8

S19-323, S19-324

 Installation

11/21/2017 

Bradley • 

215-1846 Rev. C; ECN 17-05-068

4 Test the Signaling System

Testing the signaling assembly for the first time using the drench shower may expose the flow switch to 
an unnecessary water hammer since the downstream piping may be empty of water. The flow switch is 
designed to withstand such a water hammer, but using the smaller eyewash flow is recommended.

A

Apply power to the alarm branch 
circuit . The alarm should remain in 
the OFF position and the beacon and 
area light illuminate (if applicable) . 
The signal light will not illuminate .

B

Open the eyewash valve . The horn 
should sound and the signal light 
flash shortly after water flows from 
the system . If there is the optional 
beacon light, this beacon light will 
turn off once the fixture is activated 
(the signal light will stay on, flashing) . 
The area light will always stay on .

C

If present, use the auto reset on/
off switch to silence the horn during 
a flow event . Toggling the switch to 
silence mode will shut off the horn 
but allow the signal light to keep 
flashing . All units can be silenced by 
deactivating the flow .

D

Shut off the eyewash flow valve . The 
signal light should stop flashing and 
the beacon light (if applicable) will 
turn back on at a steady state .

E

Repeat steps A through D, this time 
using the drench shower only .

Discontinuing the flow will automatically 
reset the silence feature.

The alarm signaling system is designed to work 
properly even if both the eyewash and drench 
shower are used simultaneously. The alarm will 
continue to operate so long as either the eyewash 
or drench shower is still in use.

Signaling System Maintenance

The Bradley Emergency Signaling System is designed to be virtually maintenance free . An occasional damp cloth 
wiping of the clear dust cover is all that is needed to ensure maximum visual attention-getting ability . 

Remote Sensing Option

Flow Switch Capability (see supplied wiring diagram)

If remote sensing is wanted, remove the pipe plug from the back of the junction box . Connect the extra black 
wire (common to both switch arrangements) and the blue wire (normally open switch arrangement) or red wire 
(normally closed switch arrangement) to your application per local electrical codes . The switch is rated at 5 amps 
at 125/250VAC and is isolated from the contacts used by the signaling station . The customer supplied connections 
should be of a type equal to or greater than the junction box's rating to maintain the integrity of the system .

Control Box Capability (see supplied wiring diagram)

The control box is supplied with 2 sets of double pole double throw relay contacts which change state with flow . 
These contacts can be externally powered or powered by the 24VDC un-switched outputs; combined load cannot 
exceed 770mA when internal DC power is used . If contacts are externally powered, the contacts are rated for a 
maximum 160 volts at 5 amps .

Содержание S19-323

Страница 1: ...EMA 4X Emergency Signaling System Table of Contents Pre Installation Information 2 3 Components 4 5 Install Flow Switch and Mount Assembly 6 Connect Signaling Assembly to Flow Switch 7 Complete Electr...

Страница 2: ...e beginning installation and after installation is complete Test the unit for leaks and adequate water flow Main water supply should be ON at all times unless system is being serviced Provisions shall...

Страница 3: ...gency fixtures require a minimum of 30 PSI 0 21MPa flowing pressure Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing fluid supply is present and any...

Страница 4: ...1mm NPT Hub Plugged Brass Sensor Body Brass Adapter and Tee NEMA 3R Junction Box and Cover Electrical Quick Disconnect Male 3 76mm 4 11 16 119mm Red Blue Black Remote Sensing 12 3 8 315mm System is pr...

Страница 5: ...10 9 16 269mm Beacon Light Type 4X Shown Optional NPT Hub Plugged Brass Sensor Body Brass Adapter and Tee NEMA 4X Junction Box and Cover Electrical Quick Disconnect Male 3 5 16 84mm Red Blue Black Rem...

Страница 6: ...nections C Choose a location for mounting the alarm For best visibility the signaling system should be mounted at least 7 above ground level The signaling system may be mounted directly to the drench...

Страница 7: ...option determine mounting location of selector switch and size flexible cable length accordingly Hook up the wires from the provided flexible cable to control board see wiring diagram while the cover...

Страница 8: ...flow will automatically reset the silence feature The alarm signaling system is designed to work properly even if both the eyewash and drench shower are used simultaneously The alarm will continue to...

Страница 9: ...ensure the integrity of the unit G Check that the signaling station is functioning properly once the power is restored by activating the fixture attached to the signaling station S19 323 Signal Light...

Страница 10: ...Component failure Check light connections and filament in the light Area light does not operate No power to the signal station Check that the circuit breaker or fuse is supplying power to the signal...

Страница 11: ...ket Alarm Box GA 61 S90 634 1 General Area Hardware Kit Item Part No Qty Description 80 269 1421 1 Flowswitch 1 1 4 T DPDT 80 269 1522 1 Flowswitch 1 2 T DPDT 81 269 1902 1 Junction Box Conduit Outlet...

Страница 12: ...T 32 269 1316 1 Conduit Nipple 3 4 x 6 33 169 1145 1 Elbow Pulling Conduit Item Part No Qty Description 34 269 2156 1 Close Nipple 3 4 Conduit 36 269 2460 Plug 3 4 Conduit NEMA 41 229 010 1 Selector S...

Страница 13: ...C ECN 17 05 068 11 21 2017 Wiring Diagram NOTES 1 Devices in dashed boxes are optional 2 All powered devices are 24VDC 3 All wires are 18 AWG unless supplied with the device then those wires are to be...

Страница 14: ...ELAY COIL NORMALLY OPEN NORMALLY CLOSED LIGHT HORN FLOW SWITCH FLOW SENSOR COMPONENT SOLDERED WIRE LEGEND CONTACT CONTACT INTERNAL JUMPER TERMINAL BLOCK CONNECTION NORMALLY OPEN CONNECTION NORMALLY CL...

Отзывы: