9-112
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C3102 Drive is still in drive enable
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Cause
Remedy
Drive enable has been set and command
P-0-0071,
C3100 Recalculate actual value cycle
was started
To be able to carry out the command, drive enable has
to be removed
C3102 - Attributes
Display:
C3102
Mess. no.:
C3102 (hex)
C3201 Incorrect input for current
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
P-0-4033, C3200 Command
Calculate data for asynchronous motor
an error was detected.
Cause
Remedy
List element 1 (rated current) in
P-0-4032, Type
plate list asynchronous motor
is outside of useful
limits
Value for rated current has to be inside of following
limits:
rated current > 0.01 * amplifier peak current
and
rated current < 10 * amplifier peak current
C3201 - Attributes
Display:
C3201
Mess. no.:
C3201 (hex)