Standards and certifications • Safety
Automation PC 820 User's Manual V 1.00
7.5 Leakage current
7.6 Overload
7.7 Defective component
7.8 Voltage range
Test carried out
Limits according to
VDE 0701-1
Leakage current: Phase to ground
< 3.5 mA
Table 153: Test requirements - Leakage current
Test carried out according to
UL 508
Limits according to
EN 61131-2
Limits according to
UL 508
Overload of transistor outputs
50 switches, 1.5 I
N
, 1 sec
on / 9 sec off
50 switches, 1.5 I
N
, 1 sec
on / 9 sec off
Table 154: Test requirements - Overload
Test carried out according to
UL 508
Limits according to
EN 61131-2
Limits according to
UL 508
Simulation of how components in
power supply became defective
Non-flammable surrounding cloth
No contact with conductive parts
Non-flammable surrounding cloth
No contact with conductive parts
Table 155: Test requirements - Defective component
Test carried out according to
Limits according to
EN 61131-2
Supply voltage
Measurement
value
Tolerance
min/max
24 VDC
48 VDC
125 VDC
-15%
+20%
24 VAC
48 VAC
100 VAC
110 VAC
120 VAC
200 VAC
230 VAC
240 VAC
400 VAC
- 15%
+10%
Table 156: Test requirements - Voltage range
Содержание Automation PC 820
Страница 2: ...2 Automation PC 820 User s Manual V 1 00...
Страница 4: ...4 Automation PC 820 User s Manual V 1 00...
Страница 6: ...6 Automation PC 820 User s Manual V 1 00...
Страница 80: ...80 Commissioning Installation Automation PC 820 User s Manual V 1 00 Figure 26 Tightening the fastening screws...
Страница 212: ...212 Commissioning USB flash drive Automation PC 820 User s Manual V 1 00...
Страница 246: ...Model number index 246 Automation PC 820 User s Manual V 1 00...