Operation 27/36
RE 30220-B/05.2019, Valve amplifier VT-MRPA1,
Bosch Rexroth AG
9 Operation
Should a fault occur during operation, e.g. a power failure, the VT-MRPA1-2X can
simply be switched on again without further measures and it is then ready for
operation again.
If the VT-MRPA1-2X.. detects an error, a reaction takes place according to the table
below.
Fault
Remark
LED
(red/green)
ready
LED
(yellow)
“input”
LEDs (yellow)
“functions”
Solenoid
output
stages
Output
“ready”
Output at
test jack “v”
No error
Permanently
on green
Normal
indication
Normal
indication
Normal
operation
Normal
operation
Normal
operation
Operating voltage
UB too low
UB < UBmin
Permanently
on red
Normal
indication
Normal
indication
Switched off Switched off
7 V
Operating voltage
UB too high
UB > UBmax
Flashing
green
Normal
indication
Normal
indication
Normal
operation
Normal
operation
Normal
operation
Cable break,
command value
0..±10 V
(Ucomm = 0 V) error
cannot be recognized;
behavior of the
output stages as with
command value = 0 V
(corresponds to 0 %)
Permanently
on green
Normal
indication
Normal
indication
Normal
operation
Normal
operation
Normal
operation
Cable break,
command value
+4..20 mA
Icomm < 2 mA
Permanently
on red
Normal
indication
Normal
indication
Switched off Switched off
4 V
Overcurrent,
command value
-4..20 mA [1]
Icomm > ca. 35 mA
Permanently
on red
Normal
indication
Normal
indication
Switched off Switched off
4 V
Solenoid cable
break
Error is only
recognized when >
3.5 %
Permanently
on red
Normal
indication
Normal
indication
Normal
operation
Switched off
5 V
Break of position
transducer cable
Single wire
recognition
Permanently
on red
Normal
indication
Normal
indication
Switched off Switched off
6 V
Overcurrent
solenoid/output
stages
E.g. short-circuited
solenoid
Permanently
on red
Normal
indication
Normal
indication
Switched off Switched off
8 V
Serious error
Internal parameter
memory (EEPROM)
defective
Permanently
on red
Normal
indication
Permanently
on (all 8)
Switched off Switched off
9 V
Serious error
Main controller does
not work
Fast blinking
red & green
Fast
blinking
Fast blinking
(all 8)
Switched off Switched off
-14 V
Tabelle 9: Error evaluation
The “error“ voltage at test jack “v“ is automatically output as long as the erroneous
state persists (= LED “ready“ is permanently on red). When the above causes of
error are eliminated the amplifier module automatically resumes operation according
to its intended use.
[1] For resetting the overload protection circuit the command value has to be briefly
withdrawn from the module.
In the case of serious errors the module must be replaced.