background image

®

140311

  

 3-Zone 

 Control  Panel

 

 

Installer Manual

140311-100-04

 

Warning

Read all of the instructions before proceeding

Can cause electrical shock or equipment damage. Always turn off power to the heating/
air conditioning system prior to installing or adjusting the expandable zone panel. Wire the 
entire panel before applying transformer power.
This panel is designed for professional installation, and is to be installed and configured as 
described in this manual. Any other use is not recommended and will void the warranty.
Install disconnect and overload protection on circuits as required by code authorities having 
jurisdiction for the installation.

 

 

Voltage Hazard

Caution

1 Heat / 1 Cool 
Conventional Systems

Store this manual for future reference.

P

REMIER

 

S

ERIES

Содержание 140311

Страница 1: ...nel Wire the entire panel before applying transformer power This panel is designed for professional installation and is to be installed and configured as described in this manual Any other use is not...

Страница 2: ...Current Draw Per Zone 50 VA Max 2 1 8 8 10 2 Protection Electronic self resetting current limiting for panel power and damper zones Configuration Single Stage Conventional equipment Maximum Zones 3 Z...

Страница 3: ...the base as a template to drill mounting holes see Figure 2 Attach the panel with appropriate screws Use mounting anchors as needed for drywall or plaster installations Figure 2 3 R Y W G C THERMOSTA...

Страница 4: ...depending on the equipment and type of system conventional or heat pump NOTE Up to 2 wires can be inserted into each terminal To release wires press down on top of wiring terminal and gently pull out...

Страница 5: ...r Connection Rc 1 INPUT 24 VAC Cooling Equipment Transformer Dual Transformer Systems Only Y 1 OUTPUT 1st Stage Compressor G 1 OUTPUT 1st Stage Fan Control G2 1 OUTPUT 2nd Stage Fan Control W 1 OUTPUT...

Страница 6: ...zone panel should not exceed 100 VA at 24 VAC Use a slave relay if additional damper power is required ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED Max damper VA per Zone 50 VA 24 VAC...

Страница 7: ...or dampers with a higher current draw will require the use of a separate slave relay ALWAYS PROVIDE DISCONNECT AND OVERLOAD PROTECTION AS REQUIRED 24V 24C C C HOT Dedicated Zoning Transformer Zone Pan...

Страница 8: ...r 3 seconds 2 The panel backlight will turn on and the display will change 3 Change setting if needed by pressing SELECT 4 To save and advance to the next setting press the NEXT button 5 Repeat steps...

Страница 9: ...e Supply Air Sensor Note 1 2 4 Temperature Scale DEG DEG F DEG F Select for Fahrenheit display DEG C Select for Celsius display 5 Plenum High Limit Cutout PLENUM 135 100 to 180 Select the maximum Supp...

Страница 10: ...SELECT to turn the test on and off 4 Press NEXT to move on to the next test 5 Press HOLD FOR EXIT for 3 seconds to exit test mode The following tests are available in Test Mode Heating Stage Test ON...

Страница 11: ...ed Press SELECT to test or NEXT to return to the first test LED COLOR INDICATION Panel Status LED Panel Power Green Flashing Green When Normal Equipment LED s Rh Red 24 VAC at equipment Rh Terminal Rc...

Страница 12: ...ones are calling for cooling operation FAN CALLS Number of fan calls currently being serviced Check the panel LED if it is necessary to determine exactly which zones are calling for fan operation Equi...

Страница 13: ...ation The heating stage will be turned off and the fan will be turned on until the plenum temperature returns to the normal range Service the system immediately to prevent potential damage Low Plenum...

Страница 14: ...n installed by a professional contractor this product is backed by a 5 year limited warranty Limitations apply For limitations terms and conditions you may obtain a full copy of this warranty Visit us...

Отзывы: