Command Diagnostic Messages
9-113
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3203 Incorrect input for voltage
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
List element 2 (rated voltage) in
P-0-4032, Type
plate list asynchronous motor
is outside of useful
limits
Value for rated voltage has to be between 10 V and
2000 V
C3202 - Attributes
Display:
C3202
Mess. no.:
C3202 (hex)
C3202 Incorrect input for frequency
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
List element 3 (rated frequency) in
P-0-4032, Type
plate list asynchronous motor
is outside of useful
limits
Value for rated frequency has to be between 5 Hz and
3000 Hz