Brocade FastIron GS and FastIron GS-STK Hardware Installation Guide
29
53-1001783-01
Installing a redundant power supply
2
DRAFT: BROCADE CONFIDENTIAL
FIGURE 25
DC Power Supply Connector
3
9. Connect the ground, positive, and negative wires as follows:
•
Slip the 10 AWG ground wire into the opening under the negative (—) mark until the wire is
fully in place, then use the crimper to crimp the lug snugly onto the wire. Gently pull the lug
away from the wire to verify that the lug is securely fastened.
•
Connect the -48 VDC lead to the negative (—) terminal and tighten the negative terminal
screw.
•
Connect the 48 RTN lead to the positive (+) terminal and tighten the positive terminal
screw.
•
shows how to connect the wires on a DC power supply.
1
Negative terminal screw
2
Positive terminal screw
3
48 RTN lead
4
-48 VDC lead
5
10 AWG wire
1
4
5
2
3