14.2.5 Communication Disruption and Response
Code
Name
Setting range
Default
Min.
Attri.
E8.01
Communication error
detection time
0.0...60.0 s (0.0: Inactive)
0.0
0.1
Stop
E8.02
Communication error
protection mode
0, 1, 2
1
–
Stop
●
When [E8.01] = 0.0 s, the disruption detection function is inactive.
●
If the interval between the current and next communication commands ex-
ceeds the time defined in [E8.01] 'Communication error detection time', the
frequency converter will reports a communication error code and act as de-
fined in [E8.02] 'Communication error protection mode':
– [E8.02] = 0: Freewheeling stop
The motor freewheels to stop after the communication timeout no matter
the settings of parameter E0.50 'Stop mode'.
– [E8.02] = 1: Keep running
The motor continues running at the setting frequency, and warning code
'C-dr' will be displayed on the operating panel.
– [E8.02] = 2: Emergency stop
The motor decelerate to stop after the communication timeout no matter
the settings of parameter E0.56 'Emergency stop action', the deceleration
time is E0.57.
VFC 3210
Bosch Rexroth AG
Communication
DOK-RCON04-VFC3210****-IT01-EN-P
189/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...