Brainchild BTC-9300 Скачать руководство пользователя страница 1

User's Manual

User's Manual

BTC-9300
Self-Tune Fuzzy / PID
Process / Temperature Controller

BTC-9300
Self-Tune Fuzzy / PID
Process / Temperature Controller

BRAINCHILD

UM93001C

Содержание BTC-9300

Страница 1: ...User s Manual User s Manual BTC 9300 Self Tune Fuzzy PID Process Temperature Controller BTC 9300 Self Tune Fuzzy PID Process Temperature Controller BRAINCHILD UM93001C...

Страница 2: ...perating procedure practice or the like which if not correctly performed or adhered to could result in personal injury or damage to or destruction of part or all of the product and system Do not proce...

Страница 3: ...pter 4 Programming the Full Function Chapter 4 Programming the Full Function 4 1 Event Input 4 2 Second Set Point 4 3 Second PID Set 4 4 Ramp Dwell 4 5 Remote Set Point 4 6 Differential Control 4 7 Ou...

Страница 4: ...sampling rate Self tune BTC 9300 is powered by 11 26 VAC VDC or 90 264 V AC supply incorporating a 2 amp control relay output and dual 2 amp alarm relays output as standard whereby second alarm can b...

Страница 5: ...ntrolled by PID UM93001C 5 Digital communications RS 485 RS 232 or 4 20 mA retransmission are available as an additional option These options allow BTC 9300 to be integrated with supervisory control s...

Страница 6: ...Up Load Disturbance PID control with properly tuned PID Fuzzy control Set point Temperature Time Figure 1 2 Fuzzy PID Enhances Control Stability Figure 1 2 Fuzzy PID Enhances Control Stability 6 UM93...

Страница 7: ...0 5V 5 Isolated 0 10V 6 Triac Output 1A 240VAC SSR 9 Special order 0 None 1 Relay rated 2A 240VAC 2 Pulsed voltage to drive SSR 5V 30mA 3 Isolated 4 20mA 0 20mA 4 Isolated 1 5V 0 5V 5 Isolated 0 10V 6...

Страница 8: ...cked When the unit leaves the factory the DIP switch is set so that TC RTD are selected for input 1 and all parameters are unlocked Lockout function is used to disable the adjustment of parameters as...

Страница 9: ...he parameter in a direct sequence Allow access to more parameters on user menu also used to Enter manual mode auto tune mode default setting mode and to save calibration data during calibration proced...

Страница 10: ...en used for 23456 2 hours since production The left diagram shows that the unit has been used for 23456 2 hours since production F BTC 9300 A1 A2 C OUT F BTC 9300 A1 A2 C OUT 10 UM93001C Figure 1 5 Di...

Страница 11: ...seconds to enter the auto tuning mode The flow chart shows a complete listing of all parameters For actual application the number of available parameters depends on setup conditions and should be les...

Страница 12: ...pt the auto tuning mode which performs ON OFF plus PID close loop control The mode transfer is governed by the priority conditions A lower priority mode can not alter a higher priority mode as shown i...

Страница 13: ...Low 200 0 C 360 0 F L L 500 0 C 900 0 F L L 100 0 60 200 0 C 360 0 F L L High High High High High SP2 PB2 TI2 TD2 O1HY A1HY A2HY PL1 PL2 COMM PROT Set point 2 Proportional Band 2 Value Integral Time...

Страница 14: ...rate 4 8 Kbits s baud rate 9 6 Kbits s baud rate 14 4 Kbits s baud rate 19 2 Kbits s baud rate 28 8 Kbits s baud rate 38 4 Kbits s baud rate 0 7 data bits 1 8 data bits 0 1 0 2 1 Even parity Odd pari...

Страница 15: ...r current input 0 20 mA linear current input 0 1V linear Voltage input 0 5V linear Voltage input 1 5V linear Voltage input 0 10V linear Voltage input Special defined sensor curve Low Low High High 0 1...

Страница 16: ...utput 2 no function 3 DC power supply module installed O2TY CYC2 O2FT Output 2 Signal Type Output 2 Cycle Time Output 2 Failure Transfer Mode 100 0 sec BPLS 18 0 0 0 1 Same as O1TY Low High A1FN Alarm...

Страница 17: ...tivated to replace SP1 PB1 TI1 TD1 Reset alarm 1 output 9 10 Disable Output 1 Output 2 Lock All Parameters 0 Event input no function 1 SP2 activated to replace SP1 2 PB2 TI2 TD2 activated to replace P...

Страница 18: ...rameter A2DV put ahead Parameter RAMP put ahead Parameter OFST put ahead Parameter REFC put ahead Parameter SHIF put ahead Parameter PB1 put ahead Parameter TI1 put ahead Parameter TD1 put ahead Param...

Страница 19: ...on continued 7 7 Table 1 4 Parameter Description continued 7 7 Calibration Mode Menu Display Mode Menu Low Low High High PVHI PVLO Historical Maximum Value of PV Historical Minimum Value of PV 19999 1...

Страница 20: ...Input Type Input Type J_TC N_TC K_TC L_TC T_TC PT DN E_TC PT JS B_TC CT R_TC Linear V mA or SPEC S_TC Range Low Range Low Range High Range High 120 C 184 F L L 1000 C 1832 F L L 1300 C 2372 F L L 200...

Страница 21: ...voltages capable of causing death are sometimes present in this instrument Before installation or beginning any troubleshooting procedures the power to all equipment must be switched off and isolated...

Страница 22: ...ile checking Care must be taken to ensure that maximum voltage rating specified on the label are not exceeded It is recommended that power of these units to be protected by fuses or circuit breakers r...

Страница 23: ...ply Connections Figure 2 4 Power Supply Connections This equipment is designed for installation in an enclosure which provides adequate protection against electric shock The enclosure must be connecte...

Страница 24: ...error is far greater than controller error and cannot be corrected on the sensor except by proper selection and replacement A A Proper sensor installation can eliminate many problems in a control sys...

Страница 25: ...grey grey red grey Table 2 1 Thermocouple Cable Colour Codes Table 2 1 Thermocouple Cable Colour Codes Colour of overall sheath Colour of overall sheath white blue blue white blue blue yellow blue bl...

Страница 26: ...produce 1 degree C temperature error Two wire RTD should be avoided if possible for the purpose of accuracy A 0 4 ohm lead resistance of a two wire RTD will produce 1 degree C temperature error 1 9 2...

Страница 27: ...iring 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 0 1V 0 5V 1 5V 0 10V 0 1V 0 5V 1 5V 0 10V 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 0 20mA or 4 20mA 0 20mA or 4 20mA Figure 2 8 Input 1 Linear Current Wiring...

Страница 28: ...rent Transformer Current Transformer Contactor CT Signal Input CT Signal Input CT94 1 1 2 DIN Rail DIN Rail Current Transformer Current Transformer 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 Fuse Mains su...

Страница 29: ...switch signal as well as an open collector signal The event input function EIFN is activated as the switch is closed or an open collector or a logic signal is pulled down Also refer to for event input...

Страница 30: ...3 6 14 7 15 8 16 Load 120V 240V Mains Supply 120V 240V Mains Supply _ SSR 30mA 5V Pulsed Voltage 30mA 5V Pulsed Voltage Internal Circuit Internal Circuit 5V 0V 6 5 33 33 Pulsed Voltage to Drive SSR Pu...

Страница 31: ...Linear Current Linear Current Maximum Load 500 ohms Maximum Load 500 ohms Minimum Load 10 K ohms Minimum Load 10 K ohms 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 Max 1A 240V Max 1A 240V Load Triac Triac...

Страница 32: ...3 6 14 7 15 8 16 Load 120V 240V Mains Supply 120V 240V Mains Supply _ SSR 30mA 5V Pulsed Voltage 30mA 5V Pulsed Voltage Internal Circuit Internal Circuit 5V 0V 4 3 33 33 Pulsed Voltage to Drive SSR Pu...

Страница 33: ...1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 Max 1A 240V Max 1A 240V Load Triac Triac SSR Output Direct Drive Triac SSR Output Direct Drive 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 0 20mA 4 20mA 0 20mA 4 20mA...

Страница 34: ...6 Alarm 1 Wiring Note Both Form A and B contacts are available for alarm 1 relay Order a correct form for alarm 1 to suit for your application Note Both Form A and B contacts are available for alarm 1...

Страница 35: ...elay Output Direct Drive Figure 2 17 Alarm 2 Wiring Figure 2 17 Alarm 2 Wiring Relay Output to Drive Contactor Relay Output to Drive Contactor 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 120V 240V Mains Su...

Страница 36: ...TX1 TX1 TX2 TX2 TX2 TX2 Terminator 220 ohms 0 5W Terminator 220 ohms 0 5W Max 247 units can be linked Max 247 units can be linked RS 232 PC SNA10A or SNA10B SNA10A or SNA10B Figure 2 18 RS 485 Wiring...

Страница 37: ...ocation of JP22 is shown in the following diagram must When you insert a RS 232 module CM94 2 to the connectors on CPU board C930 the jumper JP22 on terminal board T930 be modified as following J1 mus...

Страница 38: ...0 ohms Retransmit Current Retransmit Current The total effective resistance of parallel loads should be greater than 10K Ohms The total effective resistance of parallel loads should be greater than 10...

Страница 39: ...ogramming port is used for off line automatic setup and testing procedures only Don t attempt to make any connection to these jumpers when the unit is used for a normal control purpose Switch Unit DMM...

Страница 40: ...r Cooling Relay SSR SSRD Volt mA 4 Output 2 Cooling Relay SSR SSRD Volt mA DC Power supply 5 Alarm 1 Relay for Deviation Deviation Band Process Heater Break Loop Break Sensor Break Latch Hold or Norma...

Страница 41: ...olution 3 2 OUT1 OUT2 Types 3 2 OUT1 OUT2 Types O1TY Selects the signal type for Output 1 The selection should be consistent with the output 1 module installed The available output 1 signal types are...

Страница 42: ...the up down key to select the parameters you may not obtain all of the above parameters The number of visible parameters is dependent on the setup condition The hidden parameters for the specific appl...

Страница 43: ...ery quick response The ON OFF control may introduce excessive process oscillation even if hysteresis is minimized to the smallest If ON OFF control is set ie PB1 0 TI1 TD1 CYC1 OFST CPB and PL1 will b...

Страница 44: ...direct action The other functions for control control and control are same as descriptions in section 3 4 for heat only control except that the output variable and action for the cool control is inve...

Страница 45: ...s recommended to use PID control for the Heat Cool control to produce a stable and zero offset process value O1TY CYC1 O2TY CYC2 A2SP A2DV O1TY O2TY are set in accordance with the types of OUT1 OUT2 i...

Страница 46: ...and auto tuning procedures decrease CPB increase CPB Adjustment of CPB is related to the cooling media used For air is used as cooling media adjust CPB at 100 For oil is used as cooling media adjust...

Страница 47: ...available for alarm 2 Example Example UM93001C 47 Error Code Error Code Alarm 1 or alarm 2 can be configured as dwell timer by selecting TIMR for A1FN or A2FN but not both otherwise will appear As the...

Страница 48: ...f 8 functions can be selected for process alarm These are PV1 H PV1 L PV2 H PV2 L P1 2 H P1 2 L D1 2 H D1 2 L When the PV1 H or PV1 L is selected the alarm examines the PV1 value When the PV2 H or PV2...

Страница 49: ...plied to alarm 2 205 205 195 195 205 205 195 195 205 205 210 210 210 210 210 210 210 210 205 205 205 205 205 205 195 195 195 195 195 195 195 195 ON OFF ON Figure 3 7 Holding Process Alarm Figure 3 7 H...

Страница 50: ...alarm 2 A hysteresis value A1HY or A2HY can be selected to avoid interference problem of alarm in a noisy environment Normally A1HY and A2HY can be set with a minimum 0 1 value Trigger levels of alar...

Страница 51: ...Code A deviation band alarm presets two reference levels relative to set point Two types of deviation band alarm can be configured for alarm 1 and alarm 2 These are deviation band high alarm A1FN or...

Страница 52: ...A1MD NORM then Example A furnace uses two 2KW heaters connected in parallel to warm up the process The line voltage is 220V and the rating current for each heater is 9 09A If we want to detect any one...

Страница 53: ...t respond quickly as it occurs If the process value doesn t increase or decrease while the control variable MV1 has reached to its maximum or minimum value within the detecting time interval a loop br...

Страница 54: ...4 kinds of alarm modes can be selected for sensor break alarm These are Normal alarm Latching alarm Holding alarm and Latching Holding alarm However the Holding alarm and Latching Holding alarm are n...

Страница 55: ...onents in the system the sensor could not be placed any closer to the part Thermal gradient different temperature is common and necessary to an extent in any thermal system for heat to be transferred...

