62
EXPERT MENU (FOR QUALIFIED TECHNICIANS ONLY)
6 720 644 593 (2010/04)
9.5 Settings
The system-related programmer settings are dependent on the solar heating system configuration
chosen.
B
Check all setting options (
Æ
Section 9.1, page 55) for relevance to the selected configuration
diagram.
B
To switch to the Expert menu, press and hold the
button for 5 seconds.
B
Turn the rotary selector
to
select
Settings
and press the rotary selector
to
confirm.
B
Use the rotary selector
to select the desired setting and press the rotary selector
to
confirm.
B
To change the setting, press the rotary selector
again (setting starts flashing).
B
To change the setting, turn the rotary selector
.
B
To save the new setting, press the rotary selector
.
B
To return to the next menu up, press the
button.
9.5.1 Pump SP cut-in temperature differential
Menu: Expert menu > Settings > 1: Standard system > SP pump switch-on temp. differential
If the set cut-in temperature differential (
Δ
T) between the bottom of the solar cylinder and collector
array is reached and all conditions for switching on are met, the solar system pump starts up.
When the cut-in temperature differential for pump SP is altered, the cut-out temperature differential
for pump SP is automatically set to half the cut-in temperature differential.
WARNING:
risk of scalding if cylinder temperature limiter deactivated!
If pumps or valve settings are manually altered, all safety functions are disabled.
B
Turn off all hot water points and inform occupants of the premises of the risk of
scalding.
B
Cancel manual mode once it is no longer required.
Setting range
Default setting
New setting
7 -20 K
8 K
menu
+
-
ok
Advanced menu
Language
Time
System config.
Start solar system
Settings
+
-
ok
ok
+
-
ok