Stall overcurrent prevention
This function is used to prevent the frequency converter from overcurrent when
the load is excessively heavy or the acceleration time is excessively short. This
function is always active during acceleration or at constant speed.
Code
Name
Setting range
Default
Min.
Attri.
C0.27 Stall overcurrent prevention level
20.0 %…[C2.42]
150.0
0.1
Stop
The typical behavior of stall overcurrent during acceleration is shown as the fig-
ure below:
Fig. 12-43: Stall overcurrent during acceleration
●
[Output current] > [C0.27]
The output frequency stops increasing.
●
[Output current] < [C0.27]
The output frequency resumes increasing to the setting frequency with de-
fined acceleration time.
The typical behavior of stall overcurrent at constant speed is shown as the figure
below:
Bosch Rexroth AG
Functions and Parameters
VFC 3210
152/253
DOK-RCON04-VFC3210****-IT01-EN-P
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...