Страница 56: ...cts REVR and be driven ON if O1FN selects DIRT Output 2 Failure Transfer Alarm 1 Failure Transfer if activated will perform 1 If OUT2 selects COOL and BPLS is selected for O1FT then output 2 will perf...

Страница 57: ...is recovered and results in a large disturbance to the process During the sensor breaks the process loses power After bumpless transfer configured the correct control variable is applied immediately...

Страница 58: ...ff control that is PB 0 3 The controller is used for manual reset that is TI 0 4 The controller is under loop break condition 5 The controller is under failure mode e g sensor break 6 The controller i...

Страница 59: ...the process has been in steady state See Figure 3 22 Cold Start Warm Start If the auto tuning begins apart from the set point Cold Start the unit enters As the process reaches the set point value the...

Страница 60: ...et point warm start the unit passes the warm up cycle and enters the waiting cycle Afterward the procedures are same as that described for cold start Auto Tuning Error Auto Tuning Error If auto tuning...

Страница 61: ...PID values to control the process Wait and Examine the Process Wait and Examine the Process Wait and Examine the Process 0 5PB1 PB1 0 Flag 1 6PB1 PB1 0 8PB1 PB1 1 Flag 2PB1 PB1 Flag 0 Flag 1 PB1 PBu...

Страница 62: ...PID values ADJUSTMENT SEQUENCE ADJUSTMENT SEQUENCE SYMPTOM SOLUTION 1 Proportional Band P PB1 and or PB2 1 Proportional Band P PB1 and or PB2 2 Integral Time I TI1 and or TI2 2 Integral Time I TI1 and...

Страница 63: ...w TI too high TI too high Set point Set point PV Time D action D action Perfect TD too high TD too high TD too low TD too low Set point Set point UM93001C 63 Figure 3 25 Continued Effects of PID Adjus...

Страница 64: ...4 7 15 8 16 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 4 20mA 4 20mA Two line Transmitter Two line Transmitter Three line Transmitter or sensor Three line Transmitte...

Страница 65: ...troller performs open loop control as long as it stays in manual control mode The H value is exported to output 1 OUT1 and C value is exported to output 2 provided that OUT2 is performing cooling func...

Страница 66: ...ntage control value for the output 1 shows the percentage control value for the output 2 PVHI PVLO MV1 MV2 DV PV1 PV2 PB TI TD CJCT PVR PVRH PVRL PVHI PVLO MV1 MV2 DV PV1 PV2 PB TI TD CJCT PVR PVRH PV...

Страница 67: ...ry Installed CT94 1 Setup IN2 CT O1TY or O2TY RELY SSRD or SSR CYC1 or CYC2 1 sec Setup IN2 CT O1TY or O2TY RELY SSRD or SSR CYC1 or CYC2 1 sec Limitations 1 Linear output type can t be used 2 CYC1 or...

Страница 68: ...2 as the event input is activated However if alarm 2 condition is still existent the alarm 2 will be retriggered again while the event input is released RS A2 Reset Alarm 2 as the event input is acti...

Страница 69: ...trol event input Set SPMD SP1 2 and EIFN SP2 or SP P2 if the second PID is required to be used for the second set point L L Event input Event input Event input Event input 14 13 Apply Signal To Apply...

Страница 70: ...alarm 1 output is connected to event input the PID values will change from PB1 TI1 and TD1 to PB2 TI2 and TD2 If the process value exceeds a certain limit 500 C for example it is desirable to use ano...

Страница 71: ...Unit hour Unit hour Adjust Adjust RAMP Figure 4 1 RAMP Function Figure 4 1 RAMP Function A1FN or A2FN Choose A1FN or A2FN Choose TIMER TIME Dwell The Dwell timer can be used separately or accompanied...

Страница 72: ...ramp may be accompanied with a dwell timer to control the process Here is an example Example with Ramp Dwell Example with Ramp Dwell Select HRR for SPMD IN1U selects PU DP1 select 2 DP Set RAMP 60 00...

Страница 73: ...DP1 are set according to the process signal IN1L IN1H if available are set according to the process signal SPMD PV2 FUNC FULL IN2 IN2U DP2 IN2L IN2H are set according to remote signal PVMD PV1 IN1 IN1...

Страница 74: ...or PV2 PV1 Set point SP1 or SP2 PV PV1 PV2 or PV2 PV1 Set point SP1 or SP2 The PV display will indicate PV1 PV2 value if P1 2 is chosen for PVMD or PV2 PV1 value if P2 1 is chosen for PVMD If you need...

Страница 75: ...not selected for OUT2 then PL2 is If the controller is used for ON OFF control then both PL1 and PL2 are hidden hidden Operation Press for 3 seconds then press several times to reach PL1 and PL2 The P...

Страница 76: ...1 Order BTC 9300 XXXXX1 for RS 485 for RS 485 Setup Enters the setup menu Select FULL Full function for FUNC Select 485 for COMM if RS 485 is required or 232 if RS 232 is required Select RTU ie Modbus...

Страница 77: ...O and AOHI are set to map to output signal LOW SL e g 4mA and output signal High SH e g 20mA respectively The analog output signal AOS corresponding to an arbitrary value of parameter AOV is determine...

Страница 78: ...ined in setup menu The default value of FILT is 0 5 sec before shipping Adjust FILT to change the time constant from 0 to 60 seconds 0 second represents no filter is applied to the input signal The fi...

Страница 79: ...Press to leave the sleep mode 2 Disconnect the power 1 Press to leave the sleep mode 2 Disconnect the power Sleep Function can be used to replace a to reduce the system cost power switch Sleep Functio...

Страница 80: ...f the test shows that the pressure is not consumed by the process the controller will gradually decrease the power to the pump until the pump stops running As this happens the controller enters The id...

Страница 81: ...djusted as small as possible so that the controller can shut off the pump each time when all the valves are closed A typical value for REFC is between 3 and 5 5 An ordinary pump may slowly lose the pr...

Страница 82: ...oir Pressure Reservoir Providing a smoother pressure for the system Pressure Reservoir Providing a smoother pressure for the system The water pressure is required to be controlled at 10 Kg cm to achie...

Страница 83: ...IN1U PU DP1 2 DP IN1L 0 IN1H 20 00 IN2 NONE OUT1 REVR O1TY 4 20 O1FT 0 OUT2 DCPS A1FN optional EIFN NONE PVMD PV1 FILT 1 SELF NONE SLEP NONE SP1L 5 00 SP1H 15 00 SPMD PUMP SP2F DEVI Adjust the followi...

Страница 84: ...nt and stress on the load The load life is prolonged The VPFW switches the load without DC current hence minimize the harmonic current and stress on the load The load life is prolonged As the duty cyc...

Страница 85: ...r Shorter Table 5 1 Table 5 1 Function Comparison between Conventional SSR and VPFW SSR Function Comparison between Conventional SSR and VPFW SSR The output 1 and output 2 of BTC 9300 can be connected...

Страница 86: ...rs in the setup menu To achieve this function set the following parameters in the setup menu Auto Tuning is performed at 150 C for a new oven Auto Tuning is performed at 150 C for a new oven FUNC BASC...

Страница 87: ...yond the interesting range SP1L is set at 10 C and SP1H is set at 0 C The temperature is lower than the ambient a cooling action is required Hence select DIRT for OUT1 Since output 1 is used to drive...

Страница 88: ...njection mold required to be controlled at 120 C to ensure a consistent quality for the parts An oil pipe is buried in the mold Since plastics is injected at higher temperature e g 250 C the circulati...

Страница 89: ...at 250 If air is used as cooling media instead of oil the CPB is set at 100 Adjustment of DB is dependent on the system requirements More positive value of DB will prevent unwanted cooling action but...

Страница 90: ...C for 30 minutes The transition interval between high low temperature is required to be 5 minutes Make the following setup A chamber is used to test the temperature cycling effect on the personal com...

Страница 91: ...mperature for a definite time which is programmed by TIME value and then the power is shut off The temperature profile is shown in the following Figure Order a form B relay for Alarm 1 Push ON switch...

Страница 92: ...eater To Control Zone 4 Heater To Control Zone 4 Heater Master Slave Slave Slave 10 9 15 15 15 16 16 16 Figure 5 12 Figure 5 12 Remote Set Point Application Remote Set Point Application Set the follow...

Страница 93: ...Outlet From Controller Output From Controller Output 4 20 mA Valve Control Output 4 20 mA Valve Control Output Water Tank 1 Water Tank 1 Water Tank 2 Water Tank 2 Level Sensor 1 Level Sensor 1 Level...

