Operation
Operation Location to Reduce the Risk of Fire
WARNING!
Exhaust heat/gases could ignite
combustibles, structures or damage fuel tank
causing a fire, resulting in death or serious injury.
• Portable generator must be at least 5 ft. (1.5 m) from
any structure, overhang, trees, windows, doors, any wall
opening, shrubs, or vegetation over 12 in. (30.5 cm) in
height.
• Do not place portable generator under a deck or other
type of structure that may confine airflow. Smoke alarm(s)
must be installed and maintained indoors according to the
manufacturer’s instructions/recommendations.
• Carbon monoxide alarms cannot detect smoke.
• Do not place portable generator in manner other than
shown.
MUFFLER
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.