Table 24 — RTU Open Controller Inputs and Outputs
LEGEND
1.
Safety Chain Feedback: 24Vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instructions.
2.
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section
for wiring and setup instructions.
3.
Refer to the input configuration and accessory sections of the RTU Open Multi–Protocol Controller Controls, Start–Up, Operation and Troubleshooting
manual for more detail.
4.
Parallel pins J5–1 = J2–6, J5–3 = J1–10, J5–5 = J1–2 are used for field installation.
POINT NAME
BACNET OBJECT
NAME
TYPE OF I/O
CONNECTION
PIN NUMBER (S)
CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp
zone_temp
AI (10K Thermistor)
J20–1 and 2
Analog Input 10
Supply Air Temperature
sa_temp
AI (10K Thermistor)
J2–1 and 2
Analog Input 6
Outside Air Temperature
oa_temp
AI (10K Thermistor)
J2–3 and 4
Analog Input 7
Space Temperature Offset Pot
stpt_adj_offset
AI(100K
Potentiometer)
J20–3 and 4
Analog Input 11
Safety Chain Feedback
safety_status
BI (24 VAC)
J1–9
Binary Input 4
Compressor Safety Status
1
comp_status
BI (24 VAC)
J1–2
Binary Input 3
Fire Shutdown Status
firedown_status
BI (24 VAC)
J1–10
Binary Input 5
Enthalpy Status
enthalpy_status
BI (24 VAC)
J2–6 and 7
Binary Input 8
Humidistat Input Status
humstat_status
BI (24 VAC)
J5–7 and 8
Binary Input 9
Zone Temperature
n/a
n/a
J13–1–4
Rnet
CONFIGURABLE INPUTS
4
Indoor Air CO
2
iaq
AI (4–20 mA)
J4–2 and 3 or J4–5
and 6
Analog Input 2
Outdoor Air CO
2
oaq
AI (4–20 mA)
Analog Input 1
Space Relative Humidity
space_rh
AI (4–20 mA)
Analog Input 10
Supply Fan Status
2
sfan_status
BI (24 VAC)
J5–1 and 2 or
J5–3 and 4, J5–5
and 6 or J5–7 and
8
3
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Filter Status
2
filter_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Door Contact
2
door_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Remote Occupancy Input
2
occ_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
IGC Input
2
igcovr_status
BI (24 VAC)
Binary Input 9. Mandatory input on gas
heat units.
OUTPUTS
Economizer Output
econ_output
AO (4–20mA)
J2–5
Analog Output 1
Supply Fan VFD
vfd_output
AO (2–10Vdc)
J22–1 and 2
Analog Output 2
Supply Fan Relay
sfan
BO Relay (24VAC, 1A)
J1–4
Binary Output 1 (G)
Cool 1 Relay State
comp_1
BO Relay (24VAC, 1A)
J1–8
Binary Output 5 (Y1)
Cool 2 Relay State
comp_2
BO Relay (24VAC, 1A)
J1–7
Binary Output 4 (Y2)
Cool 3 Relay State
comp_3
BO Relay (24VAC, 1A)
J11–5 and 6
Binary Output 7 (Y3)
Heat 1 Relay State
heat_1
BO Relay (24VAC, 1A)
J1–6
Binary Output 3 (W1)
Heat 2 Relay State
heat_2
BO Relay (24VAC, 1A)
J1–5
Binary Output 2 (W2)
Power Exhaust Relay State
pexh
BO Relay (24VAC, 1A)
J11–2 and 3
(N.O.)
Binary Output 8 (PE)
Dehumidification Relay
dehum
BO Relay (24VAC, 1A)
J11–7 and 8
(N.O.)
Binary Output 6
AI
— Analog Input
AO
— Analog Output
BI
— Binary Input
BO
— Binary Output
Содержание 580J*16D Series
Страница 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Страница 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Страница 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Страница 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Страница 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Страница 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Страница 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Страница 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Страница 51: ...51 Fig 70 580J 8 14 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...
Страница 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...