps thoroughly to fa...

Страница 18: ...ain trap grommet is ONLY REQUIRED FOR DIRECT VENT APPLICATIONS It is NOT required for applications using single pipe or ventilated combustion air venting NOTICE TIP FROM CONTRACTORS When installing the furnace horizontally use the entire drain elbow that is do NOT cut as shown in Fig 16 to connect the trap to the drain line This helps to prevent bumps and shocks to the drain line from damaging the...

Страница 19: ...re DIRECTION OF AIRFLOW Condensing Furnace Evaporator Coil Blower 3 4 PVC 1 2 3 4 1 2 CPVC or larger Positive pressure Pressure lower than areas with Negative pressure 3 4 PVC DIRECTION OF AIRFLOW 1 2 3 4 3 4 3 4 Open standpipe 3 4 Condensing Furnace Evaporator Coil Blower 3 4 PVC 3 4 1 2 CPVC or larger Positive pressure Pressure lower than areas with Negative pressure 3 4 PVC DIRECTION OF AIRFLOW...

Страница 20: ...ng Furnace ï ï ï ï ï Evaporator Coil Blower ï 3 4 PVC 3 4 1 2 CPVC or larger Positive pressure Pressure lower than areas with Negative pressure 3 4 PVC DIRECTION OF AIRFLOW 3 4 3 4 3 4 3 4 Open standpipe Optional when coil drain is not connected to furnace drain Recommend T fitting standpipe of same diameteror larger H WHQGLQJ XSZDUG ZLWK PLQLPXP LQFK high Condensing Furnace Evaporator ÄÄÄÄÄÄÄÄÄ C...

Страница 21: ... PIPE ORIENTATION FOR CONDENSATE DISCHARGE A170128 Fig 18 Drain Trap Connection and Routing Appearance may vary INSTALLATION Cabinet air leakage is less than 2 at 1 0 in W C Cabinet air leakage is less than 1 4 at 0 5 in W C when tested in accor dance with ASHRAE Standard 193 NOTICE Upflow Installation NOTE The furnace must be pitched as shown in Fig 26 for proper condensate drainage Supply Air Co...

Страница 22: ... 1 Determine application being installed from Table 8 2 Construct hole in floor per Table 8 and Fig 21 3 Construct plenum to dimensions specified in Table 8 and Fig 21 4 Install special base coil assembly or coil box as shown in Fig 21 NOTE It is recommended that the perforated supply air duct flanges be completely removed from furnace when installing the furnace on a factory supplied cased coil o...

Страница 23: ... Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening Remove and discard this panel when bottom return air is used To remove bottom closure panel see Fig 23 and 24 Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening This panel MUST be in place when side return air inlet s ar...

Страница 24: ...0 05 13 0 07 18 0 08 21 0 13 32 0 29 72 0 20 49 1000 472 0 06 16 0 11 28 0 11 28 0 17 43 0 27 67 1200 566 0 07 18 0 15 37 0 14 36 0 22 56 1400 661 0 08 21 0 19 48 0 18 45 0 28 70 1600 755 0 09 23 0 24 60 0 21 54 1800 850 0 10 25 0 26 64 20 x 25 Filter 508 x 635 mm Factory Accessory Washable Factory Accessory Media Representative After Market Filter Media Fiberglass Pleated CFM L s 1 in 2 5 cm 4 in...

Страница 25: ...DE RETURN BOTTOM RETURN 14 3 16 360 16 x 25 x 3 4 406 x 635 x 19 14 x 25 x 3 4 356 x 635 x 19 Washable 17 1 2 445 16 x 25 x 3 4 406 x 635 x 19 16 x 25 x 3 4 406 x 635 x 19 Washable 21 533 16 x 25 x 3 4 406 x 635 x 19 20 x 25 x 3 4 508 x 635 x 19 Washable 24 1 2 622 16 x 25 x 3 4 406 x 635 x 19 24 x 25 x 3 4 610 x 635 x 19 Washable Recommended to maintain air filter face velocity See Product Data f...

