Installation regulations

Flair 325

English

Содержание Flair 325

Страница 1: ...Installation regulations Flair 325 English ...

Страница 2: ......

Страница 3: ... switch the appliance on or off but only if supervised or if they have received clear instructions on the safe use of the appliance and understand the possible dangers on the condition that the appliance has been placed and installed in the normal position for use Children between the ages of 3 and 8 may not insert the plug into the socket nor clean or make changes to the settings of the appliance...

Страница 4: ...7 Starting appliance 24 7 1 Switching appliance on and off 24 7 2 Setting the air flow 24 7 3 Other settings for installer 25 7 4 Factory settings 25 8 Fault 26 8 1 Fault analysis 26 8 2 Display Codes 26 9 Maintenance 30 9 1 Cleaning filter 30 9 2 Maintenance 31 10 Electrical diagram 35 11 Electrical connections accessories 37 11 1 Connecting position switch 37 11 1 1 Connecting position switch wi...

Страница 5: ...n The delivery size of the heat recovery appliance type Flair consists of the following components 1 Heat recovery appliance 2 Wall mounting bracket consisting of 1x mounting bracket 2x protective caps 2x rubber strip 2x rubber rings 3 Siphon 4 Documentation set consisting of 1x installation instructions 1x occupant s instructions Brink 5 Flair 325 615674 D ...

Страница 6: ...ol The Flair 325 is available in two types the Flair 325 The Flair 325 Plus The Flair 325 Plus has compared with standard Flair 325 an extra pcb giving this more functions connection possibilities Plus version page 12 These installation instructions describe both the standard Flair 325 and the Flair 325 Plus The Flair 325 and the Flair 325 Plus are available in Left hand and Right hand versions it...

Страница 7: ...ed current excl preheater A 0 08 0 08 0 09 0 11 0 15 0 21 0 41 0 59 0 73 1 07 Max rated current incl preheater switched on A 6 Cos j 0 341 0 343 0 389 0 394 0 430 0 439 0 492 0 507 0 521 0 542 Sound power Ventilation capacity m3 h 100 150 150 200 200 250 325 Sound power level Lw A Static pressure Pa 25 25 50 50 100 150 150 Casing radiation dB A 27 34 35 40 41 46 51 Duct From dwelling db A 32 40 38...

Страница 8: ...ondensate discharge is then mounted at the right hand opening below the appliance With a right hand version the warm connections 1 3 are on the right hand side of the appliance Left hand version All dimensions in millimeters Diameter of all collars is 160 mm 1 To dwelling 2 To outside 3 From dwelling 4 From outside 5 Electrical connections 6 Siphon connection 7 Exhaust air filter 8 Supply air filt...

Страница 9: ...ns in millimeters Diameter of all collars is 160 mm 1 To dwelling 2 To outside 3 From dwelling 4 From outside 5 Electrical connections 6 Siphon connection 7 Exhaust air filter 8 Supply air filter 9 Mounting Brink 9 Flair 325 615674 D ...

Страница 10: ... USB connector X13 13 Motor bypass valve 3 Service connector 14 Exhaust air filter 4 LED indicator 15 Bypass valve 5 Maximum protection preheater 16 Power cable 230 volt 6 Preheater 17 Relay output X19 7 Temperature sensor 18 24 volt connector X18 8 Supply filter 19 eBus connector X17 9 Exhaust fan 20 24 volt connector X16 10 Siphon connector 21 Modbus Brinkbus connector X15 11 Supply ventilator 2...

Страница 11: ...esirable to supply cooler outside air The warm air in the dwelling is then replaced as much as possible by cooler outside air The bypass valve opens and closes automatically when a number of conditions are met see table below for bypass conditions Follow step numbers 2 1 to 2 6 in the settings menu in the user interface Setting values standard appliance page 51 in order to adjust the operation of ...

Страница 12: ...trol board with more connections for various applications This extra control board is located in a plastic housing behind the existing control board on top of the appliance It is also possible to remove the entire Plus pcb including casing from the appliance and mount it on for example a wall separate from the heat recovery appliance this can be handy in certain circumstances such as a poor WiFi s...

Страница 13: ...stallation the appliance must be mounted to a solid wall with a minimum mass of 200 kg m2 A gypsum block or metal stud wall does not suffice Additional measures such as double panelling or extra studs are required in that case On request a mounting support for floor mounting with the same minimal mass is available In addition the following aspects must be taken into account The appliance must be i...

Страница 14: ...It is recommended to use a 32 mm connection with gasket HT DN32 not supplied with the appliance so that the siphon can be cleaned easily in the future Important During assembly always apply a lubricant such as acid free vaseline to the rubber sealing ring in the gasket This gasket connection has to be disconnected when servicing the appliance The siphon must not be glued to the condensate discharg...

Страница 15: ...e The outside air supply should be arranged from the shadowed side of the dwelling preferably from the wall or an overhang The discharge duct must be fed through the roof boarding in such a way that no condensation forms in the roof boarding The discharge duct between the Flair appliance and the roof sleeve should be such that surface condensation is prevented Always use an insulated ventilation r...

Страница 16: ...h not supplied with the appliance is connected to the modular connector type RJ12 connector X14 that is placed on the rear of the display cap of the appliance Exploded view of appliance page 10 For connection examples of multiple switch Connecting position switch page 37 A wireless remote control Connecting wireless remote control without filter indication page 39 and a combination of multiple swi...

Страница 17: ...ensor see Connecting humidity sensor page 43 5 5 6 BrinkBus Connection The Modbus Brinkbus red connector X15 can for example be used for coupling appliances Coupling appliances using BrinkBus page 18 The function of this connector can be adjusted using step number 14 1 to 14 4 in the settings menu If the appliance is fitted with a Plus pcb then this red connector X15 is also in use for connecting ...

Страница 18: ...2 X15 3 a twisted pair cable is also preferred with shorter lengths For M master Step no 8 1 Master Step no 14 1 Brink Bus For S1 Slave 1 Step no 8 1 Slave Step no 14 1 Brink Bus For S2 Slave 2 Step no 8 1 Slave Step no 14 1 Brink Bus A Multiple switch B 3 pole connector red C Modular cable D 3 core low voltage cable M Master appliance S1 S2 Slave appliances connect maximum of 10 appliances via Br...

Страница 19: ...e selected ventilation flow rate In this example the active ventilation flow rate is 100 m3 h 5 Active control 6 Filter message only displayed if applicable 7 Fault only displayed if applicable 8 Access to settings menu 9 Access to information menu Filter message and fault message are located in the same place on the display fault display has a higher priority and so will always be shown first eve...

Страница 20: ... this menu you can change the various values For all setting values of standard appliance Setting values standard appliance page 51 The Plus version of the appliance has various setting values Setting values appliance with Plus pcb page 54 Caution Incorrect settings can disrupt the operation of the appliance Use these arrows to go up or down the various menus or to increase or decrease the values ...

Страница 21: ...tting step number 15 8 to yes Control using humidity sensor Control using CO2 sensor Control using demand driven ventilation Break contact active or make contact active This appliance is set as Master appliance if a number of appliances are connected cascade Appliance is set as Slave appliance maximum of 9 appliances can be connected to a Master Control via eBus for example Brink Air Control Contr...

Страница 22: ...Zone no Symbol on display Description 4 Internet connection Signal strength USB connection active 5 11 07 Current time 6 02 11 17 Current date Flair 325 615674 D ...

Страница 23: ...eturn button takes you back 1 step in the menu Briefly press the display shorter than 5 seconds to switch on the display backlight without changing anything in the menu the display lights up for 2 minutes By pressing one of the quarter circles on the main screen the ventilation mode can be quickly adjusted The ventilation mode that has be set in this way remains active for half an hour this is vis...

