8.2.2 Control Cables
The following requirements are applicable to the signal connection wiring:
●
Flexible cables with wire end sleeves
●
Cable cross-section: 0.5...1.0 mm
2
●
Cable cross-section for connectors with insulation sleeves: 0.75 mm
2
●
Analog inputs AI, +10 V and GND: use shielded cables
●
Digital inputs X1...X4, SC, +24 V and COM: use shielded cables
●
Analog outputs AO and GND: use shielded cables
●
RS485 communication: use shielded twisted pair cables
Recommendations on cable insulation stripping:
Please strip the insulation of control cables according to the dimensions given
below. Too long stripping may cause short circuit of adjacent cables; too short
stripping may lead to cables becoming loose.
Fig. 8-3: Cable insulation stripping length
Please follow the steps below for wiring of control terminals.
Step 1: Switch off the frequency converter before performing wiring.
Step 2: Deactivate the control signals in the wiring process.
Step 3: Switch on the frequency converter.
Step 4: Set respective parameters.
Step 5: Activate respective control signals.
VFC 3210
Bosch Rexroth AG
Frequency Converter Wiring
DOK-RCON04-VFC3210****-IT01-EN-P
35/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...