Страница 26: ... 2 419 19 5 8 498 Downflow applications on combustible flooring KGASB sub base required 15 1 8 384 19 483 16 3 4 425 20 5 8 600 Downflow Applications on Combustible Flooring with CNPV CNRV CAR or CAP Coil Assembly or KCAKC coil box KGASB subbase not required 15 1 2 394 19 483 16 1 2 419 20 508 21 533 Upflow Applications on Combustible or Noncombustible Floor ing KGASB subbase not required 19 1 2 4...

Страница 27: ... CLOSURE Representative drawing only some models may vary in appearance A170123 Fig 23 Removing Bottom Closure Panel 2 Screws BOTTOM PLATE SCREWS 4 1 Lay furnace on the back or side 2 Remove the four 4 screws that secure the bottom plate to the furnace casing 3 Remove the bottom closure from the casing 4 Re install the bottom plate to the furnace casing and re install the four 4 screws Representat...

Страница 28: ...AL MIN 1 4 IN 6 MM TO 1 2 IN 13 MM MAX A11237 Fig 26 Furnace Pitch Requirements ANY COMBINATION OF 1 2 OR 3 PERMITTED A11036 Fig 27 Upflow Return Air Configurations and Restrictions A11037 Fig 28 Downflow Return Air Configurations and Restrictions HORIZONTAL TOP RETURN NOT PERMITTED FOR ANY MODEL A11038 Fig 29 Horizontal Right Return Air Configuration and Restrictions 912S ...

Страница 29: ...ON OF 1 2 40 000 14 3 16 YES YES NO YES 17 1 2 YES YES NO YES 60 000 14 3 16 YES YES NO YES 17 1 2 YES NO NO YES 80 000 17 1 2 YES YES NO YES 21 YES YES NO YES 100 000 21 YES YES NO YES 120 000 24 1 2 YES YES NO YES INPUT CASING WIDTH INCHES HORIZONTAL RIGHT RETURN AIR CONNTECIONS CONNECTION AT 1 ONLY CONNECTION AT 2 ONLY CONNECTION AT 3 ONLY COMBINATION OF 1 2 40 000 14 3 16 YES YES NO YES 17 1 2...

Страница 30: ...c Installation 2 IN 51 mm COMBUSTION AIR PIPE SEE VENTING SECTION Install 12 x 22 204 x 559 mm sheet metal in front of and above the burner compartment area The sheet metal MUST extend above the furnace casing by 1 in 25 mm with the door removed A 1 in 25 mm clearance minimum between top of furnace and combustible material is required The entire length of furnace must be supported when furnace is ...

Страница 31: ...nections to furnace with code approved tape or duct sealer NOTE Flexible connections should be used between ductwork and furnace to prevent transmission of vibration Ductwork passing through unconditioned space should be insulated to enhance system performance When air conditioning is used a vapor barrier is recommended Maintain a 1 in 25 mm clearance from combustible materials to supply air ductw...

Страница 32: ...Orange 3 5 397 1485 1470 1455 1430 1390 1340 1280 1205 1120 1035 Blue 3 2 5 426 1120 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 048100 SIDE BOTTOM Black 4 0 373 1715 1660 1610 1555 1490 1420 1340 1245 1150 1065 Yellow 3 3 5 379 1535 1480 1435 1380 1325 1260 1180 1095 1010 910 Blue 3 3 0 367 1300 1255 1205 1160 1100 1035 970 905 810 730 Red 3 2 0 ...

Страница 33: ...e a new listed connector Do not use a connector which has previously served another gas appliance Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in 51 mm outside the furnace WARNING FURNACE DAMAGE HAZARD Failure to follow this caution may result in furnace damage Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burn...

Страница 34: ...ry death or property damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnection Reconnect wires correctly Verify proper operation after servicing Always reinstall access doors after completing service and maintenance WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Blower d...

Страница 35: ...ket and screws are shipped in the loose parts bag included with the furnace See Fig 36 for J Box mounting locations The J Box mounting bracket and green ground screw is used as a grounding point for all line voltage wiring options The J Box cover may be omitted when electrical connections are made inside an external electrical box mounted external to the casing External Electrical Box on Furnace C...

Страница 36: ... drill into blower shelf of furnace to route control wiring Route any control or accessory wiring to the blower compartment through external knockouts on the casing WARNING 24 V Wiring Make field 24 v connections at the 24 v terminal strip See Fig 40 Connect terminal Y as shown in Fig 39 for proper cooling operation Use only AWG No 18 color coded copper thermostat wire NOTE Use AWG No 18 color cod...

Страница 37: ... 36 11 0 15 60100 115 60 1 127 104 11 9 15 8 12 36 11 0 20 60120 115 60 1 127 104 11 9 15 8 12 36 11 0 20 Permissible limits of the voltage range at which the unit operates satisfactorily Unit ampacity 125 percent of largest operating component s full load amps plus 100 percent of all other potential operating components EAC humidifier etc full load amps Time delay type is recommended Length shown...

Страница 38: ...NNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower operation Some thermostats require a C terminal connection as shown If any of the...

Страница 39: ...NEUTRAL CONNECTIONS COOL HEAT SPARE 1 SPARE 2 BLOWER SPEED SELECTION TERMINALS EAC 1 TERMINAL 115 VAC 1 0 AMP MAX 115 VAC L1 LINE VOLTAGE CONNECTION PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR PL1 LOW VOLTAGE MAIN HARNESS CONNECTOR TRANSFORMER 24 VAC CONNECTIONS HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX TWINNING AND OR COMPONENT TEST TERMINAL BLOWER OFF DELAY J2 J2 JUMPER PLT PL1 SPARE 3 SPARE 3 ...

Страница 40: ...his system must be UL listed material Acceptability under Canadian standard CAN CSA B149 is dependent upon full compliance with all installation instructions Under this standard it is recommended that the vent system be checked once a year by qualified service personnel The authority having jurisdiction gas inspection authority municipal building department fire department etc should be consulted ...

Страница 41: ...55 for single pipe or ventilated combustion air option A furnace shall not be connected to a chimney flue serving a separateappliance designed to burn solid fuel Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code the current edition of the National Fuel Gas Code and the vent or liner manufacturer s installation...

Страница 42: ...pe to the outdoors is not required for a single pipe vent system A 12 in 304 mm long pipe with a 2 in 51 mm tight radius 90 degree elbow is required to be attached to the combustion air pipe adapter on the furnace See Fig 56 This short inlet air pipe helps to ensure stable combustion as well as allow for sound attenuation To aid sound attenuation point the inlet air pipe away from occupants An ext...

Страница 43: ...n air pipe terminates in a well ventilated attic or crawl space Follow the clearances as shown in Fig 57 The combustion air pipe cannot terminate in attics or crawl spaces that use ventilation fans designed to operate in the heating season If ventilation fans are present in these areas the combustion air pipe must terminate outdoors as a Direct Vent System Non Direct Vent 1 Pipe System The vent pi...

Страница 44: ...l vent length Include deductions from the Maximum Equivalent Vent Length MEVL contained in the Venting Tables for elbows and flexible vent pipe Factory accessory concentric vent terminations or pipe lengths and elbows used for standard vent terminations do not require a deduction from the Maximum Equivalent Vent Length See vent termination figures associated with Table 17 Include a deduction for a...

Страница 45: ...te the vent elbow 1 Loosen the clamp on the inlet of the vent elbow attached to the inducer 2 Rotate the vent elbow to the required position There are rounded notches on the vent elbow to align it with the inducer housing for each orientation 3 Tighten the clamp around the vent elbow Torque the clamp to 15 lb in See Fig 46 49 Installing the Vent Pipe Adapter and Combustion Air Pipe Adapter CARBON ...

Страница 46: ...be supported to prevent sagging Space combustion air piping and vent piping hangers as shown in Table 14 Support pipes using perforated metal hanging strap or commercially available hangers or straps designed to support plastic pipe 17 Slope the vent and combustion air piping downward towards furnace A minimum slope of at least 1 4 in 6 mm per linear ft 1 in 25 mm per 4 ft 1 2 M with no sags betwe...

Страница 47: ... as shown in Fig 54 and all clearance shown in Fig 52 NOTE Follow the instructions of the vent terminal manufacturer These instructions are provided as a reference only Cut one 4 in 102 mm diameter hole for 2 in 50 mm ND kit or one 5 in 127 mm diameter hole for 3 in 80 mm ND kit in the desired location Loosely assemble concentric vent combustion air termination components together using instructio...

Страница 48: ...lame sense lockout Table 15 Approved Combustion Air and Vent Pipe Fitting and Cement Materials U S A Installations MATERIALS USA 1 All pipe fittings primers and solvents must conform to American National Standards Institute ANSI standards and American Society for Testing and Materials ASTM standards or ULC S636 where required by code 2 See Table below for approved materials for use in the U S A 3 ...

Страница 49: ...ign Temp C Unit Size 40 000 BTUH 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76 38 51 64 76 7 6 1 6 1 6 1 6 1 15 2 13 7 6 1 18 3 15 2 6 1 9 1 9 1 7 6 6 1 22 9 19 8 18 3 6 1 25 9 22 9 19 8 18 3 0 1 5 1 5 6 1 7 6 6 1 6 1 9 1 7 6 4 6 4 6 3 0 3 0 6 1 12 2 9 1 7 6 6 1 13 7 12 2 9 ...

Страница 50: ...ped in the loose parts bag or available through Replacement Components required under 10 ft 3 M TEVL in all orientations Required for installations from 0 2000 0 to 610 M above sea level Failure to use an outlet restric tor may result in flame disturbances or flame sense lock out 2 Inducer Outlet Restrictor disk P N 337683 401 1 25 in 32 mm Dia available through Replacement Components required for...

Страница 51: ... MEVL 95 ft 29 M For 2 pipe from Table 17 Is TEVL less than MEVL YES Therefore 2 pipe MAY be used Example 2 A direct vent 60 000 BTUH furnace installed at 2100 ft 640M Venting system includes FOR EACH PIPE 100 feet 30 M of vent pipe 95 feet 29 M of combustion air inlet pipe 3 90º long radius elbows and a polypropylene concentric vent kit Also includes 20 feet 6 1 M of flexible polypropylene vent p...

Страница 52: ...F THE INDUCER FOR USAGE SEE MAXIMUM EQUIVALENT VENT LENGTH TABLE 10FT 3 1 M OF VENT OR LESS ONLY A170006 Fig 42 Inducer Vent Elbow Avoid short horizontal offsets with 90 deg Elbows Short offsets can be difficult to slope and may trap con densate Use 45 deg Elbows where possible to ensure conden sate drainage Slope vent pipe back to the furnace at least per foot A14546 Fig 43 Near Furnace Vent Conn...

Страница 53: ...r items refer to the Inside Corner Clearance Table 3 ft 1 M to 6 ft 2 M Notes For this illustration Wall A is the wall adjacent to the wall the vent termination is located Wall B is the wall the vent termination is located The termination can be located on either wall Minimum distance of a vent terminal to an inside corner is 3 ft 1 M Maximum distance from an inside corner is 6 ft 2 M If the vent ...

Страница 54: ...vent termination within a horizontal distance of 2 ft 61 cm from the centerline of the vent termination 6 ft 2 M Clearance to a ventilation exhaust including HRV ERV on either Wall A or Wall B 12 in 305 mm Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 1 M Clearance under a veranda porch deck or balcony N P No operable windows doors or intakes of any type are pe...

Страница 55: ...r combustion air connection UPFLOW VERTICAL VENT A11310A Fig 46 Upflow Configurations Appearance may vary See Notes for Venting Options 1 2 3 4 5 6 7 5 Rotate vent elbow to required position DOWNFLOW LEFT CONFIGURATION A11311A 1 2 3 4 5 6 7 5 Rotate vent elbow to required position Any other unused knockout may be used for combustion air connection DOWNFLOW RIGHT CONFIGURATION A11312A Requires Acce...

Страница 56: ...FT RIGHT VENT CONFIGURATION A11329A Fig 48 Horizontal Left Appearance may vary See Notes for Venting Options ALTERNATE COMBUSTION AIR CONNECTIONS HORIZONTAL RIGHT VERTICAL VENT CONFIGURATION A11337 Requires Internal Vent Kit See Product Data for Current Kit Number HORIZONTAL RIGHT LEFT VENT CONFIGURATION A11336 ALTERNATE COMBUSTION AIR CONNECTIONS HORIZONTAL RIGHT RIGHT VENT CONFIGURATION A11335 F...