Страница 24: ...tage from the appliance by pulling the power plug 7 2 Setting the air flow Good ventilation contributes to healthy air in the home optimal comfort and the proper functioning of the installation The air flows of the appliance have been set in the factory as follows 50 100 150 and 250 m3 h The performance and the energy consumption of the appliance depend on the pressure drop in the duct system as w...

Страница 25: ...ngs menu Warning As changes in the settings menu can disrupt the proper functioning of the appliance changes of settings not described here require consultation with Brink Climate Systems B V Incorrect settings may seriously affect the proper performance of the appliance 7 4 Factory settings It is possible to simultaneously revert all the changed settings back to the factory settings All changed s...

Страница 26: ...d a serious locking fault for which both fans are switched off 8 2 Display Codes Non locking fault When the appliance detects a non locking fault it will keep running limitedly The permanently lighted display shows the fault symbol Press the fault symbol for an explanation solution to the fault The screen can be left by pressing the Home button If a fault cannot be solved please contact the instal...

Страница 27: ... both fans are shut down but there is still something shown on the display of the appliance Fault code Sub code Cause Appliance action User action E190 E1000 Self test not good No action E152 E1001 Flash memory faulty Stop appliance if possible Replace basic pcb UWA2 B E153 E1002 EEPROM memory defective Appliance goes to factory setting fan setting 2 Replace basic pcb UWA2 B E105 E1011 Requested s...

Страница 28: ...hen voltage is again put back on appliance E120 E2100 EBus fault general fault message Brink Air Control and other accessories connected to eBus do not work Appliance is working Check wiring to accessories Brink Air Control Check accessories Brink Air Control and replace if defective If there is still a fault after this Take voltage from appliance and replace basic pcb UWA2 B E121 E2200 BrinkBus g...

Страница 29: ...t yet been remedied Replace external preheater Put voltage back on appliance Fault has automatically been reset E172 E2800 External postheater or fuse defective general fault message No postheater comfort control responds differently Uncouple postheater and check postheater fuse replace fuse if defective Has the fault not yet been remedied Replace external postheater Put voltage back on appliance ...

Страница 30: ...menu have been followed and confirmed then the filter wizard is closed by pressing the Home button and the display then returns to the main screen the filter message is reset and the filter message now disappears Comment If the filter wizard is opened in order to replace the filter whilst there is no filter message on the display screen go in the settings menu to step number 4 2 to open the filter...

Страница 31: ...ning the heat exchanger and fans Dependent on the conditions this must done about once every three years 1 Remove the power supply by pulling out the plug Open the filter door 2 Remove the two filters 3 Remove the front cover Brink 31 Flair 325 615674 D ...

Страница 32: ...the foam parts in the appliance 5 Wash the heat exchanger with hot water max 45 C and a regular detergent Then rinse the exchanger with hot water 6 Take EPS assembly with which the fan is inserted into the appliance out of the appliance Flair 325 615674 D ...

Страница 33: ...rter of a revolution in the appliance 8 Tilt the fan in such a way that this can be taken out of the EPS assembly disconnect both fan cables from the fan 9 Now take the fan out of the appliance Brink 33 Flair 325 615674 D ...

Страница 34: ...ance when doing so take care that the EPS parts and rails in the appliance are not damaged which could otherwise leads to internal leaks in the appliance Take care when returning the heat exchanger that the text on the type plate is not upside down Place the heat exchanger back such that this type plate is visible 14 Put the front cover back on and screw it secure 15 Install two new filters and cl...

Страница 35: ...10 Electrical diagram Brink 35 Flair 325 615674 D ...

Страница 36: ...d driven ventilation 2 0 option X14 Analoog output 0 or 10 V 19 Plus pcb UWA2 E option X15 Analoog output 2 0 or 10 V 20 Connection on ModBus system option X16 NTC 10K 21 X12 is Jumper terminating resistance 120 W ModBus remove if terminating resistance has already been placed in ModBus system With Modbus application remove the jumpers X121 X122 when using BrinkBus place the jumpers X12 X121 X122 ...

Страница 37: ...e removed in order to gain access to this modular connector Plus version page 12 Depending on the type of multiple switch that is connected one can use either an RJ11 or RJ12 plug It is best to use a 4 way switch with filter indication always install an RJ12 connector in combination with a 6 core modular cable When using a 3 way switch without filter indication always install an RJ11 connector in ...

Страница 38: ...ance B 4 way switch with filter indication C Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular cable Wire colors C1 C6 may vary dependent on the type of modular cable used Flair 325 615674 D ...

Страница 39: ...itter with 2 settings for example bathroom E Any additional 2 or 4 settings transmitters maximum of 6 transmitters can be signed on to 1 receiver F Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular cable Wire colors C1 C6 may vary dependent on the type of modular cable used Brink 39 Flair 325 615674 D ...

Страница 40: ...h filter indication B2 Extra multi switch with filter indication C Splitter D Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular cable Wire colors C1 C6 may vary dependent on the type of modular cable used Flair 325 615674 D ...

Страница 41: ...ceiver for wireless remote control D Transmitter with 2 settings or 4 settings E Splitter F Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular cable Wire colors C1 C6 may vary dependent on the type of modular cable used Brink 41 Flair 325 615674 D ...

Страница 42: ...2 Connecting Brink Air Control A Flair appliance B Brink Air Control option C Two core control cables D Green two pole screw connector E Position green eBus connector to rear of control Flair 325 615674 D ...

Страница 43: ...liance 2 Basis pcb 3 Cover 4 The cable that comes with RH cable 5 RH humidity sensor 6 Duct from dwelling To switch on and set the sensitivity of the humidity sensor go to step number 7 1 and 7 2 in the settings menu Brink 43 Flair 325 615674 D ...

Страница 44: ...ectors D CO2 sensor s connect a maximum of 4 E Connection X17 eBus and X18 24V on Flair appliance For switching the CO2 sensor s on and off select the right setting at step number 6 1 in the settings menu in order to set the minimum and maximum PPM value of the CO2 sensor s set if necessary the right values following step numbers 6 2 to 6 9 Flair 325 615674 D ...

Страница 45: ...iple switch of course remains a possibility as well For further information regarding setting operating and connecting demand driven ventilation 2 0 refer to the installation instructions supplied with the demand driven device 1 Zone valve demand driven ventilation C1 brown C2 blue C3 green yellow C5 white C10 yellow C11 green 2 Power 24 VDC 3 Brink Air Control 4 Valve motor zone valve 5 EBus conn...

Страница 46: ...1 brown C2 blue C3 green yellow C4 black C5 white 2 Maximum savety with manual reset 3 2 pole eBus connection X17 on Flair aplliance 4 Temperatur sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch setting Flair postheater Flair 325 615674 D ...

Страница 47: ...own C2 blue C3 green yellow C4 black C5 white 2 Maximum savety with manual reset 3 2 pole eBus connection X17 on Flair appliance 4 Temperatur sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch setting Flair preheater Brink 47 Flair 325 615674 D ...

Страница 48: ...he serial number the year of production and the name of the part N B Appliance type serial number and year of production are stated on the identification plate behind the plastic front panel on the appliance Example Appliance type Flair 325 Plus Serial number 430000191201 Year of production 2019 Part Fan Article code 532759 Quantity 1 Flair 325 615674 D ...

Страница 49: ...12 2 Service articles Brink 49 Flair 325 615674 D ...

Страница 50: ...532751 9 Mains plug and cable 230 V 532756 10 Internal preheater incl maximum security 532761 11 Temperature sensor NTC 10K 531775 12 Condensation discharge 532762 13 Cable set 532767 It is also possible to order filters via www brinkclimatesystems com The power cable is fitted with a circuit board connector When replacing it always order a replacement mains cable from Brink To prevent dangerous s...

Страница 51: ...2 1 4 Air flow rate setting 3 250 m h Adjustable between 50 m h and 325 m h not lower than step no 1 3 1 5 Imbalance permissible Yes Yes No 1 6 Imbalance Open fireplace 0 0 20 1 7 Offset supply 0 15 15 fan setting Value calculated back to set flow rate see screen 1 8 Offset exhaust 0 15 15 fan setting 1 19 Default fan setting 1 0 or 1 2 Bypass 2 1 Mode Bypass Automatic Automatic Bypass closed Bypa...

