Add Zones to Main Panel 

5

The 4 Zone Expandable Panel can be expanded to up to 32 zones with four zones on the main panel and 28 
total expansion zones. Additional zones must have power and communication wires to be recognized and 
controlled by the main expandable panel. To add additional zones, complete all wiring and start the main 
panel test mode. 

Start the panel test mode to add additional zones:

1.

 Ensure all wiring is complete, zone addresses are set (section 4), 

  and power has been applied to the main and expansion panels.

2.

 Press 

TEST

 for 3 seconds and release.

3.

 Press and release 

SELECT

 once for each new zone added. 

  New zones must be added in blocks of two. 

NOTE:

 

After second 

  new zone is added, expander LED will change from red to green, 
  and ZONE OK will appear in the main panel display.

4.

 If new zones do not appear, check wiring and ensure expansion 

  zones have power.

5.

 Press 

HOLD FOR EXIT

 for 3 seconds to complete adding zones.

Operation 

6

The Zone Panel Expander has built in LED’s to tell the installer and the system owner the current operating 
mode of the panel. Refer to the figure below and the following descriptions of the panel LED’s for operation 
information.

10

 LED 

COLOR 

INDICATION

  Panel Status LED

  

  Panel Power 

Red 

 

Flashing Red until communication is good

     

Green   

Flashing Green when in normal operation

   Thermostat LED’s (2 Positions) 

 

   R 

Red 

 

24 VAC available to Thermostat

  Y1 

Yellow  

Thermostat First Stage Compressor Call

  Y2 

Yellow  

Thermostat Second Stage Compressor Call

 W1/E/AX1 

White  

Thermostat Call for W1 or E or AX1

  W2/AX2 

White  

Thermostat Call for W2 or AX2

  O/B/W3 

Yellow  

Thermostat Call for O, B or W3

 G 

Green  

Thermostat Fan Call

  L  

Yellow   

System Check Signal to Thermostat Active

  Damper LED’s (2 Positions)

  

  Power Close / Power Open 

Red / Green 

Red On Damper Closed; Green on Damper Open

     

 

 

No light when wiring short detected.

Содержание 140424

Страница 1: ...ing for the main panel and expansion panel before applying transformer power This panel is designed for professional installation and is to be installed and configured as described in this manual Any...

Страница 2: ...tronic self resetting current limiting for panel power and damper zones Configuration Zone number by switch setting Maximum Zones 2 Zones Per Expander Panel Up to a Maximum of 14 Two Zone Expanders 32...

Страница 3: ...all stud roof truss or the return air plenum For appearance mount the panel near the main panel for easy panel to panel wiring Remove the panel cover and use the base as a template to drill mounting h...

Страница 4: ...l wiring instructions for all systems Specific wiring will vary depending on the type of thermostats and dampers used for the installation NOTE Up to 2 wires can be inserted into each terminal positio...

Страница 5: ...MPERS PO 2 OUTPUT 24 VAC Power Open Zone Damper Terminal C 2 OUTPUT Zone Damper Common Terminal PC 2 OUTPUT 24 VAC Power Close Zone Damper Terminal EXPANSION COM1 2 OUTPUT Expander Panel Communication...

Страница 6: ...Zones Located Remote to Main Panel Remote Panels Wired in Star Configuration 6 Main Panel Expander Panel Zones 5 6 Expander Panel Zones 7 8 Expander Panel As Needed Daisy Chain All Zones Located at Ma...

Страница 7: ...Damper PO C PC PO COM PC Zone Panel 3 Wire Damper 7 Thermostat Wiring 3 2 1 HEAT 1 COOL R 24 VAC Power W1 Heat Call Y1 Cooling Call G Fan Call C 24 VAC Transformer Common Note 1 2 HEAT 2 COOL R 24 VAC...

Страница 8: ...ll G Fan Call C 24 VAC Transformer Common Note 1 3 HEAT 2 COOL With Auxiliary Heat R 24 VAC Power O B Changeover Valve Note 2 L Optional System Fault Monitor AX1 Auxiliary Heat Relay 3rd Stage Heating...

Страница 9: ...ON OFF OFF OFF 9 and 10 OFF ON OFF OFF 11 and 12 OFF OFF ON OFF 13 and 14 OFF OFF OFF ON 15 and 16 ON ON OFF OFF 17 and 18 ON OFF ON OFF 19 and 20 ON OFF OFF ON 21 and 22 OFF ON ON OFF 23 and 24 OFF...

Страница 10: ...ar check wiring and ensure expansion zones have power 5 Press HOLD FOR EXIT for 3 seconds to complete adding zones Operation 6 The Zone Panel Expander has built in LED s to tell the installer and the...

Страница 11: ...the communication terminals To locate the expander panel with the invalid address view the expander panel status LED The status LED will be flashing red Duplicate Address on Expansion Panel Displayed...

Страница 12: ...opy of this warranty Visit us online www braeburnonline com warranty Phone us 866 268 5599 Write us Braeburn Systems LLC 2215 Cornell Avenue Montgomery IL 60538 5YEAR WARRANTY LIMITED Braeburn Systems...

Отзывы: