Operation & Installation Manual RFP V2 Series
MA225 Rev 1
22 of 50
such as bells, sirens, or flashing lights, strobes and door holders etc. The contact
rating of the relays is 1A @ 12V.
3.9.3
Remote Zone Relay Board (SUB600)
The board provides a relay output clean contact and 12V
DC
non-supervised outputs
when an alarm is activated in a specific zone.
SUB600 is mounted inside a plastic base PM100 with a cover PM110. The assembly
can be mounted in any place where an output from specific zone is required. Zone
cable (3 wires) is required to connect the remote zone relay board.
3.9.4
Magnetic Door Holder Power Supply
The enclosure of RFP V2 panels has space within the cabinet to mount 24Vdc / 25W
switch mode power supply. This can be connected via the common alarm contact
on the termination board to supply 24V in normal conditions to maintain power to the
door holders.
3.10
Panel Status
The status indications of the RFP will be indicated as shown in Figure 4, page 16 for
RFP6 V2 and Figure 6 page 17 for RFP12V2/RFP18V2. The mimic display shown
in Figure 5 page 16 indicates alarm for individual Smoke/Heat Alarm, wiring from
each Alarm to the mimic panel is required as shown in Figure 14, page 39.
The status in normal, alarm, fault, etc. are shown in the next sections.
3.10.1
Normal
•
All ancillaries ‘OFF’
•
All sounders ‘OFF’
•
All yellow indicators ‘OFF’
•
All red indicators ‘OFF’
•
Only power on green indicator ‘ON’
Note: When RFP is first switched “ON”, all zone fault LEDs will illuminate for few
seconds. This is normal.
3.10.2
Zone Alarm
In the event of zone alarm, the following will occur:
•
Zone alarm indicator ‘ON’ (Red LED);
•
Panel and Smoke/Heat Alarms Sounding;
•
Ancillary outputs activated.
The red indicator will show the zone in alarm and thereby the general location of the
fire alarm. In case of false alarms see Troubleshooting in Chapter 7, page 33.
3.10.3
Zone Fault
The RFP6 main board constantly monitors the system status and upon detection of
a fault condition, the following will occur:
•
Zone fault indicator ‘ON’ (amber LED).
•
Panel Sounder sounds continuously. (Press the Sounder Silence button,
sounder will beep once every 20 second (chirp) until fault is cleared).
•
Defect Mode output (relay) activated.