Страница 57: ...w VENT PIPE FLUSH SHOWING COUPLING VENT PIPE FLUSH WITH ADAPTER VENT PIPE ADAPTER WITH GASKET INSTALLED ON FURNACE VENT PIPE IS CUT FLUSH WITH TOP OF ADAPTER PRIME AND CEMENT VENT PIPE TO ADAPTER ALLOW TO DRY BEFORE INSTALLING VENT COUPLING ALIGN NOTCHES IN VENT PIPE COUPLING OVER STAND OFF ON ADAPTER TORQUE LOWER CLAMP 15 LB IN WHEN REMAINING VENT PIPE IS INSTALLED TORQUE UPPER CLAMP TO 15 LB IN ...

Страница 58: ...minimum of two sides beneath the floor See Note 4 Manufacturer s Recommendation See Notes 3 8 M Clearance to each side of the centerline extended above or below vent terminal of the furnace to a dryer or water heater vent or other appliance s vent intake or exhaust 12 in 305 mm 12 in 305 mm N Furnace combustion air intake clearance to a water heater vent dryer vent or other types of appliance exha...

Страница 59: ...en on a minimum of two sides beneath the floor See Note 4 Manufacturer s Recommendation See Notes 3 8 M Clearance to each side of the centerline extended above or below vent terminal of the furnace to a dryer or water heater vent or other appliance s direct vent intake or exhaust 12 in 305 mm 12 in 305 mm N Clearance to a moisture exhaust duct dryer vent spa exhaust etc 12 in 305 mm See Note 4 12 ...

Страница 60: ... termination with 2 elbows preferred 12 in min 305 mm from overhang or roof Maintain 12 in 305mm minimum clearance above highest anticipated snow level or grade whichever is greater 6 in 152mm minimum clearance between wall and end of vent pipe 10 in 254mm maximum pipe lengt h Sidewall Termination with Straight Pipe preferred Roof Termination Preferred Vent Maintain 12 in minimum clearance above h...

Страница 61: ...N 305 MM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER COMBUSTION AIR ELBOW PARALLEL TO WALL OVERHANG 12 IN 305 MM MIN GROUND LEVEL OR ANTICIPATED SNOW LEVEL EXHAUST CLEARANCE TO OVERHANG PER CODE OPTIONAL BRACKET COUPLING 12 IN 305 MM MIN SEPARATION BETWEEN BOTTOM OFCOMBUSTION AIR AND BOTTOM OF VENT A13078 Fig 56 Alberta and Saskatchewan Vent Termination 912S ...

Страница 62: ...Pipe hangar Ventilated Combustion Air intake termination in crawl space Ventilated Combustion Air intake pipe CRAWL SPACE ATTIC highest level of insulation A10497 Fig 57 Vent Terminations for Ventilated Combustion Air 912S ...

Страница 63: ...y some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSATE PUMP Tee Dry Well Cap water tight and removable Tee Dry Well Cap water tight and removable Tee Dry Well Cap water tight and removable Recommend T fitting with 4 inch minimum height standpipe A of same diameter or larger extending upward A A A A170122A Fig 59 Recommended Combustion Air Inlet Moisture Trap 912S ...

Страница 64: ...er operates HUM 24vac terminal is only energized when the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal injury or death Failure to use a properly configured trap or NOT water priming trap before operating furnace may allow positive pressure vent gases to enter the structure through d...

Страница 65: ...ge the factory orifice to a different orifice Tables have been provided in the furnace installation instructions to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find installa...

Страница 66: ...nput rate If clocked rate does not match required input from Step 1 increase manifold pressure to increase input or decrease manifold pressure to decrease input Re peat steps b through e of Step 1 until correct heat input is achieved Re install regulator seal cap on gas valve 3 Restore furnace to normal operating condition a Turn gas valve ON OFF switch to OFF b Remove water column manometer or si...

Страница 67: ... on thermostat per thermostat instruc tions and install on subbase or wall 5 Install blower access door Electronic thermostat Set cycle rate for 3 cycles per hr Check Safety Controls The flame sensor gas valve and pressure switch were all checked in the Start up procedure section as part of normal operation 1 Check Main Limit Switch This control shuts off combustion system and energizes air circul...

Страница 68: ...e drawing only some models may vary in appearance A11153 Fig 60 Gas Valve without Tower Pressure Ports ON OFF SWITCH 1 8 NPT INLET PRESSURE TAP REGULATOR SEAL CAP REGULATOR ADJ UNDER CAP 1 2 NPT OUTLET MANIFOLD PRESSURE TAP SET SCREW 3 32 HEX HEAD ACCEPTS 5 16 HOSE CONNECTION OUTP INP VENT 1 2 NPT INLET INLET PRESSURE TAP SET SCREW 3 32 HEX HEAD ACCEPTS 5 16 HOSE CONNECTION Representative drawing ...

Страница 69: ...69 338309 201 Rev E A11602 Fig 64 Service Label Information 912S ...

Страница 70: ...1 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37...

Страница 71: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3 3 42 3 4 42 3 5 42 3 6 4001 775 43 3 7 43 3 8 42 3 3 42 3 4 1220 800 43 3 5 43 3 6 43 3 7 43 3 8 825 44 3 8 43 3 4 43 3 5 43 3 6 850 44 3 5 44 3 7 44 3 8 43 3 4 5000 875 44 3 3 44 3 5 44 3 6 44 3 7 15...

Страница 72: ...42 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44 3 0 44 3 1 44 3 2 625 42 3 4 42 3 5 42 3 6 42 3 7 8001 650 43 3 8 42 3 2 42 3 3 42 3 4 2439 675 43 3 5 43 3 6 43 3 7 42 3 2 700 44 3 7 43 3 4 43 3 5 43 3 6 725 44 3 5 44 3 6 44 3 7 44 3 8 9000 750 44 3 3 44 3 4 44 3 5 44 3 6 2743 775 44 3 0 ...

Страница 73: ...The maximum make point of the switch is 0 83 in W C ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing Lock out and tag switch with a suitable warning label WARNING The electrica...

Страница 74: ...erify that there is nothing plugged into the PLT connector Note If there is a jumper connector plugged into PLT remove it and discard See Fig 40 3 Verify that the Blower Heat Off Delay jumpers are set as desired See Fig 40 4 Verify that the blower and control Main doors are properly installed 5 Verify that the Status LED glows If not check that the power supply is energized and that the blower doo...

Страница 75: ...net 7 Replace filter cabinet door 8 Turn on electrical supply to furnace Blower Motor and Wheel Maintenance To ensure long life economy and high efficiency clean accumulated dirt and grease from blower wheel and motor annually The inducer and blower motors are pre lubricated and require no additional lubrication These motors can be identified by the absence of oil ports on each end of the motor Th...

Страница 76: ... or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the operating instructions on the label attached to the furnace WARNING Refer to Fig 71 1 Disc...

Страница 77: ...control door Flushing Collector Box and Drainage System ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or service Follow the operating instructions on the label attached to the furnace WARNING 1 Turn off gas ...

Страница 78: ...ir intricate design A build up of soot and carbon indicates that a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air improper vent termination incorrect size or damaged manifold orifice s improper gas or a restricted heat exchanger primary or secondary Action must be taken to correct the problem 1 Turn off gas an...

Страница 79: ...GE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glycol automotive antifreeze coolant or equivalent Failure of plastic components may occur CAUTION 1 Obtain propylene glycol RV swimming pool antifreeze or equivalent 2 Turn off gas and electrical supplies to your furnace 3 Remove furnace control door 4 Remove the top unused r...

Страница 80: ... GROMMET SCREW LOCATION BLOWER HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SCREW GND BLOWER HSG ASSY MOTOR BLOWER WHEEL BLOWER CUTOFF BLOWER DETAIL A A11584 Fig 70 Blower Assembly FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Fig 71 Burner Assembly 912S ...

Страница 81: ...If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains energized as long as the blower motor BLWM is energized f Blower Off Delay When the thermostat is satisfied the R to W circuit is opened de energizing the gas valve GV stopping gas flow to the burners ...

Страница 82: ...vious fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief component test sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed when equipped HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on ...

Страница 83: ... sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow wire MUST be connected to furnace sheet metal Flame sensor must not be grounded To determine whether the problem is i...

Страница 84: ...84 A12420 Fig 73 Wiring Diagram 912S ...

Страница 85: ...sting by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number series number and serial number located on the unit rating plate to ensure correct replacement part Model Nomenclature MODEL COOLING CAPACITY HEATING CAPACITY MOTOR WIDTH VOLTAGE FEATURES MINOR SERIES 912SC 30 040 E 14 ...

Отзывы: