Installation
EFX 20/S19-2150
Bradley
• 215-1809 Rev. C; ECN 18-09-010
2/28/2018
5
When the check valves are in the open (opera ting)
position, the cover screw for the stop/check stem
will be flush with the valve cap.
Check for leaks by
pressurizing unit SLOWLY.
Install Thermometer using
pipe sealant or teflon tape.
Check the temperature when approximately 10 GPM water
flow is reached (equivalent to two face washes)
Stop/Check
Cover Screw
Check
Stop Nut
Water Recirculation
Plug
Thermometer
Tempered Water
(to Fixture)
HOT
COLD
Shut the hot water supply off by closing hot water inlet valve or supply check valve. While the hot water supply is turned off, check
to make sure the cold water continues to flow. If the cold water is flowing properly, reopen the hot water supply.
Shut the cold water supply off by closing the cold water inlet valve or supply check valve. While the cold water supply is off, check
to make sure that the hot water flow has shut down. If hot water is shut down, reopen cold water supply. Test unit weekly for proper
function and desired set temperature.
This device must be checked for final temperature and adjusted as
necessary. The standard preset factory temperature setting is 85°F
(29°C). [the range of the valve is 65°F–90°F (18°C–32°C)]. Insert
Allen Wrench through the hole in the cap and into the set screw
to adjust. Consult proper medical and/or safety authorities for the
optimum temperature recommended for your particular application.
C
H
5/32" Allen Wrench
No single emergency fixture supplied by this device has a
minimum flow rate less than 1.5 GPM (5.7 L/m).
Connect Supply Lines and Install Thermometer
2
Adjust Temperature with Water Running
3
Test Unit
DO NOT SKIP THIS STEP!!!
4