CN - CANopen
Description
Fig. 7-15:
CANopen
Connection point
Connec‐
tion point
Type
Num‐
ber of
poles
Design
multi-wired
[mm²]
Figure
X61
D‑Sub
9
Pin on de‐
vice
0.25–0.5
Tab. 7-24:
Connection point
Pin Assignment
Pin
Signal
Function
1
n. c.
-
2
CAN-L
Negated CAN signal (Dominant Low)
3
CAN-GND
Reference potential of CAN signals
4
n. c.
-
5
Drain/Shield
Shield connection
6
GND
Reference potential of device
7
CAN-H
Positive CAN signal (Dominant High)
8
n. c.
-
9
n. c.
-
Tab. 7-25:
Signal Assignment