S19-323, S19-324

 Installation

6/11/2020 

Bradley • 

215-1846 Rev. G: ECO 20-05-028

Troubleshooting

Problem

Cause

Solution

The signal light and horn (if 

applicable) does not operate 

when water flows .

No power to the signal station .

Check that the circuit breaker or fuse is supplying power to the 

signal station

Component failure .

Check the two 3 Amp 24VDC fuses on the print circuit board in 

the signal station enclosure .

No input power .

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure .

Water flowing in wrong 

direction for flow switch body .

Verify that the direction of the water flow corresponds to the arrow 

on the flow switch body .

Insufficient water flow .

Check that water flow is sufficient (2 .4 gallons per minute is 

required) .

Installation error

Check all electrical connections, including power supply at the 

quick-connect cable, from the signal station to the flow switch .

Horn sounds and signal light 

does not light .

Component failure .

Check light connections and filament in the light .

Area light does not operate .

No power to the signal station .

Check that the circuit breaker or fuse is supplying power to the 

signal station

Component failure .

Check the two 3 Amp 24VDC fuses on the print circuit board in the 

signal station enclosure .

No input power .

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure .

Component failure .

Check light connections and filament in the light .

Beacon light does not 

operate . (This light should 

turn off when the signal light 

turns on and back on when 

the signal light turns off .)

Fixture in use .

Make sure that the flow switch contacts are open (horn and/or 

signal light are not ON) .

Power disconnected in error .

Check that the circuit breaker or fuse is supplying power to the 

signal station .

Component failure .

Check the 3 Amp 24VDC fuses on the print circuit board in the 

signal station enclosure .

No input power .

Check that there is 24VDC being supplied from the power supply 

mounted on the print circuit board in the signal station enclosure .

Component failure .

Check light connections and filament in the light .

Содержание NEMA 3R

Страница 1: ...MA 3R S19 324 NEMA 4X Emergency Signaling System Table of Contents Pre Installation Information 2 3 Components 4 5 Install Flow Switch and Mount Assembly 6 Connect Signaling Assembly to Flow Switch 7...

Страница 2: ...e beginning installation and after installation is complete Test the unit for leaks and adequate water flow Main water supply should be ON at all times unless system is being serviced Provisions shall...

Страница 3: ...res require a minimum of 30 PSI 0 21MPa flowing pressure Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing fluid supply is present and any sediment b...

Страница 4: ...1mm NPT Hub Plugged Brass Sensor Body Brass Adapter and Tee NEMA 3R Junction Box and Cover Electrical Quick Disconnect Male 3 76mm 4 11 16 119mm Red Blue Black Remote Sensing 12 3 8 315mm System is pr...

Страница 5: ...0 9 16 269mm Beacon Light Type 4X Shown Optional NPT Hub Plugged Brass Sensor Body Brass Adapter and Tee NEMA 4X Junction Box and Cover Electrical Quick Disconnect Male 3 5 16 84mm Red Blue Black Remo...

Страница 6: ...nections C Choose a location for mounting the alarm For best visibility the signaling system should be mounted at least 7 above ground level The signaling system may be mounted directly to the drench...

Страница 7: ...termine mounting location of selector switch and size flexible cable length accordingly Hook up the wires from the provided flexible cable to control board see wiring diagram while the cover is off At...

Страница 8: ...low will automatically reset the silence feature The alarm signaling system is designed to work properly even if both the eyewash and drench shower are used simultaneously The alarm will continue to o...

Страница 9: ...ensure the integrity of the unit G Check that the signaling station is functioning properly once the power is restored by activating the fixture attached to the signaling station S19 323 Signal Light...

Страница 10: ...Component failure Check light connections and filament in the light Area light does not operate No power to the signal station Check that the circuit breaker or fuse is supplying power to the signal...

Страница 11: ...ket Alarm Box GA 61 S90 634 1 General Area Hardware Kit Item Part No Qty Description 80 269 1421 1 Flowswitch 1 1 4 T DPDT 80 269 1522 1 Flowswitch 1 2 T DPDT 81 269 1902 1 Junction Box Conduit Outlet...

Страница 12: ...32 269 1316 1 Conduit Nipple 3 4 x 6 33 169 1145 1 Elbow Pulling Conduit Item Part No Qty Description 34 269 2156 1 Close Nipple 3 4 Conduit 36 269 2460 Plug 3 4 Conduit NEMA 41 229 010 1 Selector Sw...

Отзывы: