www.BrickElectric.com
Web access URL:
http://192.168.1.105/ getpara[132]=1;
Socket command text:
getpara[132]=1;
Tips:
Response 0 means: TCP Server Mode
Response 1 means: TCP Client Mode
Response 2 means: UDP mode
To set relay module to TCP Server Mode:
Web access URL:
http://192.168.1.105/ setpara[132]=0;
Socket command text:
setpara[132]=0;
EasyBus Server Local Port Number
This parameters setup the local listening port number at relay module. To read relay
module EasyBus Server Local Port Number:
Web access URL:
http://192.168.1.105/ getpara[131]=1;
Socket command text:
getpara[131]=1;
To set relay module EasyBus Server Local Port Number, for example to 5000:
Web access URL:
http://192.168.1.105/ setpara[131]=5000;
Socket command text:
setpara[131]=5000;
EasyBus Client Mode
For applications, it is better to listen at the server and let the relay module be the TCP
client and actively connecting to one server (for example, if DHCP mode is activated).
Each relay module supports only one TCP connection to server, that means only one
server can be connected in the same time.
To set relay module to TCP Client Mode:
Web access URL:
http://192.168.1.105/ setpara[132]=1;
Socket command text:
setpara[132]=1;
EasyBus Client Remote IP address
This parameter setup the remote server IP address for relay module to connect. To read
relay module EasyBus Client Remote IP address:
Web access URL: