Bray 63 Series Скачать руководство пользователя страница 1

Series 63 High-Flow Solenoid Valve

Installation, Operation and Maintenance Manual

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.
The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.  

09_2020

Description

The Bray Series 63 high-flow solenoid valves have an aluminum body 

and mounting interface pattern conforming to NAMUR for direct 

installation. The Bray Series 63 is IP65 for DIN model (Figure 1) or 

NEMA 4, 4x for flying leads model (Figure 2).
The Bray Series 63 solenoid can be used either with Single Acting/Spring 

Return or Double Acting/Direct Acting actuators. Double Acting actuators 

use the 5/2 configuration (Figure 3) and requires no adapter kit. Spring 

Return actuators use the 3/2 configuration (Figure 4) and require the use 

of a conversion kit included in the package. This kit includes an airflow 

plate, O-ring seal and longer screws.

WARNING

Installation and maintenance of the solenoid valve must be carried 

out by qualified personnel only.
Electrical connections are only to be made by trained personnel and 

in accordance with the applicable regulations and standards.

Storage

Bray Series 63 is not weatherproof until the unit is properly installed, 

or all conduits and applicable port connections are sealed off and 

prepared for storage. The units may be shipped with temporary covers 

to prevent foreign matter from entering through the conduit openings; 

however, the user is responsible for replacing with the proper sealing 

plugs to support its NEMA/IP ratings.
To prevent condensation from forming inside the unit, maintain a near 

constant external temperature and store indoors in a well ventilated, 

clean, dry room. The temperature shall be between 40°F (4°C) and 85°F 

(29°C), with a relative humidity less than 70%. Store units away from 

vibration and direct sunlight exposure, and place units on a shelf or 

wooden pallet in order to protect against dampness. Keep units covered 

to protect against dust and dirt; if storing for long term, placing the 

unit inside a plastic sealed bag may be preferred.
Bray cannot accept responsibility for deterioration caused on-site once 

the cover is removed or due to improper storage.

Installation

Valves are designed to be operated within the technical characteristics 

specified on the nameplate. Bray reserves the right to change or modify 

product design without prior notice.
These valves are pilot operated and require a minimum supply air 

pressure of 22 psi (1.5 bar) to function. Do not exceed the maximum 

allowable pressure of 130 psi (9 bar). These valves are designed to 

operate with filtered air or inert gas (e.g. Nitrogen).  Operating ambient 

temperature range is -13°F to +140°F (-25°C to +60°C). 
Before mounting the solenoid spool valve assembly on the actuator, 

it must be configured for the required function.

•  For 5/2 Double Acting/Direct Acting 4-Way:

The solenoid spool valve assembly mounts directly to the actuator 

with 2 screws (#10-32 x 1 1/8” length or M5x.8 x 30mm length, 

depending on actuator drilling) screws and O-rings as shown in 

Figure 3. No conversion kit is required.

•  For 3/2 Single Acting/Spring Return 3-Way: 

Use the 4-way to 3-way conversion kit (flow plate, O-ring and 2 

longer screws (#10-32 x 1 3/8” length or M5x.8 x 35mm length, 

depending on actuator drilling). Install the kit between the solenoid 

pilot valve and actuator as shown in Figure 4. The 4-way solenoid 

configuration may be used without the conversion kit to operate 

a Single Acting actuator – and would result in an “air assisted” 

spring return action.

Connect pipes with the required functions in accordance with this 

documentation and port markings on the valve. Make sure no 

foreign matter enters the system. Use of a coalescing filter regulator 

is recommended.
Correctly support the supply piping to avoid subjecting the solenoid 

spool valve assembly to mechanical stress, when tightening, avoid 

using the valve as a lever. Use proper tools and locate wrenches as 

close as possible to the connection point. To avoid damage of the 

equipment, 

DO NOT OVER TIGHTEN

 pipe connections.

Pneumatic Connections

•  Connect supply pipes in accordance with the markings on the 

nameplate

 

- 5/2 Double Acting/Direct Acting configuration: Supply 

pressure to Port 1 (¼" NPT). Exhaust both Ports 3 and 5 
(¼" NPT). Refer to Figure 5 for the 5/2 schematic.

 

- 3/2 Single Acting/Spring Return configuration: Supply 

pressure to Port 1 (¼" NPT), Exhaust to Port 3 (¼" NPT). It 
is recommended to protect Port 5 (when not used) with a 
vented pipe plug or screen, do not plug completely. Refer 
to Figure 6 for the 3/2 schematic.

 

- NOTE: The DIN model is also available with G1/4" metric 

ports. 

Manual Override

The solenoid is equipped with a Manual Override. Please refer to Figure 

1 and 2 for the location of the manual override button.
To engage the Override, depress the red manual override button and 

rotate 90° clockwise. The override will lock in place, causing the spool 

valve to activate. The button can also be pressed to activate the spool 

momentarily.
To disengage the Override, rotate the red manual override button 

counterclockwise 90°. The manual override button will pop out, and 

the spool will deactivate and return to the normal position.

To prevent injury or damage and to ensure correct operation of the 

solenoid valve, the Manual Override button must be returned to the 

normal (disengaged) position by rotating it 90° counterclockwise.

Отзывы: