Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0706 Error when reading the controller parameters
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
C07_0 Load defaults procedure com. (load
controller param.)
command an error occurred when reading the
controller parameters from the feedback.
Cause:
Feedback defective
Remedy:
Replace feedback
C0706 - Attributes
Display:
C0706
Mess. no.:
C0706 (hex)
C0722 Parameter default value incorrect (-> S-0-0021)
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The
S-0-0262, C07_x Load defaults procedure command
with the
"load defaults procedure for safety technology" option was started. An
error occurred when writing a default value.
Note:
The faulty parameter is recorded in parameter
S-0-0021, IDN
list of invalid operating data for communication phase 2
.
C0722 - Attributes
Display:
C0722
Mess. no.:
C0722 (hex)