Страница 52: ... PPM 6 4 Min PPM eBus CO2 sensor 2 400 PPM 6 5 Max PPM eBus CO2 sensor 2 1200 PPM 6 6 Min PPM eBus CO2 sensor 3 400 PPM 6 7 Max PPM eBus CO2 sensor 3 1200 PPM 6 8 Min PPM eBus CO2 sensor 4 400 PPM 6 9 Max PPM eBus CO2 sensor 4 1200 PPM 7 Humidity sensor 7 1 Switching humidity sensor on and off Off On Off 7 2 Sensitivity of humidity sensor 0 2 most sensitive 0 basic setting 2 least sensitive 8 Casc...

Страница 53: ... Hungarian Latvian 15 2 Date format dd mm yyyy dd mm yyyy mm dd yyyy 15 3 Date 15 4 Time format 24h 12h 24h 15 5 Time 15 8 Display No Yes No Display half an hour active as multiple switch when yes is selected touchscreen permanently set as multiple switch 15 9 Back to factory settings No Yes No 15 10 Fan position wizard No Yes No 16 Signal output 16 1 Signal output Off Off Only filter condition On...

Страница 54: ...Fan off Fan runs at absolute minimum Fan at setting 1 Fan at setting 2 Fan at setting 3 Fan at step 0 Fan according to multiple switch Fan runs at absolute maximum No exhaust fan control 9 5 Make or break contact 2 Make Make Break 9 6 Switch contact control 2 Off Off On Meets Bypass conditions Open bypass valve Open external valve 9 7 Contact 2 Supply fan action Fan off Fan off Fan runs at absolut...

Страница 55: ...f 10 5 minimum voltage input 2 0V 0V 10V Connector X 13 10 6 maximum voltage input 2 10V 0V 10V 11 Geo heat exchanger 11 1 Switching on and off Off On Off 11 2 Switch temperature 1 5 C 0 0 C 10 0 C 11 3 Switch temperature 2 25 C 15 0 C 40 0 C 11 4 Mode valve 10 volt control Closed Open Closed 11 5 Valve control Relay output 1 Relay output 1 Relay output 2 Analogue output 1 Analogue output 2 Brink ...

Страница 56: ...at recovery appliance type Flair 325 Flair 325 Plus The product described above complies with the following directives 2014 35 EU low voltage directive 2014 30 EU EMC directive RoHS 2011 65 EU substances directive 2009 125 EG 1253 1254 EU EU ErP directive The product bears the CE label Staphorst 24 11 2017 M Schouten Technical Director Flair 325 615674 D ...

Страница 57: ...liance with heat recovery Fan EC fan with infinitely variable control Type of heat exchanger Recuperative plastic cross counterflow heat exchanger Thermal efficiency 91 Maximum flow rate 325m h Maximum rated power 144 5 W Sound power level Lwa 41 dB A Reference flow rate 228m h Reference pressure 50Pa Specific Power Input SEL 0 15 W m h Control factor 1 0 in combination with multiple switch 0 95 i...

Страница 58: ...Classification from 1 January 2016 SEC class Average climate zone SEC in kWh m a A Most efficient SEC 42 A 42 SEC 34 B 34 SEC 26 C 26 SEC 23 D 23 SEC 20 G Least efficient 20 SEC 10 Flair 325 615674 D ...

Страница 59: ... Recycling Sustainable materials are used in the manufacture of this appliance The packaging should be disposed of in a responsible manner and in accordance with governmental regulations Brink 59 Flair 325 615674 D ...

Страница 60: ...Brink Climate Systems BV P O Box 11 NL 7950AA Staphorst T 31 0 522 46 99 44 E info brinkclimatesystems com www brinkclimatesystems com www brinkairforlife com 615674 D ...