30 | RG8.0 / RG4.0 | Operation
en
6. Operation
6.1
Refrigerant recovery
6.1.1
Valve positions for normal recovery
IN
VAPOUR
LIQUID
OPEN
CLOSED
CLOSED
RECOVER
PURGE
OUT
Fig. 2:
Valve positions for normal recovery
6.1.2
Normal recovery
CLOS
ED
CLOS
ED
OPE
N
VAPOU
R
LI
Q
U
ID
PURG
E
REC
OVE
R
IN
OUT
1
2
3
4
5
6
7
8
9
10
Fig. 3:
Normal recovery
1 Liquid port/ High side port
2 A/C or refrigeration system
3 Vapour port / Low side port
4 Vapour/ Low side hose
5 Manifold gauge set with optional sight glass
6 Outlet hose.
7 Refrigerant tank.
8 Weighing scale
9 Inlet hose
10 Manguera de líquido/ lado alto
i
The sight glass provides a method of determining the
state (liquid or vapour) of the system's refrigerant and
the presence of contamination in it
1.
Disconnect the power supply to the A/C or refrigera-
tion system.
2.
Connect the RG8.0 / RG4.0 to a mains power supply
that matches the voltage and frequency rating on the
RG8.0 / RG4.0.
3.
Before making any hose connections, ensure that
A/C or refrigeration system service valves, manifold
gauge set valves, recovery unit control valves and
recovery tank valves are all in the closed position.
Also, make sure that the recovery / purge valve is in
the
RECOVER
position (pointed upwards). Refer to
Fig. 2.