Blower assembly LED descriptions (Continued)
TABLE 9
LED purpose Color
Status
Recommended action
Flashing amber (on 1/2
second, then off 3.5
seconds)
Fan is disabled.
Run the
fanEnable
command to
enable the fan.
Fast-flashing amber (on
1/2 second, then off 1/2
second)
Environmental range
exceeded.
Check for out-of-bounds
environmental condition, resolve any
problems, and reseat the unit. If the
LED continues to flash, replace the
unit.
Determining the status of a WWN card
Complete the following steps to determine the status of a WWN card.
NOTE
The WWN bezel (logo plate) covers the WWN cards.
1. Enter the
chassisShow
command to display information about the WWN card. (WWN units
correspond to information specific to the WWN card.) Error messages that may indicate problems
with a WWN card are summarized in the following table.
Messages that may indicate WWN card failure
TABLE 10
Type of message
Sample error message
WWN unit fails its field-replaceable
unit (FRU) header access.
0x24c (fabos): Switch: switchname, error EM-
I2C_TIMEOUT, 2, WWN 1 I2C timed out: state 0x4
WWN unit fails to power on.
<timestamp>, [EM-1004], <sequence-number>,,
CRITICAL, <system-name>, WWN # failed to power
onor<timestamp>, [EM-1043], <sequence-number>,,
WARNING, <system-name>, Can't power <FRU Id> <state
(on or off)>.
WWN unit is being faulted.
0x24c (fabos): Switch: switchname, Critical EM-
WWN_UNKNOWN, 1, Unknown WWN #2 is being
faultedor<timestamp>, [EM-1003], 40, SLOT 7 | FFDC
| CHASSIS, CRITICAL, Brocade_DCX, WWN 2 has unknown
hardware identifier: FRU faultedor<timestamp>,
[EM-1034], <sequence-number>,, ERROR, <system-
name>, WWN # set to faulty, rc=<return code>
WWN unit is not present or is not
accessible.
0x24c (fabos): Switch: switchname, Error EM-
WWN_ABSENT, 2, WWN #1 not presentor<timestamp>,
[EM-1036], <sequence-number>,, WARNING, <system-
name>, <FRU Id> is not accessible.
Writing to the FRU history log
(
hilSetFruHistory
) has failed.
0x24c (fabos): Switch: switchname, Error EM-
HIL_FAIL, 2, HIL Error: hilSetFruHistory failed,
rc=-3 for SLOT 3
WWN unit insertion was detected.
<timestamp>, [EM-1049], <sequence-number>,, INFO,
<system-name>, FRU WWN # insertion detected.
Determining the status of a WWN card
72
Brocade DCX 8510-8 Backbone Hardware Reference Manual
53-1002180-08
Содержание DCX 8510-8
Страница 1: ...53 1002180 08 19 September 2014 Brocade DCX 8510 8 Backbone Hardware Reference Manual ...
Страница 12: ...What s new in this document 12 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 22: ...Network manageability 22 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 34: ...Installing ICL cables 34 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 148: ...Port Numbering Template 148 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 166: ...Brocade DCX 8510 Technical Specifications 166 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...
Страница 172: ...Danger Notices 172 Brocade DCX 8510 8 Backbone Hardware Reference Manual 53 1002180 08 ...