Rexroth IndraDrive
Status Diagnostic Messages
6-35
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
A0503 DC bus charging active
Supported by Supply Unit:
HMV01
The DC bus is presently charged to the crest value of the mains voltage
("soft start"). When the voltage in the DC bus has reached the crest value
of the mains voltage, the mains contactor is switched in.
A0503 - Attributes
Display:
charg
Mess. no.:
A0503 (hex)
A0510 Test run for voltage control
Supported by Supply Unit:
HMV01
The mains contactor has been switched in, the DC bus is regulated to
65 V. All monitoring thresholds have been adjusted for a test run at 43 V
mains voltage.
Note:
This operating status is only available for manufacturer-side
testing and developing purposes!
A0510 - Attributes
Display:
lb
Mess. no.:
A0510 (hex)
A0511 Test run for current control
Supported by Supply Unit:
HMV01
The mains contactor has been switched in, the DC bus current is
regulated with regard to a preset command value. All monitoring
thresholds have been adjusted for a test run at 43 V mains voltage.
Note:
This operating status is only available for manufacturer-side
testing and developing purposes!
A0511 - Attributes
Display:
i lb
Mess. no.:
A0511 (hex)