7.5 Quick Configuration For Rexroth HM20 Pressure Sensor
For application using Rexroth HM20 pressure transducer, configuration parame-
ters of HM20 sensor can be automatically loaded by selecting the corresponding
type code in parameter F2.10. Please make sure the right analog input channel
has been set through [F2.00]...[F2.02] before setting [F2.10], since the configu-
ration parameters (AI input mode and scaling factors) will be set for the selec-
ted channel for pressure feedback.
Code
Name
Setting range
Default Min. Attri.
E1.35 AI1 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2…10 V
2
-
Run
E1.40 AI2 input mode
1
-
Run
H8.05 EAI input mode
0...4 (same as E1.35)
5: -10...10 V
0
-
Stop
H8.30 EAI2 input mode
0: 0...20 mA
1: 4...20 mA
2: 0…10 V
3: 0…5 V
4: 2...10 V
5: -10...10 V
0
-
Stop
F2.00 Analog input AI1
0: No function assigned from ASF
1: Pressure command
2: Pressure feedback
3: Flow command
4: Oxygen feedback (for myCro)
0
-
Stop
F2.01 Analog input AI2
2
-
Stop
F2.02 External analog input EAI
(-10V...10V, 4...20mA)
0
-
Stop
F2.03 External analog input EAI2
(-10V...10V, 4...20mA)
0
-
Stop
F2.06 Pressure feedback corre-
sponding to 5V, 10V or 20mA 0.1...1000.0 bar
100.0 0.1
Stop
FcP 5020
Bosch Rexroth AG
Block Diagram of Main Functions
DOK-RCON03-FCP5020****-QU04-EN-P
25/83