Adjust the setting frequency by multi-speed function
Multi-speed function offers flexible, switchable 16 independent stages of setting
frequency. The rotation direction of each stage depends on both the 'Stage ac-
tion' and the 'Run command source', see the table below:
Frequency source Run command source
Rotation direction
Acc. / Dec. time
Multi-speed
Operating panel
[E3.60], [E3.62], [E3.64], [E3.66]
[E3.68], [E3.70], [E3.72], [E3.74]
[E0.26] / [E0.27]
[E3.10] / [E3.11]
[E3.12] / [E3.13]
[E3.14] / [E3.15]
[E3.16] / [E3.17]
[E3.18] / [E3.19]
[E3.20] / [E3.21]
[E3.22] / [E3.23]
External terminals
8 or less stages: 2-wire control
Communication
Set by communication
Tab. 12-2: Setting frequency and multi-speed settings
To configure the multi-speed settings, take the following steps:
Step 1: Activate multi-speed function
Code
Name
Setting range
Default
Min.
Attri.
E0.00 First frequency setting source
21: Multi-speed settings
0
–
Stop
E0.02 Second frequency setting source
2
–
Stop
Step 2: Select any 3 digital inputs and define functions accordingly
Assign functions to digital inputs properly when 'Acceleration / deceleration
time activation' and '2-wire / 3-wire control mode' are also necessary defined via
digital inputs.
Code
Name
Setting range
Default
Min.
Attri.
E1.00 X1 input
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
Step 3: Configure the setting frequency for each stage
If the setting frequency of next stage is lower than that of the current stage, it
will decelerate to the next stage with the deceleration time of the current stage;
if the setting frequency of next stage is higher than that of the current stage, it
will accelerate to the next stage with the acceleration time of next stage.
VFC 3210
Bosch Rexroth AG
Functions and Parameters
DOK-RCON04-VFC3210****-IT01-EN-P
97/253
Содержание Rexroth VFC 3210
Страница 1: ...Frequency Converter VFC 3210 Operating Instructions R912007862 Edition 01 ...
Страница 18: ...Bosch Rexroth AG VFC 3210 XVI DOK RCON04 VFC3210 IT01 EN P ...
Страница 146: ...Fig 12 23 Stop DC braking Bosch Rexroth AG Functions and Parameters VFC 3210 118 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 239: ...Fig 15 2 0020 N 03 0025 N 03 VFC 3210 Bosch Rexroth AG Accessories DOK RCON04 VFC3210 IT01 EN P 211 253 ...
Страница 240: ...Fig 15 3 0008 A 05 Fig 15 4 0020 N 05 Bosch Rexroth AG Accessories VFC 3210 212 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 249: ...Fig 16 3 Assembly of the fan VFC 3210 Bosch Rexroth AG Maintenance DOK RCON04 VFC3210 IT01 EN P 221 253 ...
Страница 280: ...Bosch Rexroth AG VFC 3210 252 253 DOK RCON04 VFC3210 IT01 EN P ...
Страница 281: ...Notes VFC 3210 Bosch Rexroth AG ...