BRI-TEK BRI0116 Скачать руководство пользователя страница 1

Product No: BRI0116

Operation

Non-Maintained

The lamp is normally off and battery on automatic charge {green LED on) when the A.C. supply is healthy. Solid 

state circuitry automatically switches the lamp on when the A.C. supply is interrupted.

Maintained

The lamp is normally on when the supply to the switched live is on. The battery is on automatic charge {green 

LED on). Lamp will switch on or remain on if A.C. supply is interrupted.

Monitoring

The green LED indicator lamp will be on continuously. It will go out if A.C. supply or charger fails

Fault Finding and Corrective Action

1

Green LED indicator not illuminated: A.C. supply is not connected or battery not connected or the 

charger has failed.

2

Unit is not meeting the required emergency duration: The fitting may need cycling. Discharge then 

recharge for full 30 hours. Retest. The battery may need replacing it emergency duration is still not 

achieved.

Battery Replacement: (N.B. Replace with BRITEK BRI0116CELL only)

1

Switch off the electricity at the mains

2

Allow batteries to fully discharge then reconnect to supply and allow charging for 30 hours

3

Test again for 3 hours, if light does not remain lit change the battery pack as follows:

a

Remove the shell from the body by easing each of the 4 lugs off the body using a 

5mm flat screwdriver

b

Unplug the battery lead from the circuit board

c

Remove the battery lead from the housing

d

Write current date on the new battery pack

e

Fit new battery pack into the housing

f

Plug battery back into circuit board

g

Refit the shell and press each of the 4 lugs to ensure they are fully located

h

Restore power and allow charging for 30 hours

I

Perform full operation check and update test record.

Guarantee

This product is guaranteed for a period of 3 year from the date of purchase. (N.B. The battery Cell BRI0116CELL is guaranteed for 4 years from assembly date which is denoted by the batch code.) 

The guarantee is invalid In the case of Improper use, tampering, removal of the Q.C. date label, installation in an improper working environment or installation not according to the current edition of the 

I.E.E. Wiring Regulations BS7671).  Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept 
responsibility for any installation costs associated with the replacement of this product  Your statutory rights are not affected. We reserve the right to alter specifications without prior notice

MAINTAINED

NON MAINTAINED

U

nsw

itch

e

d

 

S

up

p

ly

EMERGENCY
BATTERY FOR 
LED LIGHTING

Product No: BRI0116

Installation

Note: Some LED Luminaires come with a female connector to the light and a male connector to the driver. If this 

is the case disconnect the male lead from 5 & 6 and the female lead from 3 & 4 on the terminal block, and 

connect the male lead to 3 & 4 and the female lead to 5 & 6 on the terminal block.

Ensure the mains supply is isolated before attempting installation!

Please refer to the diagram above for mains supply, driver and lamp connections. 

1

Remove the lid

2

Connect the AC supply to the battery (Connection points 1 and 2) on an externally fused supply

3

Connect the LED Indicator to the green (Connection points 7 and 8) 6 pin terminal block

4

Connect the DC side of the driver (for maintained) to the top adaptor lead (if supplied)

N.B. If no connector leads are supplied connect the driver directly to the Connection points 3 & 4

5

Connect the LED Luminaire to the middle lead (if supplied)

N.B. If no connector leads are supplied connect the LED and driver directly to the Connection points 5 & 6

6

Once wiring is complete, ensure the lid is fixed in place using the screw on the base. If external 

plug and socket connectors are used without means to prevent accidental disconnection, the 

remote box should be sited so that it is protected from unauthorised disconnection.

A recessed mount can be found inside the packaging carton to assist installation of the indicator LED. Once 

installed, the indicator LED will be illuminated and the supply should be left undisturbed for a minimum of 24 

hours to charge the batteries before attempting a commissioning test. After a successful test, the date should 

be noted on the space provided on the battery. Commissioning should be recorded on the commissioning page.

EMERGENCY
BATTERY FOR 
LED LIGHTING

Dedicate AC mains

Required

DC Connection 
to the LED 
Light Fitting

LED Indicator

N

L

+

-

+

+

-

-

S

w

itc

h

ed

 S

u

pp

ly

N

L

LED Driver

+

-

+

-

+

-

LED

Light

3

4

5

6

7

8

L

N

LED

Indicator

1

2

Switched 

AC In

Switched 

DC Out

D

C

 I

n

D

C

 In

Dedicated AC Supply

N

L

+

-

+

+

-

-

N

L

+

-

+

-

+

-

LED

Light

5

6

7

8

LED

Indicator

1

2

D

C

 In

D

C

 I

n

Dedicated AC Supply

Optional.

DC Connection to LED Driver.

For maintained supply where the 

LED Light can be operated by a 

light switch or sensor

Ta

+45°C

EL

Tc

+70°C

For use with LED lighting only

For use with LED lighting only

Отзывы: