C0751 Parameter default value incorrect (-> S-0-0021)
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The
S-0-0262, C07_x Load defaults procedure command
with the
"load basic parameters" option was started. An error occurred when
writing a default value. The faulty parameter is displayed in S-0-0021.
Note:
The faulty parameter is recorded in the
S-0-0021, IDN list of
invalid operating data for communication phase
2
parameter.
C0751 - Attributes
Display:
C0751
Mess. no.:
C0751 (hex)
C0752 Locked with password
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
C07_1 Load defaults procedure com. (load
basic parameters)
command an error occurred.
Cause:
The drive parameters were write-protected by means of the
S-0-0267,
Password
parameter. The C0752 diagnostic message signals that the
C07_1 Load defaults procedure com. (load basic parameters)
command was started without first deactivating the customer password.
Remedy:
Deactivate the write protection by entering the password. Start the
command again.
See also Functional Description "Using a Password"
C0752 - Attributes
Display:
C0752
Mess. no.:
C0752 (hex)