Страница 94: ...PID2 PVMD PV1 SPMD MINR 2 Adjust the following parameters in the User menu 2 Adjust the following parameters in the User menu A1SP 800 C A1HY 1 0 C PL1 100 RAMP According to the process requirement S...

Страница 95: ...ust the following parameters in the User menu 2 Adjust the following parameters in the User menu TIME 30 0 Minutes RAMP 20 0 C Minute SP1 1000 C SP2 200 C PL1 100 L L L TIME 30 0 Minutes RAMP 20 0 C M...

Страница 96: ...e of improving the quality and productivity A cost effective solution for the above application is to use 80 units of plus a and PC based software for this purpose tile kiln BTC 9300 XXXXX1 SNA10B Sma...

Страница 97: ...the set point as well as other control parameters such as PID values down load the ramp and soak profile to the controllers execute the manual control or trigger an auto tuning etc and print out a re...

Страница 98: ...d in a file The user can program the temperature as well as other control parameters such as PID values He can setup the controller down load a ramp and soak profile also execute the manual control or...

Страница 99: ...Setup menu UNIT 1 UNIT 1 UNIT 2 UNIT 2 FUNC FULL COMM 0 5V AOFN PV1 AOLO 20 0 C AOHI 30 0 C IN1 PTDN IN1U C DP1 1 DP FUNC FULL COMM 0 5V AOFN PV1 AOLO 20 0 C AOHI 30 0 C IN1 PTDN IN1U C DP1 1 DP FUNC...

Страница 100: ...ber providing 25 C 50 C temperature range 3 A switching network SW6400 optional for automatic calibration 4 A calibration fixture equipped with programming units optional for automatic calibration 5 A...

Страница 101: ...n press scroll key for at least 3 seconds The display will blink a moment and a new value is obtained Otherwise if the display didn t blink or if the obtained value is equal to 360 or 360 then the cal...

Страница 102: ...ay didn t blink or if the obtained value is equal to 199 9 or 199 9 then the calibration fails Perform step 8 to calibrate as well as CT function if required for input 2 voltage Perform step 8 to cali...

Страница 103: ...calibrator source is set at 0 00 C with internal compensation mode 50 3 C A B Step 11 Step 11 Step 11N Step 11N The unit under calibration is powered in a still air room with temperature Stay at least...

Страница 104: ...nal contactor Burned out line fuses Burned out relay inside control Defective solid state relays Defective line switches Burned out contactor Defective circuit breakers 3 If the points listed on the a...

Страница 105: ...lues been used Dwell timer TIMR is selected for both A1FN and A2FN 7 Check and correct setup values of A1FN and A2FN Dwell timer can only be properly used for single alarm output Communication error b...

Страница 106: ...ensor wiring connections Wrong sensor or thermocouple type wrong input mode selected Analog portion of A D converter defective Check sensor or thermocouple type and if proper input mode was selected R...

Страница 107: ...10 C 700 C 346 F 1292 F 210 C 700 C 346 F 1292 F 8mV 70mV 8mV 70mV 3mA 27mA 3mA 27mA 1 3V 11 5V 1 3V 11 5V A0 05 A0 05 A0 05 A0 05 70 5 302 K 302 K 1 3 K 1 3 K 1 3 K 1 3 K Type Range Input Impedance I...

Страница 108: ...1 1V min 0 22 2mA 0 20mA or 4 20mA 0 5 55V 0 5V 1 5V 0 11 1 V 0 10V A A L A L A Resolution Accuracy Load Resistance Output Regulation Output Settling Time Isolation Breakdown Voltage Integral Linearit...

Страница 109: ...ance Dielectric Strength Vibration Resistance Shock Resistance Moldings Dimensions Weight 10 C to 50 C 40 C to 60 C 0 to 90 RH non condensing 20 Mohms min at 500 VDC 2000 VAC 50 60 Hz for 1 minute 10...

Страница 110: ...or SPP2 provided that PB2 0 Exists if EIFN selects PID2 or SPP2 provided that PB2 0 Exists if OUT2 selects COOL Exists if OUT2 selects COOL If PID2 or SPP2 is selected for EIFN then O1HY exists if PB1...

Страница 111: ...cts 4 20 0 20 0 1V 0 5V 1 5V or 0 10 Exists if IN2 selects 4 20 0 20 0 1V 0 5V 1 5V or 0 10 Exists if COMM selects 4 20 0 20 0 1V 0 5V 1 5V or 0 10 and AOFN is not MV1 and MV2 Exists if COMM selects 4...

Страница 112: ...PV1H PV1L PV2H PV2L P12H P12L D12H D12L LB or SENB Exists if EIFN selects SP2 or SPP2 or if SPMD selects PUMP Exists if EIFN selects SP2 or SPP2 or if SPMD selects PUMP Exists if A2FN is not NONE Exi...

Страница 113: ...gnal Value of Special Sensor Point 9 Signal Value of Special Sensor Point 6 Signal Value of Special Sensor Point 8 Signal Value of Special Sensor Point 7 Indication Value of Special Sensor Point 6 Ind...

Страница 114: ...pless Transfer Value OUT2 Bumpless Transfer Value 0 65535 Hours 0 0 9 Hour 0 0 FFFF FFFF 0 100 00 0 100 00 0000 007F Low Low Low Low Low Low Low High High High High High High High 0 0 000A CJCL Low Hi...

Страница 115: ...set Integral The integral function of a control that automatically compensates for the difference between the set point and the actual process temperature A signal moves the proportional band up or do...

Страница 116: ...an extended period of time Deviation alarm An offset value that follows the set point If the set point is 350 F and the Deviation alarm value is 20 F the alarm value would be 350 F plus 20 F or 370 F...

Страница 117: ...le Double Throw Utilizes the N O N C and common contacts The user has the option of wiring for a Form A or Form B contact Refer to the Form A and Form B above for more information Heat of fusion The a...

Страница 118: ...unding insulation Hi Pot test To apply a high voltage to an electrical conductor to test the surrounding insulation Hysteresis In ON OFF control the temperature change necessary to change the output f...

Страница 119: ...lectrical interference on the signal wires Noise suppression A device used to reduce electrical interference Noise suppression A device used to reduce electrical interference NIST National Institute o...

Страница 120: ...lid state SSR Solid state relay see relay solid state Tera The prefix for one trillion T Tera The prefix for one trillion T Thermal lag The time delay in the distribution of heat throughout a thermal...

Страница 121: ...on measurements Working standard A standard of unit measurement calibrated from either a primary or secondary standard which is used to calibrate other devices or make comparison measurements Zero vol...

Страница 122: ...11 13 42 45 46 51 76 89 107 108 110 Critical steady state 62 Auto tuning 11 12 43 45 46 58 59 60 61 68 70 81 86 89 91 94 97 98 105 108 Automatic calibration 100 103 Automatic programming 4 8 Baud 14 7...

Страница 123: ...ing code 7 64 77 OUT1 11 15 22 41 43 44 45 65 75 82 83 85 86 87 88 89 90 92 93 105 Linear current 15 26 27 31 33 41 Linear DC input wiring 26 Linear output 43 45 52 67 107 108 Linear voltage 15 26 27...

Страница 124: ...99 SP1 range 40 54 SP1 8 13 17 18 40 43 44 45 47 48 49 50 51 54 68 69 71 72 74 75 80 86 89 90 91 92 93 94 95 99 S Second PID 40 68 69 70 94 95 Second set point 69 107 SEL1 4 8 11 18 42 SEL2 8 11 18 42...

Страница 125: ...2 TD2 O1HY A1HY A2HY PL1 User Menu PL2 FUNC Setup Menu Setup Menu COMM PROT BAUD DATA PARI STOP AOFN AOLO AOHI IN1U IN1 DP1 IN1L IN1H IN2U DP2 IN2L IN2H IN2 ADDR Contained in Contained in Contained in...

Страница 126: ...SR1 MA1G PVHI PVLO MV1 MV2 DV PV1 126 Calibra tion Mode Menu Display Mode Menu Setup Menu Contained in Contained in Contained in Contained in Parameter Notation Parameter Notation Parameter Notation...

Страница 127: ...s option is limited to replacement or repair free of charge or refund of purchase price within the warranty period specified This warranty does not apply to damage resulting from transportation alter...

Страница 128: ...886 2 27861299 Fax 886 2 27861395 web site http www bcmfg com http www brainchild com tw 6F No 209 Chung Yang Rd Nan Kang Dist Taipei Taiwan R O C Tel 886 2 27861299 Fax 886 2 27861395 web site http...