![Bryant 580J*04A Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/bryant/580j-04a/580j-04a_installation-instructions-manual_2822120029.webp)
29
Table 13 — Menu Structure (cont)
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
NOTES
ADVANCED
SETUP (CONT)
MAT T CAL
0.0°F
±2.5°F
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OAS T CAL
0.0°F
±2.5°F
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
OA H CAL
0% RH
±10% RH
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
RA T CAL
0.0°F
±2.5°F
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
RA H CAL
0% RH
±10% RH
RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity sensor.
DA T CAL
0.0°F
±2.5°F
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration temperature
sensor.
2SP FAN DELAY
5 Minutes
0 to 20 minutes in 1
minute increments
TIME DELAY ON 2nd STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try
to satisfy the call for second stage cooling before the first stage mechan-
ical cooling is enabled.
CHECKOUT
DAMPER MINIMUM POSI-
TION
N/A
N/A
The checkout for the damper minimum position is based on the system.
See Table 14.
DAMPER OPEN
N/A
N/A
Position damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Pause in
the mode to allow exhaust contacts to energize due to the delay in the
system.
DAMPER CLOSE
N/A
N/A
Positions damper to the fully closed position
CONNECT Y1–O
N/A
N/A
Closes the Y1–O relay (Y1–O)
CONNECT Y2–O
N/A
N/A
Closes the Y2–O relay (Y2–O)
CONNECT AUX1-O
N/A
N/A
Energizes the AUX output. If Aux setting is:
• NONE — not action taken
• ERV — 24 Vac out. Turns on or signals an ERV that the conditions are
not good for economizing but are for ERV operation.
• SYS — 24 Vac out. Issues a system alarm
CONNECT EXH1
N/A
N/A
Closes the power exhaust fan 2 relay (EXH1)
ALARMS
Alarms display only when they are active. The menu title “ALARMS(#)” includes the number of active alarms in parenthesis ( ). When using SYLK
bus sensors, “SYLK” will appear on the screen, and when using 20k OA temperature sensors, “SENS T” will appear on the screen
MA T SENS ERR
N/A
N/A
SUPPLY AIR TEMPERATURE SENSOR ERROR
Mixed air sensor has failed or become disconnected - check wiring then
replace sensor if the alarm continues.
CO2 SENS ERR
N/A
N/A
CO
2
SENSOR ERROR
CO
2
sensor has failed, gone out of range or become disconnected -
check wiring then replace sensor if the alarm continues.
OA SYLK T ERR
N/A
N/A
OUTSIDE AIR S-BUS SENSOR ERROR
Outdoor air enthalpy sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
OA SYLK H ERR
N/A
N/A
RA SYLK T ERR
N/A
N/A
RETURN AIR S-BUS SENSOR ERROR
Return air enthalpy sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues.
RA SYLK H ERR
N/A
N/A
DA SYLK T ERR
N/A
N/A
DISCHARGE AIR S-BUS SENSOR ERROR
Discharge air sensor has failed or become disconnected - check wiring
then replace sensor if the alarm continues.
OA SENS T ERR
N/A
N/A
OUTSIDE AIR TEMPERATURE SENSOR ERROR
Outdoor air temperature sensor has failed or become disconnected -
check wiring then replace if the alarm continues.
ACT ERROR
N/A
N/A
ACTUATOR ERROR
Actuator has failed or become disconnected - check for stall, over volt-
age, under voltage and actuator count. Replace actuator if damper is
movable and supply voltage is between 21.6 V and 26.4 V. Check actu-
ator count on STATUS menu.
FREEZE ALARM
N/A
N/A
Check if outdoor temperature is below the LOW Temp Lockout on set-
point menu. Check if mixed air temperature on STATUS menu is below
the Lo Setpoint on Advanced menu. When conditions are back in normal
range then the alarm will go away.
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......