Installation
EFX 125/S19-2300
Bradley
• 215-1594 Rev. E; ECN 17-09-009
12/7/2017
5
When the check valves are in the
open (opera ting) position, the cover
screw for the stop/check stem will
be flush with the valve cap.
Check for leaks by
pressurizing unit SLOWLY.
Install Thermometer using
pipe sealant or teflon tape.
Check the temperature when approximately
20 GPM water flow is reached (equivalent to
one drench shower).
Slotted Cover
Screw
Stop/Check
Cover Screw
Check
Stop Nut
Water Recirculation
Plug
Thermometer
Tempered
Water (to
Fixture)
HOT
COLD
Slotted Cover
Screw
Temperature Set
Screw
C
H
Shut the hot water supply off by closing hot water inlet valve or supply check valve. While the hot water supply is turned off, check to
make sure the cold water continues to flow. If the cold water is flowing properly, reopen the hot water supply.
Shut the cold water supply off by closing the cold water inlet valve or supply check valve. While the cold water supply is off, check
to make sure that the hot water flow has shut down. If hot water is shut down, reopen cold water supply. Test unit weekly for proper
function and desired set temperature.
This device must be checked for final temperature and
adjusted as necessary. The standard preset factory
temperature setting is 85°F (29°C). [the range of the
valve is 65°F–95°F (18°C–35°C)]. Consult proper medical
and/or safety authorities for the optimum temperature
recommended for your particular application.
5/32" Allen Wrench
Connect Supply Lines and Install Thermometer
2
Adjust Temperature with Water Running
3
Test Unit
DO NOT SKIP THIS STEP!!!
4