Settings in the service menu
Greenstar 8000 Style – 6720883855 (2019/01)
54
7.2.4
Function check menu
Table 20 Function check menu
7.2.5
Reset menu
Table 21 Reset menu
7.3
Thermal disinfection
To prevent hot water from becoming contaminated by bacteria such as
legionella, we recommend thermal disinfection after long downtimes.
CAUTION:
Risk of scalding.
During thermal disinfection, discharging unmixed hot water can cause
serious scalding.
▶ Only use the maximum adjustable hot water temperature for thermal
disinfection.
▶ Inform occupants of the premises of the risk of scalding.
▶ Perform thermal disinfection outside of the normal operating times.
▶ Do not discharge DHW unmixed.
Proper thermal disinfection involves the DHW system including the
draw-off points.
▶ Set the thermal disinfection in the hot water program of the heating
controller (
heating controller operating instructions).
▶ Close DHW draw-off points.
▶ Set any DHW circulation pump to continuous operation.
▶ Wait until the maximum temperature is reached.
▶ Open all DHW draw-off points, from the nearest to the one furthest
away, and draw off hot water until hot water at a minimum of 70 °C
has flown from all draw-off points for at least 3 minutes.
▶ Restore the original settings.
Menu item
Settings/adjustment range
Comment/restriction
Activate test
Burner
•
Off
...100 %
This service function enables testing of the burner.
Ignition
• On
•
Off
Permanent ignition.
Test the ignition with permanent ignition without gas
supply.
▶ To prevent damages to the ignition transformer, never
leave this function on for longer than 2 minutes.
Fan
• On
•
Off
Permanent fan operation.
Fan operation without gas supply or ignition.
Pump
• On
•
Off
Permanent pump run (internal or external pumps).
Cyl. prim. pump
• On
•
Off
Permanent pump run (hot water charge pump); only if
cylinder primary pump is installed.
3-way valve
• Hot water
•
Heating
Permanent position of the 3-way valve.
HC1 pump
• On
•
Off
Permanent HK1 pump run (downstream the low loss
header).
DHW circ. pump
• On
•
Off
Permanent hot water circulating pump run; only if hot
water circulation pump is installed.
Ionisat.oscill.
• On
•
Off
Check the ionisation measurement function at the flame.
Solar pump
• On
•
Off
Permanent pump run (solar pump).
Menu item
Settings/adjustment range
Comment/restriction
Default setting
Restore?
All settings of the heat source are reset to the respective
default setting. The system needs to be re-commissioned
following this reset.
Fault history
Reset?
Reset the maintenance first. The fault history of the heat
source is deleted. If currently a fault is present, it is
immediately entered again.