  Reinstall the heat recovery core with its filters.

 

For EVO5 700 HRV HEPA and HRV 7.1 HEPA units only

: The heat recovery core must be reinstalled BEFORE the core 

 

bracket. Reinstall the HEPA filter but before reinstalling the prefilter, look at the installation date on HEPA filter frame. If there 

 

are more than 6 months passed, discard the prefilter and install a new one, but keep the HEPA filter. 

  Reinstall the door, plug back the unit and turn it on.

 

NOTE: The unit will return to its previous setting after a 20-second delay for boot sequence.

  Reset the wall control.

VQ0083

 5.2 

R

EGULAR

 M

AINTENANCE

 

(

CONT

D

)

 5.3 

A

NNUAL

 M

AINTENANCE

Perform this maintenance on the unit when the wrench icon appears on wall control screen for the fourth time (refer to tables in 
5.1 Maintenance Cycles on previous page).

Perform steps 

 to 

 of the regular maintenance then continue with the followings:

  Allow the heat recovery core to soak for 3 hours in a solution of warm water and mild soap (dishwashing liquid). 

 

Rinse carefully, drain off water and reinstall with its filters.

 

For EVO5 700 HRV HEPA and HRV 7.1 HEPA units only:

 The heat recovery core must be reinstalled BEFORE the core 

 

bracket. Discard HEPA filter and its prefilter and replace with new ones. DO NOT FORGET TO WRITE THE INSTALLATION 

 

DATE ON NEW HEPA FILTER FRAME.

22

5. M

AINTENANCE

 

(

CONT

D

)

6. S

ERVICE

 P

ARTS

Description

Part 

Number

Qty. in EVO5 700 HRV HEPA 

and HRV 7.1 HEPA units

Qty. in EVO5 500 HRV 

and HRV 5.1 units

HEPA filter (1 per kit) 
and prefilter (2 per kit) kit

21293

1

-

Prefilter (2 per kit)

61561

1

-

Core filter

61563

2

2

All parts listed in the following table are available where you have bought your unit.

NOTE: Please note that parts not listed are not available; those parts require assembly knowledge that only manufacturer can garantee.

  Check the exterior hood; make sure there are no leaves, twigs, ice or snow that could be drawn 

 

into the vent. Clean if necessary.

VD0312

  Reinstall the door, plug back the unit and turn it on.

 

NOTE: The unit will return to its previous setting after a 20-second delay for boot sequence.

  Reset the wall control.

VQ0083

Содержание VB0310

Страница 1: ...HEPA HRV 5 1 These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA They meet ENERGY STAR requirements only when used in Ca...

Страница 2: ...ugged into a mating 3 prong grounding receptacle grounded in accordance with the national electrical code and local codes and ordinances Do not remove the ground prong Do not use an extension cord 8 D...

Страница 3: ...RTS 11 3 7 INSTALLING DUAL EXTERIOR HOOD 11 12 3 7 1 ASSEMBLING DUAL EXTERIOR HOOD 11 3 7 2 LOCATING DUAL EXTERIOR HOOD 11 3 7 3 CONNECTING TANDEM TRANSITION TO DUAL EXTERIOR HOOD 12 3 8 CONNECTING TH...

Страница 4: ...evel Homes with more than one level require at least one exhaust register at the highest level See figure at right 1 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM VH0089 Stale air coming from...

Страница 5: ...NSITION VD0118A 8 222 mm 9 248 mm The joist opening needed to install theTandem tansition included in ISKV1000 and ISKB1000 installation kits must be 9 248 mm minimum Also the maximumheightoftheTandem...

Страница 6: ...stallation date on the HEPA filter frame for future reference see illustration at right TO P DES SU S FR O N T AV A N T Ins tal dat e Da te d in sta l _ _ _ _ _ _ _ _ 212 93 F R O N T A V A N T In st...

Страница 7: ...minimum Do not ventilate crawl spaces or cold rooms Do not attempt to recover the exhaust air from a dryer or a range hood This would cause clogging of the filters and recovery module If the house ha...

Страница 8: ...level to ensure the greatest possible air circulation Keep in mind that the fresh air diffuser must be located as far as possible from the stale air diffuser If desired you can install another diffuse...

Страница 9: ...orresponding port then do the same for the exhaust air to building duct and port See illustration at right NOTE Use an insulated duct not included if the duct will have to go through a space where it...

Страница 10: ...will need two exterior hoods instead of one In this case do not use the Tandem transition go to point 3 6 2 and refer to the optional single hood enclosed instructions For each duct pull back the ins...

Страница 11: ...around the joint Compressed insulation loses its insulation properties and causes water dripping due to condensation on the exterior surface of the duct CAUTION 3 7 INSTALLING DUAL EXTERIOR HOOD Exte...

Страница 12: ...de duct will be located on top CAUTION VD0085 XMAS TREE PIN Join the end of the Tandem transition to the rear of the exterior backplate Secure with 2 Xmas tree pins and seal properly with duct tape Th...

Страница 13: ...of the LED will show on which defrost cycle the unit is set NOTE No command will be taken until the unit is fully booted 4 2 DEFROST CYCLES Five seconds after the booting sequence is done the LED 2 wi...

Страница 14: ...tic operation of the unit and or the wall control Never install more than one main wall control per ventilation unit Keep control low voltage wiring at least 1 foot 305 mm away from motors lighting ba...

Страница 15: ...artment interface Plug the unit Usetheterminalconnectorincludedintheinstallationkittoperformtheelectricalconnection for main and optional wall controls Check if all wires are correctly inserted in the...

Страница 16: ...key 4 6 1 OPERATION MODES 4 6 MAIN WALL CONTROL USE When the wall control is ON press the MODE key to choose the operation mode of the ventilation unit Operating Mode label will then appear on LCD scr...

Страница 17: ...t was in TURBO mode for this particular case the unit will get back to the mode chosen before TURBO mode When the wall control is ON no matter the operation mode pressing on TURBO key will turn the un...

Страница 18: ...AYED TEMPERATURE UNIT NOTE Prior to perform this setting the wall control must be ON Press and hold on ECO key during 4 seconds NOTE To get back to C for temperature display repeat the complete proced...

Страница 19: ...appear on screen while 25 13 will flash factory set value OR according to the displayed temperature unit chosen To enter a lower value press on ECO key to enter a higher value press the TURBO key OR 4...

Страница 20: ...ances When the wrench icon appears on wall control screen perform the required maintenance according to the unit model MAINTENANCE TABLE FOR EVO5 500 HRV AND HRV 5 1 UNITS APPEARANCE MAINTENANCE TYPE...

Страница 21: ...wall of the unit with a damp cloth then wipe with a dry one Remove dust on core using a vacuum cleaner with a soft brush attachment Wash both core filters under hot water with mild soap Rinse thoroug...

Страница 22: ...water and mild soap dishwashing liquid Rinse carefully drain off water and reinstall with its filters For EVO5 700 HRV HEPA and HRV 7 1 HEPA units only The heat recovery core must be reinstalled BEFO...

Страница 23: ...cold at the air supply grille on cold season Check if the exterior hood is not blocked specifically the top grille Set the unit in AUTO or ECO mode See Control section 4 6 1 Operation modes on pages 1...

Страница 24: ...enuine replacement parts only The manufacturer genuine replacement parts are specially designed for each unit and are manufactured to comply with all the applicable certification standards and maintai...

Отзывы: