9-44
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0158 Field bus: Tcyc (P-0-4076) incorrect
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0127, C0100 Communication
phase 3 transition check
an error with regard to the timing settings of
the master communication was detected.
Cause
Remedy
P-0-4076, Field bus: cycle time (Tcyc)
is not an
integral multiple of the position loop clock
Adjust
P-0-4076, Field bus: cycle time (Tcyc)
to
position loop clock (control section ADVANCED: 500
µ
s
or 250
µ
s, control section BASIC: 500
µ
s)
Note:
The minimum field bus cycle time [
P-0-4076, Field bus: cycle
time (Tcyc)
] is 500
µ
s for control section ADVANCED and
1000
µ
s for control section BASIC.
For removing command errors see "Command Errors"
C0158 - Attributes
Display:
C0158
Mess. no.:
C0158 (hex)
C0159 Field bus: P-0-4077 missing for cycl. command values
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0127, C0100 Communication
phase
3 transition check
an error with regard to the telegram
configuration of the master communication was detected.
Cause
Remedy
The operating data of
P-0-4081, Field bus: config.
list of cyclic command value data ch.
contains
neither
P-0-4077, Field bus: control word
nor
P-0-4068, Field bus: control word IO
. At least one
control word has to be contained.
According to profile type configure one of both control
words in
P-0-4081, Field bus: config. list of cyclic
command value data ch.
For removing command errors see "Command Errors"
C0159 - Attributes
Display:
C0159
Mess. no.:
C0159 (hex)