Add Zones to Main Panel
5
The 4 Zone Expandable Panel can be expanded to up to 32 zones with four zones on the main panel and 28
total expansion zones. Additional zones must have power and communication wires to be recognized and
controlled by the main expandable panel. To add additional zones, complete all wiring and start the main
panel test mode.
Start the panel test mode to add additional zones:
1.
Ensure all wiring is complete, zone addresses are set (section 4),
and power has been applied to the main and expansion panels.
2.
Press
TEST
for 3 seconds and release.
3.
Press and release
SELECT
once for each new zone added.
New zones must be added in blocks of two.
NOTE:
After second
new zone is added, expander LED will change from red to green,
and ZONE OK will appear in the main panel display.
4.
If new zones do not appear, check wiring and ensure expansion
zones have power.
5.
Press
HOLD FOR EXIT
for 3 seconds to complete adding zones.
Operation
6
The Zone Panel Expander has built in LED’s to tell the installer and the system owner the current operating
mode of the panel. Refer to the figure below and the following descriptions of the panel LED’s for operation
information.
10
LED
COLOR
INDICATION
Panel Status LED
Panel Power
Red
Flashing Red until communication is good
Green
Flashing Green when in normal operation
Thermostat LED’s (2 Positions)
R
Red
24 VAC available to Thermostat
Y1
Yellow
Thermostat First Stage Compressor Call
Y2
Yellow
Thermostat Second Stage Compressor Call
W1/E/AX1
White
Thermostat Call for W1 or E or AX1
W2/AX2
White
Thermostat Call for W2 or AX2
O/B/W3
Yellow
Thermostat Call for O, B or W3
G
Green
Thermostat Fan Call
L
Yellow
System Check Signal to Thermostat Active
Damper LED’s (2 Positions)
Power Close / Power Open
Red / Green
Red On Damper Closed; Green on Damper Open
No light when wiring short detected.