Safety equipment
39
Uni Condens 8000 F – 6720867056 (2016/10)
13
Safety equipment
Further safety accessories are listed on the Bosch Commercial and
Industrial website.
13.1
Arrangement of minimum safety equipment in
accordance with BS EN 12828:2012
Boiler
300 kW; operating temperature
105 °C; shutdown
temperature(high limit safety cut-out)
110 °C – direct heating
Fig. 43 Safety equipment in accordance with BS EN 12828:2012 for
boilers > 300 kW with high limit safety cut-out (STB) ≤ 110 °C
RK
Boiler return
VK
Flow
[1]
heat source
[2]
Shut-off valve, flow/return
[3]
Temperature controller
1)
[4]
High limit safety cut-out
1)
[5]
Temperature capturing facility
1)
[6]
Diaphragm safety valve MSV 2.5 bar/3.0 bar or
[7]
Pressure relief valve HFS ≥ 2.5 bar
[8]
Flash trap; not required in systems > 300 kW if a high limit safety
cut-out (with a limit of ≤ 110 °C) and a maximum pressure limiter
are additionally provided for each boiler.
[9]
Maximum pressure limiter
[10] Pressure meter
[11] Low water indicator; not in systems ≤ 300 kW, where instead a
minimum pressure limiter or a replacement measure approved by
the manufacturer is provided for each boiler.
[12] Non-return component
[13] Drain & fill valve (DFV)
[14] Safety pipe
[15] Shut-off valve – protected against unintentional closure, e.g. by
sealed cap valve
[16] Drain upstream of the expansion vessel
[17] Expansion vessel (EN 13831)
[18] Filling facility
[19] Suitable device for separate heating from potable water system
[20] Boiler safety assembly drain valve (manostat bar)
The figures provide a schematic representation of the safety equipment
in accordance with BS EN 12828:2012 for the system version listed
here - no claim is made as to their completeness. Practical
implementation is subject to currently applicable technical rules.
▶ Observe country-specific limits.
Low water indicator to protect against overheating
In accordance with BS EN 12828:2012, a low water indicator is
required to protect the boiler against overheating. BS EN 12828:2012
permits an approved minimum pressure limiter as an alternative to the
low water indicator.
2
11
9
20
15
6/7
12
1
8
14
15
16
17
2
1
3
RK
VK
8
0,5
%
P
1
>
3
00 kW
10
5
1)
4
1)
3
1)
001001177
8
-001
19
1) The maximum achievable flow temperature in combination with control units in
the CFB 800/CFB 900 series is around 18 K below the cut-off temperature of the
high limit safety cut-out.
The maximum achievable flow temperature in combination with control units of
the CC 8000 series is around 12 K below the cut-off temperature of the high limit
safety cut-out.