background image

285B

EVOLUTION

R

15 HEAT PUMP

WITH PURON

r

REFRIGERANT

1--1/2 TO 5 TONS

Wiring Diagram

SPEED 

UP

JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE

1) MOMENTARILY SHORT PINS AND RELEASE TO BYPASS COMPRESSOR OFF DELAY.
2) SHORT FOR 5+ SEC. AND RELEASE FOR FORCED DEFROST.
3) PERMANENT SHORT WILL BE IGNORED.
 

DEFROST WILL TERMINATE IN 30 SEC. IF DFT OPEN.

 

DEFROST WILL TERMINATE NORMALLY IF DFT IS CLOSED.

FIELD SELECTABLE OPTIONS FOR TIME PERIOD
BETWEEN DEFROST CYCLES (MINUTES)

1

2

3

1

2

3

1

2

3

1

2

3

30 MINUTES

60 MINUTES

(DEFAULT)

90 M INUTES

120  MINUTES

120

30

OR

OR

OR

60

90

DIP SWITCH SETTINGS

1

2

3

QUIET

SHFT

ON

OFF

(DEFAULT)

 

FLASH 

CODE

 

FAULT DEFINITION

 

On, No Flash

 

Standby

 

 

 

1, Pause

 

Normal Operation

 

16

 

System Communications Failure

 

 

 

31

 

High Pressure Switch

 

45

 

Control Fault

 

46

 

Brown out (24V)

 

53

Outside Temp Sensor

FLASH 

CODE

 

FAULT DEFINITION

 

72

 

Thermal Cutout

 

73

 

Contactor Shorted

 

74

 

No 230V at Compressor 

 

 

 

 

 

 

 

 

 

 

 

82

Thermal lockout

83

Low pressure lockout

84

High pressure lockout

32

Low Pressure Switch

55

Coil Temp  Sensor

56

Thermistor Range Error

1.  Compressor and fan motor furnished with inherent thermal protection.
2.  To be wired in accordance with national electric code (N.E.C.) And local codes.
3.  N.E.C. Class 2, 24 V circuit, min. 40 VA required, 60VA on units installed with LLS.
4.  Use copper conductors only from disconnect to units suitable for at least 75ºC (167ºF).
5.  Must use thermostat and sub-base as stated in pre-sale literature.
6.  If indoor section has a transformer with a grounded secondary, connect the Grounded 
     side to "C" on the circuit board.
7.  If any of the original wire, as supplied, must be replaced, use the same or 
     Equivalent wire.
8.  Check all electrical connections inside control box for tightness.
9.  Do not attempt to operate unit until service valves have been opened.
10. Symbols are electrical representation only.
11. When start relay and start capacitor are installed, start thermistor is not used.
12. For communicating control only.
13. In case of non-communicating Indoor system, disconnect factory provided wires 
     from A, B, C, and D terminals.  Using factory provided wires connect to R, C, Y, W2, 
     and O terminals as required by Installation Instructions.  Connect field 24V wires to 
     factory provided wires, cap or remove unused factory provided wires.

THIS DEFROST CONTROL 

BOARD CONTAINS A FIVE 

MINUTE SHORT CYCLE 

PROTECTOR.  A FIVE 

MINUTE DELAY WILL 

OCCUR BETWEEN 

COMPRESSOR OFF/ON 

CYCLES.

NOTE

+t°

* ST

* CHS

* CH

23

R

C

S

5

2

1

L1

ODF

ODFR

L2

23

CONT

ODF

CAP

F

C

COMP

H

*SC

* SR

GND

EQUIP

21

11

L1

CONT

C

* HPS

C

RVS

R

W2

O

RVSR

AUXR

LLSR

CONT

OAT

OCT

LPS

INPUT

OUTPUT

L

O
G

I

C

ODFR

RVSR

AUXR

LLSR

K4

LS

Y

L1
VS
VR

A BCD

CB

K4

SEE NOTE #12

YEL / BLU

COMP

ODF

S

C

R

RED or BLK

CONT

208/230 1Ø

POWER

SUPPLY

EQUIP  GND

L1

L2

BLU

CAP

H

C

F

*ST

+t

BLU

YEL

YEL

*SC

*CHS

*SR

(NOTE #8)

1

2
5

*C

H

BLK

BLK

or

RED

BLK

BRN

BLK

BRN / YEL

CC

1

3

LPS

1

HPS

1 2

2

VS

VR

L1

ODF

* LPS

1

2
3
4
5

OCT

OAT

* HPS

OCT

OAT

DEFROST

TIME

FORCED

DEFROST

COMM

STATUS

UTIL

3

2

C

RVS

TO  INDOOR UNIT

PL5

YEL/PNK

BRN

BRN

BLK

BLK

YEL/PNK

BLU/PNK

BLU/PNK

PL4

PL3

PL2

QUIET

SHIFT

4

HP

PL1

ORG

ORG

RVS

BLU

P1

CB

BRN

YEL

BLK

YEL

BLU

11

21

23

23

C

C

R C Y

LS W2 O

OPTIONAL 

NON-COMMUNICATING

CONTROL

SEE NOTE #13

AS PROVIDED

BY MANUFACTURER

SEE NOTE #12

R C

Y LS W2 O

A B C D

RED

GRN

YEL

WHT

YEL

VIO

BLK

YEL

AUXR

CAP

CB

*CH

*CHS

COMP

AUXILLARY HEAT RELAY
CAPACITOR (DUAL RUN)
CIRCUIT BOARD
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR

NOTES:

SCHEMATIC DIAGRAM  (LADDER FORM)

 * MAY BE FACTORY OR FIELD INSTALLED

LEGEND

FACTORY POWER WIRING

FACTORY CONTROL WIRING

FIELD CONTROL WIRING

FIELD POWER WIRING

CONDUCTOR ON CIRCUIT BOARD

COMPONENT CONNECTION

FIELD SPLICE

JUNCTION

PLUG RECEPTACLE

 

 

 

CONNECTION DIAGRAM

1.  Compressor damage may occur if system is over charged.
2.  This unit is factory charged with R-410A in accordance with the amount shown 
      on the rating plate.  The charge is adequate for most systems using matched 
      coils and tubing not over 15 feet long. Check refrigerant charge for maximum 
      efficiency.  See Product Data Literature for required Indoor air Flow Rates and 
      for use of line lengths over 15 feet.
3.  Relieve pressure and recover all refrigerant before system repair or final 
     disposal.  Use all service ports and open all flow-control devices, including 
     solenoid valves.
4.  Never vent refrigerant to atmosphere.  Use approved 
     recovery equipment.

CAUTION

 

CONT

DFT

DR

*HPS

*LPS

LLSR

OAT
OCT

ODFR

ODF
RVS

RVSR

*SC
*SR
*ST

CONTACTOR
DEFROST THERMOSTAT
DEFROST RELAY AND CIRCUITRY
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
LIQUID LINE SOLENOID RELAY
OUTDOOR AIR THERMISTOR
OUTDOOR COIL THERMISTOR
OUTDOOR FAN RELAY
OUTDOOR FAN
REVERSING VALVE SOLENOID
REVERSING VALVE SOLENOID
RELAY START CAPACITOR
START RELAY
START THERMISTOR

339109-101 REV. A

Fig. 1 – Wiring Diagram — Model size 1.5 -- 5 tons, 208/230--1