background image

2

E19-130

 Installation

7/18/2017 

Bradley • 

215-152E Rev. S; ECN 17-05-039

WARNING

Flush the water supply lines before beginning installation and after installation is complete. Test 

the unit for leaks and adequate water flow. Main water supply to the eyewash should be “ON” at all 

times. Provisions shall be made to prevent unauthorized shutoff.

CAUTION

Emergency equipment must be supplied with tepid water (60°F to 100°F/15.6°C to 37.8°C). Any 

prolonged exposure to near freezing water affects the body's ability to maintain body temperature, 

increasing the risk of hypothermia.

NOTICE

Before installing this product, ensure that there are adequate clearances around the product and 

activation of the product does not interfere with other products or obstructions.

Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with water after 

cleaning.

IMPORTANT

The installation and location of all safety drench showers, eye and eye/face washes must comply 

with the requirements of ANSI/ISEA Z358.1.

Read this installation manual completely to ensure proper installation, then file it with the owner or 

maintenance department. Compliance and conformity to drain requirements and other local codes 

and ordinances is the responsibility  of the installer.

Separate parts from packaging and make sure all parts are accounted for before discarding any 

packaging material. If any parts are missing, do not begin installation until you obtain the missing 

parts.

 The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley plumbed 

emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure. 

 Self-closing spring-loaded valves are not UL classified to ANSI/ISEA Z358.1.

Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable 

flushing fluid supply is present and any sediment build-up in the supply line is cleared. Emergency 

equipment should be inspected monthly to address any maintenance issues ensuring the 

equipment is in good operating condition and that there are no signs of wear.

Workers who may come in contact with potentially hazardous materials should be trained regarding 

the placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.

For questions regarding the operation or installation of this product, visit www.bradleycorp.com or 

call 800-BRADLEY (272.3539). 
Product warranties and parts information may also be found under ”Products” on our web site at 

bradleycorp.com.

Отзывы: